# 20 kVA 2200/220 V, LV-side circuit

Electrical Machine · Chapter 2: Transformer

- Asked in: 2070 Magh, 8 marks
- Video: [35. OPEN CIRCUIT TEST, SHORT CIRCUIT TEST NUMERICAL PROBLEM, FIND TRANSFORMER CIRCUIT CONSTANT](https://www.youtube.com/watch?v=PCpJF99BoZs) — Electrical Tutorial
- Answer checked by Claude Opus 5.5 (high effort) on 2026-10-14
- Page: https://www.bctengineer.com/q/semester_4/electrical_machine/transformer-20kva-2200-220-lv-side
- Whole chapter: https://www.bctengineer.com/md/semester_4/electrical_machine/chapter-2

## Question

The following test results were obtained on a 20 kVA, 2200/220 V, 50 Hz single phase transformer:
Open-circuit Test (LV Side): 220 V, 1.1 A, 125 W
Short-circuit Test (HV Side): 52.7 V, 8.4 A, 287 W
Calculate the equivalent circuit referred to L.V side and draw the equivalent circuit.

## Short answer

Referred to LV side: Ro=387.2 Ω, Xo=233.6 Ω, R02=0.0407 Ω, X02=0.0478 Ω (Z02=0.0627 Ω).

## Answer

**Given:** 20 kVA, 2200/220 V. OC test on the LV side: 220 V, 1.1 A, 125 W. SC test on the HV side: 52.7 V, 8.4 A, 287 W. The turns ratio is 2200/220 = 10. The HV (2200 V) winding is the primary, so the series values on the HV side are R01, X01 and on the LV side R02, X02.

#### Shunt branch (the OC test is on the LV side, so no transfer is needed)
```text
cos φ0 = 125/(220 × 1.1) = 0.5165
Iw = 1.1 × 0.5165 = 0.568 A
Iμ = √(1.1² − 0.568²) = 0.942 A
Ro = 220/0.568 = 387.2 Ω
Xo = 220/0.942 = 233.6 Ω
```

#### Series branch (the SC test is on the HV side, so refer it to the LV side by dividing by 10² = 100)
```text
On HV:  Z01 = 52.7/8.4 = 6.274 Ω
        R01 = 287/8.4² = 4.067 Ω
        X01 = √(6.274² − 4.067²) = 4.777 Ω
On LV:  Z02 = 0.06274 Ω ; R02 = 0.04067 Ω ; X02 = 0.04777 Ω
```

#### Equivalent circuit referred to the LV side
```text
          R02=0.0407Ω  X02=0.0478Ω
 o──┬─────┬────/\/\/────────(((──────o
    │     │                          
 387.2Ω 233.6Ω                  load
    │     │                      V2 (LV)
 o──┴─────┴───────────────────────────o
```
**Answer: Ro = 387.2 Ω, Xo = 233.6 Ω, R02 = 0.0407 Ω, X02 = 0.0478 Ω (Z02 = 0.0627 Ω), all on the LV side.**

## Check yourself

The answer's key points as multiple-choice questions, with the correct option and why.

1. Why are Ro = 387.2 Ω and Xo = 233.6 Ω used directly for the LV-side circuit?
   A. Because the OC test was done on the LV side
   B. Because they are small
   C. Because K = 1
   D. Because they are series parameters
   Answer: A. OC test on LV side gives LV-side values. (Key point: Shunt branch no transfer)

2. How is the HV-side SC impedance referred to the LV side when K = 10?
   A. Divide by 10
   B. Multiply by 100
   C. Multiply by 10
   D. Divide by 100
   Answer: D. Z01 = Z02/K² = Z02/100. (Key point: Referring series to LV)

3. What is R01 referred to LV?
   A. 4.067 Ω
   B. 0.4067 Ω
   C. 0.00407 Ω
   D. 0.0407 Ω
   Answer: D. R02 = 4.067 Ω divided by 100 gives 0.0407 Ω. (Key point: R01 value)

## Related in Electrical Machine

- [20 kVA 2200/220 V tests, equivalent circuit LV side](https://www.bctengineer.com/question.md?key=semester_4%2Felectrical_machines%3Atf-20kva-2200-220-lv-equivalent) — Electrical Machines, chapter 2
- [Equivalent circuit of 20 kVA 220/2200 V transformer](https://www.bctengineer.com/question.md?key=semester_4%2Felectrical_machines_i%3Aoc-sc-20kva-220-2200-primary) — Electrical Machines I, chapter 2
- [20 kVA 2200/220 V tests, efficiency](https://www.bctengineer.com/question.md?key=semester_4%2Felectrical_machine%3Atransformer-20kva-2200-220-primary) — Electrical Machine, chapter 2
- [Equivalent circuit of 100 kVA 2200/220 V transformer](https://www.bctengineer.com/question.md?key=semester_4%2Felectrical_machines_i%3Aoc-sc-100kva-2200-220-hv) — Electrical Machines I, chapter 2, asked 3×
- [8 kVA 400/120 V tests, parameters on HV side](https://www.bctengineer.com/question.md?key=semester_4%2Felectrical_machines%3Atf-8kva-400-120-efficiency-hv) — Electrical Machines, chapter 2
- [Equivalent circuit, efficiency and regulation of 5 kVA transformer](https://www.bctengineer.com/question.md?key=semester_4%2Felectrical_machines_i%3Aoc-sc-5kva-220-400-lv) — Electrical Machines I, chapter 2

## Related in other subjects

- [Design: 125 kVA single phase transformer](https://www.bctengineer.com/question.md?key=semester_5%2Felectric_machine_design%3Adesign-125kva-single-phase-windings) — Electric Machine Design, chapter 3, asked 3×
- [Equivalent circuit and half-load efficiency of 50 kVA transformer](https://www.bctengineer.com/question.md?key=semester_4%2Felectrical_machines_i%3A50kva-2500-250-test-secondary-half) — Electrical Machines I, chapter 2
- [Design: 100 kVA 2200/480 V single phase transformer](https://www.bctengineer.com/question.md?key=semester_5%2Felectric_machine_design%3Adesign-100kva-single-phase-ducts) — Electric Machine Design, chapter 3, asked 3×
- [20 kVA 250/2500 V tests, equivalent circuit](https://www.bctengineer.com/question.md?key=semester_4%2Felectrical_machines%3Atf-20kva-250-2500-parameters) — Electrical Machines, chapter 2, asked 2×