# 20 kVA 2200/220 V tests, efficiency

Electrical Machine · Chapter 2: Transformer

- Asked in: 2073 Bhadra, 8 marks
- Video: [Transformer OC test and SC test problems | effeciency, voltage regulation calculations](https://www.youtube.com/watch?v=aB2j_Fqd4zo) — The PiSquare Academy
- Answer checked by Claude Opus 5.5 (high effort) on 2026-10-14
- Page: https://www.bctengineer.com/q/semester_4/electrical_machine/transformer-20kva-2200-220-primary
- Whole chapter: https://www.bctengineer.com/md/semester_4/electrical_machine/chapter-2

## Question

The following test results were obtained on a 20 kVA, 2200/220 V, 50 Hz single phase transformer
Open circuit test: 220 V, 1.1 A, 125 W
Short circuit test: 52.7 V, 8.4 A, 287 W
i) Calculate the equivalent circuit parameters referred to primary side and draw the equivalent circuits
ii) Calculate maximum efficiency at full load
iii) Calculate the efficiency at half full load with 0.8 power factor lagging

## Short answer

Referred to primary: Ro=38.72 kΩ, Xo=23.36 kΩ, R01=4.07 Ω, X01=4.78 Ω. Maximum efficiency at full load (unity pf) is 98.0% occurring at 61% load. Half-load efficiency at 0.8 pf lagging is 97.45%.

## Answer

**Given:** 20 kVA, 2200/220 V. OC (LV side): 220 V, 1.1 A, 125 W. SC (HV side): 52.7 V, 8.4 A, 287 W. Primary = HV side (2200 V); K = 220/2200 = 0.1.

#### (i) Parameters referred to the primary
**Shunt branch (the OC test is on the LV side, so transfer it to the HV side with 1/K² = 100):**
```text
cos φ0 = 125/(220 × 1.1) = 0.5165
Iw = 1.1 × 0.5165 = 0.568 A ;  Iμ = √(1.1² − 0.568²) = 0.942 A
On LV:  Ro = 220/0.568 = 387.2 Ω ;  Xo = 220/0.942 = 233.6 Ω
On HV:  Ro = 387.2 × 100 = 38 720 Ω ;  Xo = 233.6 × 100 = 23 357 Ω
```
**Series branch (the SC test is on the HV side, so the values are used directly):**
```text
Z01 = 52.7/8.4 = 6.274 Ω ;  R01 = 287/8.4² = 4.067 Ω
X01 = √(6.274² − 4.067²) = 4.777 Ω
```
**Equivalent circuit (referred to primary)**
```text
 o──┬──────┬──────/\/\/────(((────────o
    │      │     4.067 Ω   4.777 Ω
  38 720  23 357                  load
    Ω      Ω                      V2'
 o──┴──────┴────────────────────────o
```
This is the approximate equivalent circuit: the shunt branch is moved to the input terminals, and the series branch follows it.

#### (ii) Maximum efficiency
```text
Rated HV current I1 = 20 000/2200 = 9.091 A
Full-load Cu loss  = 287 × (9.091/8.4)² = 336.2 W
Iron loss Pi = 125 W
x (max η) = √(Pi/Pcu) = √(125/336.2) = 0.610
Output at max η, unity pf = 0.610 × 20 000 = 12 196 W
η_max = 12 196/(12 196 + 2 × 125) = 97.99 %
```
(Full-load efficiency at unity pf: 20 000/(20 000 + 125 + 336.2) = 97.75 %.)

#### (iii) Half load, 0.8 lagging
```text
Output = 0.5 × 20 000 × 0.8 = 8000 W
Cu loss = 0.5² × 336.2 = 84.0 W
η = 8000/(8000 + 125 + 84.0) = 97.45 %
```
**Answer: (i) Ro = 38.72 kΩ, Xo = 23.36 kΩ, R01 = 4.07 Ω, X01 = 4.78 Ω; (ii) η_max ≈ 98.0 % (at unity pf, about 61 % load); (iii) η ≈ 97.45 %.**

## Check yourself

The answer's key points as multiple-choice questions, with the correct option and why.

1. The OC test was on the LV side. How are Ro and Xo referred to the HV (primary) side?
   A. Multiply by 100
   B. Divide by 100
   C. Multiply by 10
   D. Leave unchanged
   Answer: A. Impedance on LV is multiplied by 1/K² = 100 to refer it to HV. (Key point: Shunt branch transfer)

2. The SC test was on the HV side (primary). What is R01?
   A. 4.067 Ω
   B. 0.04067 Ω
   C. 6.274 Ω
   D. 0.0342 Ω
   Answer: A. R01 = Wsc/Isc² = 287/8.4² = 4.067 Ω, needing no transfer. (Key point: Series branch)

3. Why is the full-load Cu loss 336.2 W rather than 287 W?
   A. Because iron loss is added
   B. Because SC test current 8.4 A is below rated 9.091 A, so loss is scaled by (9.091/8.4)²
   C. Because of temperature rise
   D. Because the test is on LV side
   Answer: B. Rated HV current is 20000/2200 = 9.091 A; copper loss scales with current squared. (Key point: Full-load copper loss)

4. At half load and 0.8 pf lagging, what is the efficiency approximately?
   A. 96.5 %
   B. 98.0 %
   C. 97.45 %
   D. 99.2 %
   Answer: C. η = 8000/(8000 + 125 + 84) = 97.45 %. (Key point: Efficiency at half load)

## Related in Electrical Machine

- [20 kVA 2200/220 V tests, equivalent circuit LV side](https://www.bctengineer.com/question.md?key=semester_4%2Felectrical_machines%3Atf-20kva-2200-220-lv-equivalent) — Electrical Machines, chapter 2
- [20 kVA 2200/220 V, LV-side circuit](https://www.bctengineer.com/question.md?key=semester_4%2Felectrical_machine%3Atransformer-20kva-2200-220-lv-side) — Electrical Machine, chapter 2
- [Equivalent circuit of 20 kVA 220/2200 V transformer](https://www.bctengineer.com/question.md?key=semester_4%2Felectrical_machines_i%3Aoc-sc-20kva-220-2200-primary) — Electrical Machines I, chapter 2
- [Equivalent circuit of 100 kVA 2200/220 V transformer](https://www.bctengineer.com/question.md?key=semester_4%2Felectrical_machines_i%3Aoc-sc-100kva-2200-220-hv) — Electrical Machines I, chapter 2, asked 3×
- [Equivalent circuit, efficiency and regulation of 5 kVA transformer](https://www.bctengineer.com/question.md?key=semester_4%2Felectrical_machines_i%3Aoc-sc-5kva-220-400-lv) — Electrical Machines I, chapter 2
- [Equivalent circuit and half-load efficiency of 50 kVA transformer](https://www.bctengineer.com/question.md?key=semester_4%2Felectrical_machines_i%3A50kva-2500-250-test-secondary-half) — Electrical Machines I, chapter 2

## Related in other subjects

- [20 kVA 250/2500 V tests, regulation, efficiency](https://www.bctengineer.com/question.md?key=semester_4%2Felectrical_machines%3Atf-20kva-250-2500-regulation-efficiency) — Electrical Machines, chapter 2
- [OC and SC tests to build transformer equivalent circuit](https://www.bctengineer.com/question.md?key=semester_4%2Felectrical_machines_i%3Aoc-sc-test-10kva-6600-220) — Electrical Machines I, chapter 2
- [25 kVA 250/2500 V tests, equivalent circuit](https://www.bctengineer.com/question.md?key=semester_4%2Felectrical_machines%3Atf-25kva-250-2500-parameters) — Electrical Machines, chapter 2, asked 2×
- [Equivalent circuit of 8 kVA 400/120 V transformer](https://www.bctengineer.com/question.md?key=semester_4%2Felectrical_machines_i%3Aoc-sc-8kva-400-120-hv) — Electrical Machines I, chapter 2