# Practical vs ideal transformer, phasor diagram

Electrical Machines · Chapter 2: Transformer

- Asked in: 2078 Poush, 2+6 marks
- Video: [Ideal Transformer and Practical Transformer (Basic Electrical Engineering) BTech 1st year](https://www.youtube.com/watch?v=VaVOmLKCZ3c) — Gautam Varde
- Answer checked by Claude Opus 5.5 (high effort) on 2026-10-14
- Page: https://www.bctengineer.com/q/semester_4/electrical_machines/practical-vs-ideal-transformer-phasor
- Whole chapter: https://www.bctengineer.com/md/semester_4/electrical_machines/chapter-2

## Question

How practical transformer is different from ideal one? Explain with phasor diagram the operation of practical transformer when secondary is connected to load.

## Short answer

An ideal transformer has no resistance, no leakage, no core loss, and zero no-load current. A practical transformer has winding resistances, leakage reactances, core loss, and draws an exciting current I0. On load, V2 = E2 – I2(R2 + jX2) and I1 = I0 + I2/a, where a = N1/N2.

## Answer

#### Practical vs ideal transformer

| Point | Ideal transformer | Practical transformer |
|---|---|---|
| Winding resistance | Zero | $R_1$, $R_2$ present (copper loss) |
| Leakage flux | None (unity coupling) | Leakage reactances $X_1$, $X_2$ |
| Core permeability | Infinite | Finite, needs magnetising current $I_\mu$ |
| Core loss | Zero | Hysteresis and eddy loss, current $I_c$ |
| No-load current | Zero | Small $I_0 = I_c + I_\mu$ |
| Efficiency | 100% | 95 to 99% |
| Voltage regulation | Zero | Non-zero |
| $V_1/V_2$ | Exactly $N_1/N_2$ | Slightly different on load |

#### Operation of a practical transformer on load

When load current $I_2$ flows, the secondary terminal voltage and primary current are given by

$$
V_2 = E_2 - I_2(R_2 + jX_2),\qquad I_1 = I_0 + I_1',\ \ I_1' = \frac{N_2}{N_1}I_2,\qquad V_1 = -E_1 + I_1(R_1 + jX_1)
$$

**Phasor diagram (inductive load, lagging $\phi_2$):**

```text
          V1 (applied)
         /|
   I1X1/ |             Steps:
      /  | I1R1        1. Take flux phi as reference.
 -E1 /___|              2. E1, E2 lag phi by 90 deg.
     |                  3. I2 lags V2 by phi2.
     |  E2              4. E2 = V2 + I2R2 + jI2X2.
     |   \ I2X2         5. I1' = I2/a opposes the I2 mmf.
 phi |    \ I2R2        6. I1 = I0 + I1'.
     v     \V2          7. V1 = -E1 + I1R1 + jI1X1.
```

Steps in words:
1. Draw the flux $\phi$ as reference. The emfs $E_1$ and $E_2$ lag it by 90°, and $-E_1$ is drawn opposite to $E_1$.
2. Draw $V_2$, then $I_2$ lagging it by $\phi_2$. Add $I_2R_2$ (parallel to $I_2$) and $I_2X_2$ (90° ahead) to reach $E_2$.
3. The load component $I_1'$ is drawn opposite to $I_2$ (scaled by $N_2/N_1$). The no-load current $I_0$ is drawn leading the flux by the hysteresis angle, with $I_\mu$ along $\phi$ and $I_c$ along $-E_1$.
4. $I_1 = I_0 + I_1'$. Add $I_1R_1$ and $I_1X_1$ to $-E_1$ to get $V_1$.

The angle between $V_1$ and $I_1$ is the primary power factor angle $\phi_1$, slightly different from $\phi_2$ because of $I_0$ and the drops.

## Check yourself

The answer's key points as multiple-choice questions, with the correct option and why.

1. Compared with an ideal transformer, a practical transformer has:
   A. Zero regulation and 100% efficiency
   B. Infinite permeability
   C. Winding resistance, leakage reactance, finite permeability and core loss
   D. No-load current of zero
   Answer: C. These give copper loss, leakage drops, magnetising current and iron loss. (Key point: Differences)

2. In a practical transformer I0 equals:
   A. Ic - Im
   B. Zero
   C. I2/a
   D. Ic + Im
   Answer: D. A core-loss component and a magnetising component. (Key point: No-load current)

3. The load component I1' is drawn:
   A. Opposite to I2 (scaled by N2/N1)
   B. In phase with I2
   C. At 90 degrees to I2
   D. Along the flux
   Answer: A. It balances the secondary mmf. (Key point: Load component)

4. In the phasor construction, flux is the reference and E1, E2 lag it by:
   A. 0 degrees
   B. 90 degrees
   C. 180 degrees
   D. 45 degrees
   Answer: B. e = -N dphi/dt lags a sinusoidal flux by 90 degrees. (Key point: Phasor reference)

## Related in Electrical Machines

- [Loaded transformer and phasor diagram for inductive load](https://www.bctengineer.com/question.md?key=semester_4%2Felectrical_machines_i%3Atransformer-loaded-operation-phasor-inductive) — Electrical Machines I, chapter 2
- [Transformer no-load operation and ideal transformer properties](https://www.bctengineer.com/question.md?key=semester_4%2Felectrical_machines_i%3Atransformer-no-load-ideal-properties) — Electrical Machines I, chapter 2
- [Transformer on load and no load, phasor diagrams](https://www.bctengineer.com/question.md?key=semester_4%2Felectrical_machines%3Atransformer-load-phasor-resistive-capacitive) — Electrical Machines, chapter 2
- [Transformer no-load and load operation, constant core flux](https://www.bctengineer.com/question.md?key=semester_4%2Felectrical_machines_i%3Aideal-transformer-noload-load-constant-flux) — Electrical Machines I, chapter 2, asked 5×
- [Ideal transformer no-load and loaded, ratios](https://www.bctengineer.com/question.md?key=semester_4%2Felectrical_machines%3Aideal-transformer-voltage-current-ratio) — Electrical Machines, chapter 2, asked 2×
- [Real transformer no-load operation and amp-turn balance](https://www.bctengineer.com/question.md?key=semester_4%2Felectrical_machines_i%3Areal-transformer-noload-amp-turn-balance) — Electrical Machines I, chapter 2

## Related in other subjects

- [Transformer on load, phasor diagrams](https://www.bctengineer.com/question.md?key=semester_4%2Felectrical_machine%3Atransformer-phasor-resistive-capacitive) — Electrical Machine, chapter 2
- [Ideal vs practical filters and scaling](https://www.bctengineer.com/question.md?key=semester_5%2Ffilter_design%3Aideal-practical-filters-scaling) — Filter Design, chapter 1, asked 2×
- [Filter importance in communication; ideal vs practical](https://www.bctengineer.com/question.md?key=semester_5%2Ffilter_design%3Afilter-communication-ideal-practical) — Filter Design, chapter 1, asked 2×
- [Ideal transformer no-load, load, ratios](https://www.bctengineer.com/question.md?key=semester_4%2Felectrical_machine%3Aideal-transformer-ratios-derivation) — Electrical Machine, chapter 2, asked 2×