# Why iron loss neglected in SC test; parameters

Electrical Machines · Chapter 2: Transformer

- Asked in: 2079 Jestha, 2+6 marks
- Video: [Transformer OC test and SC test problems | effeciency, voltage regulation calculations](https://www.youtube.com/watch?v=aB2j_Fqd4zo) — The PiSquare Academy
- Answer checked by Claude Opus 5.5 (high effort) on 2026-10-14
- Page: https://www.bctengineer.com/q/semester_4/electrical_machines/sc-test-iron-loss-400-200
- Whole chapter: https://www.bctengineer.com/md/semester_4/electrical_machines/chapter-2

## Question

Why is iron loss neglected in short circuit test of transformer? A single phase 400/200 V, 50 Hz transformer gave the following test results:
Open circuit Test: 200 V, 1.5 A, 110 W on LV side
Short circuit Test: 30 V, 18 A, 350 W on HV side
Calculate the equivalent circuit parameters referred to primary side and draw the equivalent circuit showing calculated parameters.

## Short answer

Short circuit test uses only 5–10% rated voltage, so flux and iron loss are negligible. Equivalent circuit parameters referred to primary (400 V): Req = 1.08 Ω, Xeq = 1.269 Ω, R0 = 1455 Ω, X0 = 573.3 Ω.

## Answer

#### Why iron loss is neglected in the SC test

In the short-circuit test only a small voltage (about 5 to 10% of the rated value) is applied, just enough to circulate full-load current in the shorted secondary. The core flux is proportional to the applied voltage, so it is only about 5 to 10% of normal flux. Core loss varies approximately as the square of the flux, so it becomes about 0.25 to 1% of the rated core loss, which is negligible. The wattmeter therefore reads the copper loss alone. In this problem $30/400 = 7.5\%$ of rated voltage, so the core loss is about $0.075^2\times110 \approx 0.6$ W against 350 W.

#### Equivalent circuit parameters (referred to the primary)

Primary = HV side (400 V), secondary = LV side (200 V).

#### Open-circuit test (on the LV side)

The no-load power is almost entirely core loss, so the shunt branch is found from it.

$$
\begin{aligned}
\cos\phi_0 &= \frac{P_0}{V_0I_0} = \frac{110}{200\times1.5} = 0.3667 \\
I_w &= I_0\cos\phi_0 = 0.55\ \text{A},\qquad I_\mu = \sqrt{I_0^2 - I_w^2} = 1.396\ \text{A} \\
R_0 &= \frac{V_0}{I_w} = 363.6\ \Omega,\qquad X_0 = \frac{V_0}{I_\mu} = 143.3\ \Omega\quad(\text{on the LV side})
\end{aligned}
$$

#### Short-circuit test (on the HV side)

At the reduced test voltage the core loss is negligible, so the wattmeter reading is the copper loss.

$$
\begin{aligned}
Z_{sc} &= \frac{V_{sc}}{I_{sc}} = \frac{30}{18} = 1.667\ \Omega \\
R_{sc} &= \frac{P_{sc}}{I_{sc}^2} = \frac{350}{18^2} = 1.08\ \Omega \\
X_{sc} &= \sqrt{Z_{sc}^2 - R_{sc}^2} = 1.269\ \Omega\quad(\text{on the HV side})
\end{aligned}
$$

#### Referring to the HV side

The turns ratio is $K = 400/200 = 2$, so $K^2 = 4$. Impedances are multiplied by $K^2$ when moved from LV to HV, and divided by $K^2$ when moved from HV to LV.

$$
\begin{aligned}
R_0' &= 363.6 \times 4 = 1455\ \Omega \\ X_0' &= 143.3 \times 4 = 573.3\ \Omega
\end{aligned}
$$

#### Equivalent circuit referred to the HV side

```text
   Req=1.08 ohm   Xeq=1.27 ohm
 o--+-----/\/\/\-----UUUU------o
    |                          
   [R0=1455] [X0=573.3]   Load
    |      (in parallel)
 o--+---------------------------o
```

$R_{eq} = 1.08\ \Omega$, $X_{eq} = 1.269\ \Omega$ ($Z_{eq} = 1.667\ \Omega$), shunt branch $R_0 = 1455\ \Omega$ in parallel with $X_0 = 573.3\ \Omega$.

The shunt branch carries $I_0$ referred to the primary $= 1.5/2 = 0.75$ A.

**Answer (referred to primary):** $R_{01} = 1.080\ \Omega$, $X_{01} = 1.269\ \Omega$, $R_0 = 1454.5\ \Omega$, $X_0 = 573.3\ \Omega$.

## Check yourself

The answer's key points as multiple-choice questions, with the correct option and why.

1. Why is iron loss neglected in the SC test?
   A. The low applied voltage gives a small flux, and core loss varies as flux squared
   B. The core is removed in the SC test
   C. Copper loss cancels the core loss
   D. The secondary current demagnetises the core
   Answer: A. At 5 to 10% voltage the core loss is only about 0.25 to 1% of its rated value. (Key point: Why iron loss negligible)

2. What is cos phi0 in the OC test (200 V, 1.5 A, 110 W)?
   A. 0.5
   B. 0.667
   C. 0.3667
   D. 0.1833
   Answer: C. cos phi0 = 110/(200 x 1.5) = 0.3667. (Key point: OC power factor)

3. The OC shunt values measured on the LV side are referred to the HV side by:
   A. Dividing by K^2 = 4
   B. Multiplying by K^2 = 4
   C. Multiplying by K = 2
   D. Dividing by K = 2
   Answer: B. Impedance moved from LV to HV is multiplied by K^2. (Key point: Referring impedance)

4. What is R_sc in the SC test (30 V, 18 A, 350 W)?
   A. 1.08 ohm
   B. 1.667 ohm
   C. 19.4 ohm
   D. 0.58 ohm
   Answer: A. R_sc = P/I^2 = 350/324 = 1.08 ohm. (Key point: SC resistance)

## Related in Electrical Machines

- [10 kVA 200/400 V tests, parameters on LV side](https://www.bctengineer.com/question.md?key=semester_4%2Felectrical_machines%3Atf-10kva-200-400-lv-params) — Electrical Machines, chapter 2
- [8 kVA 400/120 V tests, parameters on HV side](https://www.bctengineer.com/question.md?key=semester_4%2Felectrical_machines%3Atf-8kva-400-120-efficiency-hv) — Electrical Machines, chapter 2
- [OC/SC test of 2200/110 V, 40 kVA transformer](https://www.bctengineer.com/question.md?key=semester_4%2Felectrical_machines_i%3Atransformer-oc-sc-2200-110-40kva) — Electrical Machines I, chapter 2
- [Equivalent circuit of 5 kVA 200/400 V transformer](https://www.bctengineer.com/question.md?key=semester_4%2Felectrical_machines_i%3Aoc-sc-5kva-200-400-primary) — Electrical Machines I, chapter 2, asked 2×
- [20 kVA 2200/220 V tests, equivalent circuit LV side](https://www.bctengineer.com/question.md?key=semester_4%2Felectrical_machines%3Atf-20kva-2200-220-lv-equivalent) — Electrical Machines, chapter 2
- [Equivalent circuit of 8 kVA 400/120 V transformer](https://www.bctengineer.com/question.md?key=semester_4%2Felectrical_machines_i%3Aoc-sc-8kva-400-120-hv) — Electrical Machines I, chapter 2

## Related in other subjects

- [10 kVA 200/400 V LV-side parameters](https://www.bctengineer.com/question.md?key=semester_4%2Felectrical_machine%3Atransformer-10kva-oc-sc-lv-circuit) — Electrical Machine, chapter 2
- [10 kVA 200/400 V test parameters](https://www.bctengineer.com/question.md?key=semester_4%2Felectrical_machine%3Atransformer-10kva-test-params) — Electrical Machine, chapter 2
- [20 kVA 2200/220 V, LV-side circuit](https://www.bctengineer.com/question.md?key=semester_4%2Felectrical_machine%3Atransformer-20kva-2200-220-lv-side) — Electrical Machine, chapter 2
- [4 kVA 200/400 V test parameters](https://www.bctengineer.com/question.md?key=semester_4%2Felectrical_machine%3Atransformer-4kva-200-400-lv-side) — Electrical Machine, chapter 2