title: "20 kVA 2200/220 V tests, equivalent circuit LV side"
subject: "Electrical Machines"
chapter: 2
key: "semester_4/electrical_machines:tf-20kva-2200-220-lv-equivalent"
source: https://www.bctengineer.com/q/semester_4/electrical_machines/tf-20kva-2200-220-lv-equivalent
site: BCT Engineering
---

# 20 kVA 2200/220 V tests, equivalent circuit LV side

Electrical Machines · Chapter 2: Transformer

- Asked in: 2070 Magh, 8 marks
- Video: [(E)EM Ex 2.2 || Equivalent Circuit of a Transformer || Refer to Pri & Secy sides ||Open-Short Test](https://www.youtube.com/watch?v=uJP_rFndPtU) — Electrical Engineering Academy
- Answer checked by Claude Opus 5.5 (high effort) on 2026-10-14
- Page: https://www.bctengineer.com/q/semester_4/electrical_machines/tf-20kva-2200-220-lv-equivalent
- Whole chapter: https://www.bctengineer.com/md/semester_4/electrical_machines/chapter-2

## Question

The following test results were obtained on a 20 kVA, 2200/220 V, 50 Hz single phase transformer:
Open-circuit Test (LV Side): 220 V, 1.1 A, 125 W
Short-circuit Test (HV Side): 52.7 V, 8.4 A, 287 W
Calculate the equivalent circuit referred to L.V side and draw the equivalent circuit.

## Short answer

Referred to LV side: shunt branch R0=387.2 Ω, X0=233.6 Ω; series branch Req=0.04067 Ω, Xeq=0.04777 Ω (Zeq=0.0627 Ω).

## Answer

**Given:** 20 kVA, 2200/220 V, so HV = 2200 V, LV = 220 V, $K = 10$, $K^2 = 100$. (Rated HV current is $20\,000/2200 = 9.09$ A; the SC test was at 8.4 A, near full load.)

#### Open-circuit test (on the LV side)

The no-load power is almost entirely core loss, so the shunt branch is found from it.

$$
\begin{aligned}
\cos\phi_0 &= \frac{P_0}{V_0I_0} = \frac{125}{220\times1.1} = 0.5165 \\
I_w &= I_0\cos\phi_0 = 0.5682\ \text{A},\qquad I_\mu = \sqrt{I_0^2 - I_w^2} = 0.9419\ \text{A} \\
R_0 &= \frac{V_0}{I_w} = 387.2\ \Omega,\qquad X_0 = \frac{V_0}{I_\mu} = 233.6\ \Omega\quad(\text{on the LV side})
\end{aligned}
$$

#### Short-circuit test (on the HV side)

At the reduced test voltage the core loss is negligible, so the wattmeter reading is the copper loss.

$$
\begin{aligned}
Z_{sc} &= \frac{V_{sc}}{I_{sc}} = \frac{52.7}{8.4} = 6.274\ \Omega \\
R_{sc} &= \frac{P_{sc}}{I_{sc}^2} = \frac{287}{8.4^2} = 4.067\ \Omega \\
X_{sc} &= \sqrt{Z_{sc}^2 - R_{sc}^2} = 4.777\ \Omega\quad(\text{on the HV side})
\end{aligned}
$$

#### Referring to the LV side

The turns ratio is $K = 2200/220 = 10$, so $K^2 = 100$. Impedances are multiplied by $K^2$ when moved from LV to HV, and divided by $K^2$ when moved from HV to LV.

$$
\begin{aligned}
R_{eq} &= 4.067 \div 100 = 0.04067\ \Omega \\ X_{eq} &= 4.777 \div 100 = 0.04777\ \Omega
\end{aligned}
$$

#### Equivalent circuit referred to the LV side

```text
   Req=0.0407 ohm   Xeq=0.0478 ohm
 o--+-----/\/\/\-----UUUU------o
    |                          
   [R0=387.2] [X0=233.6]   Load
    |      (in parallel)
 o--+---------------------------o
```

$R_{eq} = 0.04067\ \Omega$, $X_{eq} = 0.04777\ \Omega$ ($Z_{eq} = 0.06274\ \Omega$), shunt branch $R_0 = 387.2\ \Omega$ in parallel with $X_0 = 233.6\ \Omega$.

**Answer (referred to LV side):** $R_0 = 387.2\ \Omega$, $X_0 = 233.6\ \Omega$, $R_{eq} = 0.04067\ \Omega$, $X_{eq} = 0.04777\ \Omega$ ($Z_{eq} = 0.0627\ \Omega$)

## Check yourself

The answer's key points as multiple-choice questions, with the correct option and why.

1. How are the HV-side SC results moved to LV?
   A. Divide by K^2 = 100
   B. Multiply by 100
   C. Divide by 10
   D. Multiply by 10
   Answer: A. Req = 4.067/100 = 0.04067 ohm. (Key point: Series referral)

2. What is cos phi0 for OC (220 V, 1.1 A, 125 W)?
   A. 0.32
   B. 0.5165
   C. 0.75
   D. 0.9
   Answer: B. 125/(220 x 1.1) = 0.5165. (Key point: Power factor OC)

3. How is X_sc found from Zsc and Rsc?
   A. Zsc - Rsc
   B. Zsc + Rsc
   C. sqrt(Zsc^2 - Rsc^2) = 4.777 ohm
   D. Zsc x Rsc
   Answer: C. R and X are at right angles in Z. (Key point: SC reactance)

## Related in Electrical Machines

- [Equivalent circuit of 20 kVA 220/2200 V transformer](https://www.bctengineer.com/question.md?key=semester_4%2Felectrical_machines_i%3Aoc-sc-20kva-220-2200-primary) — Electrical Machines I, chapter 2
- [Equivalent circuit of 100 kVA 2200/220 V transformer](https://www.bctengineer.com/question.md?key=semester_4%2Felectrical_machines_i%3Aoc-sc-100kva-2200-220-hv) — Electrical Machines I, chapter 2, asked 3×
- [8 kVA 400/120 V tests, parameters on HV side](https://www.bctengineer.com/question.md?key=semester_4%2Felectrical_machines%3Atf-8kva-400-120-efficiency-hv) — Electrical Machines, chapter 2
- [10 kVA 200/400 V tests, parameters on LV side](https://www.bctengineer.com/question.md?key=semester_4%2Felectrical_machines%3Atf-10kva-200-400-lv-params) — Electrical Machines, chapter 2
- [Equivalent circuit, efficiency and regulation of 5 kVA transformer](https://www.bctengineer.com/question.md?key=semester_4%2Felectrical_machines_i%3Aoc-sc-5kva-220-400-lv) — Electrical Machines I, chapter 2
- [20 kVA 250/2500 V tests, equivalent circuit](https://www.bctengineer.com/question.md?key=semester_4%2Felectrical_machines%3Atf-20kva-250-2500-parameters) — Electrical Machines, chapter 2, asked 2×

## Related in other subjects

- [20 kVA 2200/220 V, LV-side circuit](https://www.bctengineer.com/question.md?key=semester_4%2Felectrical_machine%3Atransformer-20kva-2200-220-lv-side) — Electrical Machine, chapter 2
- [20 kVA 2200/220 V tests, efficiency](https://www.bctengineer.com/question.md?key=semester_4%2Felectrical_machine%3Atransformer-20kva-2200-220-primary) — Electrical Machine, chapter 2
- [220/2200 V transformer test parameters](https://www.bctengineer.com/question.md?key=semester_4%2Felectrical_machine%3Atransformer-220-2200-test-primary) — Electrical Machine, chapter 2, asked 2×
- [Design: 125 kVA single phase transformer](https://www.bctengineer.com/question.md?key=semester_5%2Felectric_machine_design%3Adesign-125kva-single-phase-windings) — Electric Machine Design, chapter 3, asked 3×