# 8 kVA 400/120 V tests, parameters on HV side

Electrical Machines · Chapter 2: Transformer

- Asked in: 2071 Magh, 8 marks
- Video: [Transformer OC test and SC test problems | effeciency, voltage regulation calculations](https://www.youtube.com/watch?v=aB2j_Fqd4zo) — The PiSquare Academy
- Answer checked by Claude Opus 5.5 (high effort) on 2026-10-14
- Page: https://www.bctengineer.com/q/semester_4/electrical_machines/tf-8kva-400-120-efficiency-hv
- Whole chapter: https://www.bctengineer.com/md/semester_4/electrical_machines/chapter-2

## Question

The following test results were obtained for open circuit and short circuit tests on a 8 kVA, 400/120 V, 50 Hz transformer:
Open-circuit Test (LV Side): 120 V, 4 A, 75 W
Short-circuit Test (HV Side): 9.5 V, 20 A, 110 W
Calculate the equivalent circuit parameters referred to high voltage side. Also calculate the efficiency at half full load and 0.8 power factor lagging load.

## Short answer

Referred to HV side: shunt branch R0=2133 Ω, X0=337.5 Ω; series branch Req=0.275 Ω, Xeq=0.3873 Ω. Efficiency at half load, 0.8 pf lag: η=96.90%.

## Answer

**Given:** 8 kVA, 400/120 V. HV = 400 V, LV = 120 V, $K = 400/120 = 3.333$, $K^2 = 11.11$. Rated HV current $= 8000/400 = 20$ A, so the SC test is at full load.

#### Open-circuit test (on the LV side)

The no-load power is almost entirely core loss, so the shunt branch is found from it.

$$
\begin{aligned}
\cos\phi_0 &= \frac{P_0}{V_0I_0} = \frac{75}{120\times4} = 0.1562 \\
I_w &= I_0\cos\phi_0 = 0.625\ \text{A},\qquad I_\mu = \sqrt{I_0^2 - I_w^2} = 3.951\ \text{A} \\
R_0 &= \frac{V_0}{I_w} = 192\ \Omega,\qquad X_0 = \frac{V_0}{I_\mu} = 30.37\ \Omega\quad(\text{on the LV side})
\end{aligned}
$$

#### Short-circuit test (on the HV side)

At the reduced test voltage the core loss is negligible, so the wattmeter reading is the copper loss.

$$
\begin{aligned}
Z_{sc} &= \frac{V_{sc}}{I_{sc}} = \frac{9.5}{20} = 0.475\ \Omega \\
R_{sc} &= \frac{P_{sc}}{I_{sc}^2} = \frac{110}{20^2} = 0.275\ \Omega \\
X_{sc} &= \sqrt{Z_{sc}^2 - R_{sc}^2} = 0.3873\ \Omega\quad(\text{on the HV side})
\end{aligned}
$$

#### Referring to the HV side

The turns ratio is $K = 400/120 = 3.333$, so $K^2 = 11.11$. Impedances are multiplied by $K^2$ when moved from LV to HV, and divided by $K^2$ when moved from HV to LV.

$$
\begin{aligned}
R_0' &= 192 \times 11.11 = 2133\ \Omega \\ X_0' &= 30.37 \times 11.11 = 337.5\ \Omega
\end{aligned}
$$

#### Equivalent circuit referred to the HV side

```text
   Req=0.275 ohm   Xeq=0.387 ohm
 o--+-----/\/\/\-----UUUU------o
    |                          
   [R0=2133] [X0=337.5]   Load
    |      (in parallel)
 o--+---------------------------o
```

$R_{eq} = 0.275\ \Omega$, $X_{eq} = 0.3873\ \Omega$ ($Z_{eq} = 0.475\ \Omega$), shunt branch $R_0 = 2133\ \Omega$ in parallel with $X_0 = 337.5\ \Omega$.

#### Efficiency at half load, 0.8 pf lagging

$$
\begin{aligned}
P_{out} &= 0.5\times8000\times0.8 = 3200\ \text{W} \\
P_{cu} &= 0.5^2\times110 = 27.5\ \text{W},\qquad P_i = 75\ \text{W} \\
\eta &= \frac{3200}{3200 + 27.5 + 75}\times100 = 96.90\%
\end{aligned}
$$

**Answer (referred to HV):** $R_0 = 2133\ \Omega$, $X_0 = 337.5\ \Omega$, $R_{eq} = 0.275\ \Omega$, $X_{eq} = 0.3873\ \Omega$; efficiency at half load $= 96.90\%$

## Check yourself

The answer's key points as multiple-choice questions, with the correct option and why.

1. What are K and K^2 for 400/120 V?
   A. 3.333 and 11.11
   B. 0.3 and 0.09
   C. 120 and 14400
   D. 3.333 and 3.333
   Answer: A. K = 400/120. (Key point: Turns ratio)

2. How is R0 = 192 ohm (LV) referred to HV?
   A. Multiply by K^2 to give 2133 ohm
   B. Divide by K^2 to give 17.3 ohm
   C. Multiply by K to give 640 ohm
   D. Leave unchanged
   Answer: A. LV to HV multiplies by K^2. (Key point: Shunt to HV)

3. What is the efficiency at half load and 0.8 pf?
   A. 97.5%
   B. 96.90%
   C. 95.6%
   D. 98.1%
   Answer: B. Output 3200 W; Pcu = 27.5 W; Pi = 75 W. (Key point: Half load efficiency)

## Related in Electrical Machines

- [20 kVA 2200/220 V tests, equivalent circuit LV side](https://www.bctengineer.com/question.md?key=semester_4%2Felectrical_machines%3Atf-20kva-2200-220-lv-equivalent) — Electrical Machines, chapter 2
- [10 kVA 200/400 V tests, parameters on LV side](https://www.bctengineer.com/question.md?key=semester_4%2Felectrical_machines%3Atf-10kva-200-400-lv-params) — Electrical Machines, chapter 2
- [Equivalent circuit of 8 kVA 400/120 V transformer](https://www.bctengineer.com/question.md?key=semester_4%2Felectrical_machines_i%3Aoc-sc-8kva-400-120-hv) — Electrical Machines I, chapter 2
- [Equivalent circuit of 20 kVA 250/2500 V transformer from tests](https://www.bctengineer.com/question.md?key=semester_4%2Felectrical_machines_i%3Aoc-sc-20kva-250-2500) — Electrical Machines I, chapter 2, asked 3×
- [Equivalent circuit of 5 kVA 200/400 V transformer](https://www.bctengineer.com/question.md?key=semester_4%2Felectrical_machines_i%3Aoc-sc-5kva-200-400-primary) — Electrical Machines I, chapter 2, asked 2×
- [20 kVA 250/2500 V tests, equivalent circuit](https://www.bctengineer.com/question.md?key=semester_4%2Felectrical_machines%3Atf-20kva-250-2500-parameters) — Electrical Machines, chapter 2, asked 2×

## Related in other subjects

- [8 kVA 400/120 V tests, half-load efficiency](https://www.bctengineer.com/question.md?key=semester_4%2Felectrical_machine%3Atransformer-8kva-400-120-hv-side) — Electrical Machine, chapter 2
- [10 kVA 200/400 V LV-side parameters](https://www.bctengineer.com/question.md?key=semester_4%2Felectrical_machine%3Atransformer-10kva-oc-sc-lv-circuit) — Electrical Machine, chapter 2
- [20 kVA 2200/220 V, LV-side circuit](https://www.bctengineer.com/question.md?key=semester_4%2Felectrical_machine%3Atransformer-20kva-2200-220-lv-side) — Electrical Machine, chapter 2
- [20 kVA 250/2500 V test parameters](https://www.bctengineer.com/question.md?key=semester_4%2Felectrical_machine%3Atransformer-20kva-250-2500-primary) — Electrical Machine, chapter 2, asked 2×