# Equivalent circuit and half-load efficiency of 50 kVA transformer

Electrical Machines I · Chapter 2: Transformer

- Asked in: 2069 Poush, 8 marks
- Video: [#3  Equivalent circuit, Voltage Regulation and efficiency of single phase transformer #transformer](https://www.youtube.com/watch?v=L94UpXXINe8) — Dr. B. M. Manjunath
- Answer checked by Claude Opus 5.5 (high effort) on 2026-10-14
- Page: https://www.bctengineer.com/q/semester_4/electrical_machines_i/50kva-2500-250-test-secondary-half
- Whole chapter: https://www.bctengineer.com/md/semester_4/electrical_machines_i/chapter-2

## Question

A 50 kVA, 2500V/250V, 50 Hz single phase transformer draws a current of 0.3 Amp at no load and consumes 300 Watts. When the primary winding is supplied by 100 V with secondary winding short circuited, the primary draws a current of 20 Amp and consumes 500 watts. Calculate the equivalent circuit parameters of the transformer referred to secondary side. Also calculate the efficiency of the transformer at half load.

## Short answer

From open-circuit test on HV: R0=20833 Ω, X0=9092 Ω, referred to secondary become 208.33 Ω and 90.92 Ω. Short-circuit test gives R01=1.25 Ω, X01=4.841 Ω, referred to secondary: R02=0.0125 Ω, X02=0.0484 Ω. At half load, copper loss=125 W, iron loss=300 W, efficiency (upf)=98.33%.

## Answer

**Interpretation:** the no-load test (0.3 A, 300 W) is at rated primary voltage, 2500 V, and the SC test is on the primary (HV) with the secondary shorted. Rated primary current $= 50000/2500 = 20$ A, so the SC test is at full load. Factor HV to LV: $\left(\frac{250}{2500}\right)^2 = 0.01$.

#### Shunt branch (no-load test on HV: 2500 V, 0.3 A, 300 W)
$$
\begin{aligned}
\cos\phi_0 &= \frac{300}{2500 \times 0.3} = 0.4, \quad \sin\phi_0 = 0.9165 \\
I_w &= 0.3 \times 0.4 = 0.12\ \text{A}, \quad I_\mu = 0.3 \times 0.9165 = 0.275\ \text{A} \\
R_0 &= \frac{2500}{0.12} = 20833\ \Omega, \quad X_0 = \frac{2500}{0.275} = 9092\ \Omega \ (\text{HV side})
\end{aligned}
$$
Referred to secondary:
$$
R_0' = 20833 \times 0.01 = 208.33\ \Omega, \qquad X_0' = 9092 \times 0.01 = 90.92\ \Omega
$$

#### Series branch (SC test on HV: 100 V, 20 A, 500 W)
$$
\begin{aligned}
Z_{01} &= \frac{100}{20} = 5\ \Omega, \quad R_{01} = \frac{500}{20^2} = 1.25\ \Omega \\
X_{01} &= \sqrt{5^2 - 1.25^2} = 4.841\ \Omega
\end{aligned}
$$
Referred to secondary:
$$
\begin{aligned}
R_{02} &= 1.25 \times 0.01 = 0.0125\ \Omega \\
X_{02} &= 4.841 \times 0.01 = 0.0484\ \Omega \\
Z_{02} &= 5 \times 0.01 = 0.05\ \Omega
\end{aligned}
$$

#### Equivalent circuit referred to secondary
```text
 I1 ->        I0                 I2
 o-----+--------+---[ R02 ]---[ jX02 ]---o
 +     |        |                        +
     [ R0 ]  [ jX0 ]                   load
 V1'   |        |                       V2
 -     |        |                        -
 o-----+--------+------------------------o
 All values referred to secondary (250 V):
 R0 = 208.33 ohm, X0 = 90.92 ohm
 R02 = 0.0125 ohm, X02 = 0.0484 ohm
```

#### Efficiency at half load
Iron loss $P_i = 300$ W; full-load copper loss $= 500$ W (test at rated current). Assuming unity pf:
$$
\begin{aligned}
\text{Output} &= 0.5 \times 50000 \times 1 = 25000\ \text{W} \\
P_{cu} &= 0.5^2 \times 500 = 125\ \text{W} \\
\eta &= \frac{25000}{25000 + 300 + 125}\times 100 = 98.33\%
\end{aligned}
$$

**Answer:** Referred to secondary: $R_0 = 208.33\ \Omega$, $X_0 = 90.92\ \Omega$, $R_{02} = 0.0125\ \Omega$, $X_{02} = 0.0484\ \Omega$; half-load efficiency (upf) = **98.33%**.

## Check yourself

The answer's key points as multiple-choice questions, with the correct option and why.

1. To refer HV-side impedances of a 2500/250 V transformer to the secondary, they are multiplied by:
   A. 10
   B. 100
   C. 0.1
   D. 0.01
   Answer: D. Impedance scales by the square of the turns ratio (250/2500)^2 = 0.01. (Key point: Referring to LV side)

2. For the SC test (100 V, 20 A, 500 W), R01 and X01 are:
   A. R01 = 1.25 ohm, X01 = 4.841 ohm
   B. R01 = 5 ohm, X01 = 1.25 ohm
   C. R01 = 25 ohm, X01 = 4.841 ohm
   D. R01 = 1.25 ohm, X01 = 5 ohm
   Answer: A. R01 = W/I^2 = 500/400 = 1.25 ohm, Z01 = 100/20 = 5 ohm, X01 = sqrt(25 - 1.5625) = 4.841 ohm. (Key point: Series branch from SC test)

3. In the OC test (2500 V, 0.3 A, 300 W), the working component Iw and R0 (HV side) are:
   A. 0.12 A and 20833 ohm
   B. 0.275 A and 9092 ohm
   C. 0.3 A and 8333 ohm
   D. 0.12 A and 9092 ohm
   Answer: A. cos phi0 = 0.4, so Iw = 0.12 A and R0 = 2500/0.12 = 20833 ohm. (Key point: Shunt branch from OC test)

4. Which losses are used for efficiency at half load (unity pf) in this problem?
   A. 300 W iron and 500 W copper
   B. 300 W iron and 125 W copper
   C. 150 W iron and 125 W copper
   D. 300 W iron and 250 W copper
   Answer: B. Iron loss is constant (300 W); copper loss is 0.5^2 x 500 = 125 W, giving eta = 25000/25425 = 98.33%. (Key point: Half-load efficiency)

## Related in Electrical Machines I

- [Primary current and efficiency of 100 kVA Δ/Y transformer](https://www.bctengineer.com/question.md?key=semester_4%2Felectrical_machines_i%3Adelta-star-100kva-11kv-100a-efficiency) — Electrical Machines I, chapter 2
- [Equivalent circuit, efficiency and regulation of 5 kVA transformer](https://www.bctengineer.com/question.md?key=semester_4%2Felectrical_machines_i%3Aoc-sc-5kva-220-400-lv) — Electrical Machines I, chapter 2
- [Efficiency of 25 kVA transformer at half load and overload](https://www.bctengineer.com/question.md?key=semester_4%2Felectrical_machines_i%3A25kva-2200-220-efficiency-half-overload) — Electrical Machines I, chapter 2
- [Full-load and half-load efficiency of 100 kVA transformer](https://www.bctengineer.com/question.md?key=semester_4%2Felectrical_machines_i%3A100kva-1200w-960w-efficiency) — Electrical Machines I, chapter 2
- [Equivalent circuit of 20 kVA 220/2200 V transformer](https://www.bctengineer.com/question.md?key=semester_4%2Felectrical_machines_i%3Aoc-sc-20kva-220-2200-primary) — Electrical Machines I, chapter 2
- [Equivalent circuit of 5 kVA 200/400 V transformer](https://www.bctengineer.com/question.md?key=semester_4%2Felectrical_machines_i%3Aoc-sc-5kva-200-400-primary) — Electrical Machines I, chapter 2, asked 2×

## Related in other subjects

- [500 kVA transformer efficiency full/half load](https://www.bctengineer.com/question.md?key=semester_4%2Felectrical_machine%3Atransformer-500kva-efficiency-full-half) — Electrical Machine, chapter 2
- [500 kVA transformer efficiency, full and half load](https://www.bctengineer.com/question.md?key=semester_4%2Felectrical_machines%3Atf-500kva-6600-400-efficiency) — Electrical Machines, chapter 2
- [100 kVA transformer efficiency at full and half load](https://www.bctengineer.com/question.md?key=semester_4%2Felectrical_machines%3Atf-100kva-efficiency-full-half-load) — Electrical Machines, chapter 2
- [Design: 100 kVA 2200/480 V single phase transformer](https://www.bctengineer.com/question.md?key=semester_5%2Felectric_machine_design%3Adesign-100kva-single-phase-ducts) — Electric Machine Design, chapter 3, asked 3×