title: "Induction motor equivalent circuit from two-wattmeter tests"
subject: "Electrical Machines I"
chapter: 5
key: "semester_4/electrical_machines_i:im-400v-noload-blocked-two-wattmeter"
source: https://www.bctengineer.com/q/semester_4/electrical_machines_i/im-400v-noload-blocked-two-wattmeter
site: BCT Engineering
---

# Induction motor equivalent circuit from two-wattmeter tests

Electrical Machines I · Chapter 5: Three-Phase Induction Machines

- Asked in: 2071 Bhadra, 8 marks
- Answer checked by Claude Opus 5.5 (high effort) on 2026-10-14
- Page: https://www.bctengineer.com/q/semester_4/electrical_machines_i/im-400v-noload-blocked-two-wattmeter
- Whole chapter: https://www.bctengineer.com/md/semester_4/electrical_machines_i/chapter-5

## Question

The data obtained from the test of a 3-phase star connected, 400 V, 50 Hz induction motor are as follows:
No-Load Test: V1 = 400 V, I0 = 20 A, W1 = 5000 W and W2 = −3200 W
Blocked rotor test: VSC = 50 V, ISC = 60 A, W1 = 2300 W and W2 = 750 W
Calculate the equivalent circuit parameters referred to stator side.

## Short answer

Per‑phase equivalent circuit parameters (referred to stator): R0 = 88.89 Ω, X0 = 11.65 Ω; R1 = R2' = 0.1412 Ω, X1 = X2' = 0.1948 Ω.

## Answer

In the two-wattmeter method the total 3-phase power is the algebraic sum of the readings. The no-load test gives the shunt branch, the blocked-rotor test the series branch. Star connection: $V_{ph} = V_L/\sqrt{3}$, $I_{ph} = I_L$.

#### No-load test

$$
\begin{aligned}
P_0 &= W_1 + W_2 = 5000 + (-3200) = 1800\ \text{W} \\
V_{ph} &= \frac{400}{\sqrt{3}} = 230.94\ \text{V} \\
\cos\phi_0 &= \frac{P_0}{\sqrt{3}V_L I_0} = \frac{1800}{\sqrt{3}\times 400 \times 20} = 0.1299, \quad \sin\phi_0 = 0.9915 \\
I_w &= I_0\cos\phi_0 = 20 \times 0.1299 = 2.598\ \text{A} \\
I_\mu &= I_0\sin\phi_0 = 20 \times 0.9915 = 19.83\ \text{A} \\
R_0 &= \frac{V_{ph}}{I_w} = \frac{230.94}{2.598} = 88.89\ \Omega \\
X_0 &= \frac{V_{ph}}{I_\mu} = \frac{230.94}{19.83} = 11.65\ \Omega
\end{aligned}
$$

(The negative reading $W_2$ confirms pf below 0.5, as expected at no load.)

#### Blocked-rotor test

$$
\begin{aligned}
P_{sc} &= W_1 + W_2 = 2300 + 750 = 3050\ \text{W} \\
Z_{eq} &= \frac{V_{sc}/\sqrt{3}}{I_{sc}} = \frac{28.87}{60} = 0.4811\ \Omega \\
R_{eq} &= \frac{P_{sc}}{3I_{sc}^2} = \frac{3050}{3 \times 60^2} = 0.2824\ \Omega \\
X_{eq} &= \sqrt{Z_{eq}^2 - R_{eq}^2} = \sqrt{0.4811^2 - 0.2824^2} = 0.3895\ \Omega
\end{aligned}
$$

Stator resistance is not given, so the usual split is assumed:

$$
\begin{aligned}
R_1 &= R_2' = \frac{R_{eq}}{2} = 0.1412\ \Omega \\
X_1 &= X_2' = \frac{X_{eq}}{2} = 0.1948\ \Omega
\end{aligned}
$$

Note: the power factors were found from $P/(\sqrt{3}VI)$ using the measured V, I and total power; the ratio formula $\tan\phi = \sqrt{3}(W_1 - W_2)/(W_1 + W_2)$ gives different values ($\cos\phi_0 \approx 0.126$ at no load and $\cos\phi_{sc} \approx 0.75$ in the blocked-rotor test, against 0.130 and 0.587 here) because the given readings are not consistent with the measured V and I.

```text
 I1  0.1412  j0.1948      j0.1948  0.1412
 o--[====]--[~~~~]--+---+--[~~~~]--[====]--+
                    |   |                  |
 V=230.94 V    R0=88.89 jX0=11.65   0.1412(1-s)/s
                    |   |                  |
 o------------------+---+------------------+
```

**Answer (per phase, referred to stator): $R_0 = 88.89\ \Omega$, $X_0 = 11.65\ \Omega$, $R_1 = R_2' = 0.1412\ \Omega$, $X_1 = X_2' = 0.1948\ \Omega$.**

## Check yourself

The answer's key points as multiple-choice questions, with the correct option and why.

1. With W1 = 5000 W and W2 = -3200 W in the no-load test, what is the total input power?
   A. 1800 W
   B. 8200 W
   C. 3200 W
   D. 5000 W
   Answer: A. Total power is the algebraic sum of the readings: 5000 + (-3200) = 1800 W. (Key point: Two-wattmeter power)

2. How are R0 and X0 obtained from the no-load test?
   A. R0 = P0/I0^2 and X0 = V/I0
   B. R0 = Vph/Iw and X0 = Vph/Imu, using Iw = I0 cos(phi0) and Imu = I0 sin(phi0)
   C. R0 = Vph/Imu and X0 = Vph/Iw
   D. R0 = Vsc/Isc and X0 = Psc/Isc
   Answer: B. The no-load current splits into a core-loss component Iw and a magnetising component Imu, each with the phase voltage across it. (Key point: Shunt branch from no-load test)

3. How is R_eq found from the blocked rotor test?
   A. R_eq = Vsc/Isc = 0.4811 ohm
   B. R_eq = P_sc/Isc = 50.8 ohm
   C. R_eq = P_sc/(3 Isc^2) = 0.2824 ohm
   D. R_eq = sqrt(Zeq^2 + Xeq^2)
   Answer: C. Total copper loss is 3 Isc^2 R_eq, so R_eq = 3050/(3 x 3600) = 0.2824 ohm. (Key point: Series branch from blocked rotor test)

4. Stator values are not given, so how are R1, R2' and X1, X2' obtained?
   A. Assume R1 = Req and R2' = 0
   B. Assume X1 = Xeq and X2' = 0
   C. Measure them from the no-load test
   D. Assume R1 = R2' = Req/2 and X1 = X2' = Xeq/2
   Answer: D. The usual assumption splits the blocked-rotor values equally, giving 0.1412 ohm and 0.1948 ohm. (Key point: Splitting R and X)

## Related in Electrical Machines I

- [Induction motor equivalent circuit from no-load and blocked rotor tests](https://www.bctengineer.com/question.md?key=semester_4%2Felectrical_machines_i%3Aim-noload-blocked-400v-equivalent) — Electrical Machines I, chapter 5
- [No-load and blocked rotor tests of induction motor](https://www.bctengineer.com/question.md?key=semester_4%2Felectrical_machines_i%3Aim-noload-blocked-rotor-test-explain) — Electrical Machines I, chapter 5
- [Performance of 7.5 kW induction motor from equivalent circuit](https://www.bctengineer.com/question.md?key=semester_4%2Felectrical_machines_i%3Aim-400v-7p5kw-equivalent-circuit-slip2) — Electrical Machines I, chapter 5
- [Equivalent circuit and half-load efficiency of 50 kVA transformer](https://www.bctengineer.com/question.md?key=semester_4%2Felectrical_machines_i%3A50kva-2500-250-test-secondary-half) — Electrical Machines I, chapter 2
- [Starting, no-load and full-load current of slip ring motor](https://www.bctengineer.com/question.md?key=semester_4%2Felectrical_machines_i%3Aslip-ring-0p8-4ohm-400v-ratio4) — Electrical Machines I, chapter 5
- [OC and SC tests to build transformer equivalent circuit](https://www.bctengineer.com/question.md?key=semester_4%2Felectrical_machines_i%3Aoc-sc-test-10kva-6600-220) — Electrical Machines I, chapter 2

## Related in other subjects

- [Two-wattmeter method star load](https://www.bctengineer.com/question.md?key=semester_1%2Fbasic_electrical_and_electronics_engineering%3Atwo-wattmeter-star-load) — Basic Electrical and Electronics Engineering, chapter 1
- [20 kVA 250/2500 V tests, equivalent circuit](https://www.bctengineer.com/question.md?key=semester_4%2Felectrical_machines%3Atf-20kva-250-2500-parameters) — Electrical Machines, chapter 2, asked 2×
- [20 kVA 2200/220 V tests, equivalent circuit LV side](https://www.bctengineer.com/question.md?key=semester_4%2Felectrical_machines%3Atf-20kva-2200-220-lv-equivalent) — Electrical Machines, chapter 2
- [2.2 kW 400 V cage motor (star-delta) design](https://www.bctengineer.com/question.md?key=semester_5%2Felectric_machine_design%3Adesign-2-2kw-400v-star-delta) — Electric Machine Design, chapter 4, asked 3×