title: "Loaded transformer and phasor diagram for inductive load"
subject: "Electrical Machines I"
chapter: 2
key: "semester_4/electrical_machines_i:transformer-loaded-operation-phasor-inductive"
source: https://www.bctengineer.com/q/semester_4/electrical_machines_i/transformer-loaded-operation-phasor-inductive
site: BCT Engineering
---

# Loaded transformer and phasor diagram for inductive load

Electrical Machines I · Chapter 2: Transformer

- Asked in: 2071 Bhadra, 4+3 marks
- Video: [PHASOR DIAGRAM ( INDUCTIVE LOAD) FOR A SINGLE PHASE TRANSFORMER](https://www.youtube.com/watch?v=IKx5yHPn3V8) — Xplanator
- Answer checked by Claude Opus 5.5 (high effort) on 2026-10-14
- Page: https://www.bctengineer.com/q/semester_4/electrical_machines_i/transformer-loaded-operation-phasor-inductive
- Whole chapter: https://www.bctengineer.com/md/semester_4/electrical_machines_i/chapter-2

## Question

Explain the loaded operation of transformer. Draw the phasor diagram of a power transformer for inductive load.

## Short answer

When loaded, secondary MMF opposes main flux, so primary draws an extra current I2' to cancel it, keeping core flux nearly constant. The primary current is I0 + I2'. For an inductive load, I2 lags V2, V2 is less than E2 due to impedance drops, and I1 lags V1.

## Answer

#### Loaded operation of a transformer
When a load is connected to the secondary, a current $I_2$ flows, set by the load: $I_2 = V_2/Z_L$.

1. $I_2$ in $N_2$ turns produces an MMF $N_2I_2$ that, by Lenz's law, **opposes** the main flux $\phi$.
2. The flux tends to fall, so the back EMF $E_1$ falls slightly and the primary draws an extra current $I_2'$ from the supply.
3. $I_2'$ is just large enough for its MMF to cancel the secondary MMF: $N_1I_2' = N_2I_2$, so $I_2' = KI_2$ (with $K = N_2/N_1$).
4. The total primary current is the phasor sum $\bar I_1 = \bar I_0 + \bar I_2'$.
5. Because the net MMF is still $N_1I_0$, the **core flux stays almost constant** from no load to full load, so the iron loss is constant.

In a real transformer the windings have resistance and leakage reactance, so:
$$
\begin{aligned}
\bar V_1 &= -\bar E_1 + \bar I_1(R_1 + jX_1) \\
\bar V_2 &= \bar E_2 - \bar I_2(R_2 + jX_2)
\end{aligned}
$$
As the load increases, these drops increase, so $V_2$ falls (voltage regulation).

#### Phasor diagram for inductive (lagging) load
Steps: draw $\phi$ as the reference; $E_1$ and $E_2$ lag $\phi$ by 90°; $I_0$ leads $\phi$ by a small angle (because of core loss); $I_2$ lags $V_2$ by $\phi_2$; $V_2 = E_2 - I_2R_2 - jI_2X_2$; $I_2'$ is drawn equal and opposite to $I_2$; $I_1 = I_0 + I_2'$; $V_1 = -E_1 + I_1R_1 + jI_1X_1$.

```text
                   V1
                   ^
                  /|  I1.X1 (perpendicular to I1)
                 / |
       -E1 ^    /--+  I1.R1 (parallel to I1)
           |   /
           |  /         ^ I2' (equal and opposite to I2)
           | /        /
           |/       /   ^ I1 = I0 + I2'
           |      /   /
           |    /   /
           |  /   /  ___...---> I0 (leads phi slightly)
           |/  /..--'
  ---------O-------------------------> phi (main flux, reference)
          /|
         / |
        /  |
       v   |
     I2    v V2 = E2 - I2(R2 + jX2)
 (lags V2  |
  by phi2) v E2   (E1 also lies along this line)

  phi1 = angle between V1 and I1; phi2 = angle between V2 and I2
```
(For clarity many textbooks take $K = 1$, so $E_1 = E_2$ and $I_2' = I_2$ in magnitude.)

Key features for an inductive load:
- $I_2$ lags $V_2$ by $\phi_2$, so it points down and to the left of $V_2$; $I_2'$ is exactly opposite to it, lagging $-E_1$.
- $I_1$ lags $V_1$ by $\phi_1$, with $\phi_1$ slightly greater than $\phi_2$ because of $I_0$ and the drops.
- $V_2 < E_2$ and $V_1 > E_1$; the drop is largest for lagging loads.
- On full load $I_0$ is small compared with $I_2'$, so $I_1 \approx I_2'$ and $\frac{I_1}{I_2} \approx K$.

## Check yourself

The answer's key points as multiple-choice questions, with the correct option and why.

1. When load current I2 flows, its MMF N2 I2 tends to:
   A. Increase the main flux
   B. Oppose the main flux
   C. Have no effect on the flux
   D. Reverse the supply voltage
   Answer: B. By Lenz's law it opposes the flux, so the primary draws extra current. (Key point: Secondary MMF effect)

2. The extra primary current I2' satisfies:
   A. N1 I2' = N2 I2
   B. N1 I2' = I0
   C. I2' = I2 / K
   D. I2' = I2 K^2
   Answer: A. I2' cancels the secondary MMF, giving I2' = K I2. (Key point: Primary balance)

3. From no load to full load, the core flux and hence iron loss:
   A. Doubles
   B. Falls to zero
   C. Stays almost constant
   D. Rises as load squared
   Answer: C. The net MMF stays equal to N1 I0, so flux is almost constant. (Key point: Core flux)

4. The total primary current is:
   A. I0 - I2'
   B. The phasor sum I0 + I2'
   C. I2' only
   D. I0 x I2'
   Answer: B. I1 is the phasor sum of the no-load current and the load component I2'. (Key point: Total primary current)

## Related in Electrical Machines I

- [Transformer no-load and load operation, constant core flux](https://www.bctengineer.com/question.md?key=semester_4%2Felectrical_machines_i%3Aideal-transformer-noload-load-constant-flux) — Electrical Machines I, chapter 2, asked 5×
- [Real transformer no-load operation and amp-turn balance](https://www.bctengineer.com/question.md?key=semester_4%2Felectrical_machines_i%3Areal-transformer-noload-amp-turn-balance) — Electrical Machines I, chapter 2
- [Transformer no-load operation and ideal transformer properties](https://www.bctengineer.com/question.md?key=semester_4%2Felectrical_machines_i%3Atransformer-no-load-ideal-properties) — Electrical Machines I, chapter 2
- [Full-load efficiency of 500 kVA transformer](https://www.bctengineer.com/question.md?key=semester_4%2Felectrical_machines_i%3A500kva-90pc-half-load-full-load) — Electrical Machines I, chapter 2
- [Full-load and half-load efficiency of 100 kVA transformer](https://www.bctengineer.com/question.md?key=semester_4%2Felectrical_machines_i%3A100kva-1200w-960w-efficiency) — Electrical Machines I, chapter 2
- [Efficiency of 5 kVA transformer at 2 kW load](https://www.bctengineer.com/question.md?key=semester_4%2Felectrical_machines_i%3A5kva-1100-110-max-efficiency-40a) — Electrical Machines I, chapter 2

## Related in other subjects

- [Practical vs ideal transformer, phasor diagram](https://www.bctengineer.com/question.md?key=semester_4%2Felectrical_machines%3Apractical-vs-ideal-transformer-phasor) — Electrical Machines, chapter 2
- [No-load and loaded operation, constant flux](https://www.bctengineer.com/question.md?key=semester_4%2Felectrical_machines%3Aideal-transformer-no-load-loaded-flux) — Electrical Machines, chapter 2, asked 3×
- [Transformer on load, phasor diagrams](https://www.bctengineer.com/question.md?key=semester_4%2Felectrical_machine%3Atransformer-phasor-resistive-capacitive) — Electrical Machine, chapter 2
- [Transformer on load and no load, phasor diagrams](https://www.bctengineer.com/question.md?key=semester_4%2Felectrical_machines%3Atransformer-load-phasor-resistive-capacitive) — Electrical Machines, chapter 2