title: "OC/SC test of 2200/110 V, 40 kVA transformer"
subject: "Electrical Machines I"
chapter: 2
key: "semester_4/electrical_machines_i:transformer-oc-sc-2200-110-40kva"
source: https://www.bctengineer.com/q/semester_4/electrical_machines_i/transformer-oc-sc-2200-110-40kva
site: BCT Engineering
---

# OC/SC test of 2200/110 V, 40 kVA transformer

Electrical Machines I · Chapter 2: Transformer

- Asked in: 2082 Kartik (new course), 6 marks
- Video: [35. OPEN CIRCUIT TEST, SHORT CIRCUIT TEST NUMERICAL PROBLEM, FIND TRANSFORMER CIRCUIT CONSTANT](https://www.youtube.com/watch?v=PCpJF99BoZs) — Electrical Tutorial
- Answer checked by Claude Opus 5.5 (high effort) on 2026-10-14
- Page: https://www.bctengineer.com/q/semester_4/electrical_machines_i/transformer-oc-sc-2200-110-40kva
- Whole chapter: https://www.bctengineer.com/md/semester_4/electrical_machines_i/chapter-2

## Question

During open circuit and short circuit test of a 2200/110 V, 40 kVA transformer, following results were obtained. The meters for open circuit test were placed on LV side and for short circuit test on HV side.
Open circuit: P = 320 W; I = 8.4 A; V = 110 V
Short circuit: P = 650 W; I = 18.2 A; V = 85 V
Determine: (i) R0 and X0 (ii) The efficiency at full load with pf 0.85 lag (iii) The approx. voltage regulation

## Short answer

R₀ = 37.81 Ω, X₀ = 13.96 Ω (LV side). Full-load efficiency at 0.85 pf lag is 97.23%. Approximate voltage regulation is 3.22%.

## Answer

The OC test (LV side) gives the shunt branch; the SC test (HV side) gives the series impedance referred to HV. Rated HV current $= 40000/2200 = 18.18$ A, so the SC test (18.2 A) is practically at full load.

#### (i) $R_0$ and $X_0$ (LV side)

$$
\begin{aligned}
\cos\phi_0 &= \frac{320}{110\times8.4} = 0.3463 \\
I_c &= 8.4\times0.3463 = 2.909\ \text{A}, \quad I_m = 8.4\times\sin(69.74^\circ) = 7.880\ \text{A} \\
R_0 &= \frac{110}{2.909} = 37.81\ \Omega, \quad X_0 = \frac{110}{7.880} = 13.96\ \Omega
\end{aligned}
$$

#### SC test values (HV side)

$$
\begin{aligned}
R_{eq} &= \frac{650}{18.2^2} = 1.962\ \Omega, \quad Z_{eq} = \frac{85}{18.2} = 4.670\ \Omega \\
X_{eq} &= \sqrt{4.670^2 - 1.962^2} = 4.238\ \Omega
\end{aligned}
$$

#### (ii) Full-load efficiency at 0.85 pf lag

Full-load copper loss (corrected to rated current 18.18 A):

$$
\begin{aligned}
P_{cu,fl} &= 650\left(\frac{18.18}{18.2}\right)^2 = 648.7\ \text{W} \\
P_{out} &= 40000\times0.85 = 34000\ \text{W} \\
\eta &= \frac{34000}{34000 + 320 + 648.7} = \frac{34000}{34968.7} = 97.23\%
\end{aligned}
$$

#### (iii) Approximate voltage regulation (0.85 pf lag, $\sin\phi = 0.527$)

$$
\begin{aligned}
\%R &= \frac{I(R_{eq}\cos\phi + X_{eq}\sin\phi)}{V}\times100 \\
&= \frac{18.18(1.962\times0.85 + 4.238\times0.527)}{2200}\times100 \\
&= \frac{30.33 + 40.59}{2200}\times100 = 3.22\%
\end{aligned}
$$

**Answer:** $R_0 = 37.81\ \Omega$, $X_0 = 13.96\ \Omega$ (LV side); full-load efficiency = **97.23%**; regulation ≈ **3.22%**.

## Check yourself

The answer's key points as multiple-choice questions, with the correct option and why.

1. How are R0 and X0 found?
   A. R0 = P/I0² = 4.5 Ω, X0 from the SC test
   B. Ic = I0 cos φ0 and Im = I0 sin φ0, then R0 = V/Ic, X0 = V/Im, giving 37.81 Ω and 13.96 Ω
   C. R0 = V/I0 = 13.1 Ω and X0 = 0
   D. R0 = 650/18.2² and X0 = 4.24 Ω
   Answer: B. cos φ0 = 320/(110×8.4) = 0.3463, so Ic = 2.909 A and Im = 7.88 A. (Key point: Shunt branch)

2. Why is the SC copper loss corrected to 650×(18.18/18.2)²?
   A. Because the SC test was at half load
   B. Rated HV current is 40000/2200 = 18.18 A, and Cu loss varies as I²
   C. Because iron loss adds to the SC reading
   D. Because rated HV current is 8.4 A
   Answer: B. Copper loss at rated current is 648.7 W. (Key point: Full-load copper loss)

3. What is the full-load efficiency at 0.85 pf lag?
   A. 97.9%, from 40000/(40000 + 320 + 648.7)
   B. 99.1%, because iron loss is ignored
   C. 97.23%, from 34000/(34000 + 320 + 648.7)
   D. 95.2%, because losses are counted twice
   Answer: C. Output = 40000 × 0.85 = 34 kW, and losses are iron 320 W plus full-load copper 648.7 W. (Key point: Efficiency)

4. What is the approximate regulation formula and value?
   A. I(Req cos φ − Xeq sin φ)/V ×100 ≈ 0.4%
   B. I(Req cos φ + Xeq sin φ)/V ×100 ≈ 3.22%
   C. I Zeq/V ×100 = 3.86% always
   D. I(Req sin φ + Xeq cos φ)/V ×100 ≈ 3.3%
   Answer: B. For lagging pf the two drops add: 30.33 + 40.59 = 70.92 V of 2200 V. (Key point: Regulation)

## Related in Electrical Machines I

- [Equivalent circuit of 100 kVA 2200/220 V transformer](https://www.bctengineer.com/question.md?key=semester_4%2Felectrical_machines_i%3Aoc-sc-100kva-2200-220-hv) — Electrical Machines I, chapter 2, asked 3×
- [OC and SC tests to build transformer equivalent circuit](https://www.bctengineer.com/question.md?key=semester_4%2Felectrical_machines_i%3Aoc-sc-test-10kva-6600-220) — Electrical Machines I, chapter 2
- [Equivalent circuit of 20 kVA 220/2200 V transformer](https://www.bctengineer.com/question.md?key=semester_4%2Felectrical_machines_i%3Aoc-sc-20kva-220-2200-primary) — Electrical Machines I, chapter 2
- [Equivalent circuit, efficiency and regulation of 5 kVA transformer](https://www.bctengineer.com/question.md?key=semester_4%2Felectrical_machines_i%3Aoc-sc-5kva-220-400-lv) — Electrical Machines I, chapter 2
- [Equivalent circuit of 8 kVA 400/120 V transformer](https://www.bctengineer.com/question.md?key=semester_4%2Felectrical_machines_i%3Aoc-sc-8kva-400-120-hv) — Electrical Machines I, chapter 2
- [Equivalent circuit of 5 kVA 200/400 V transformer](https://www.bctengineer.com/question.md?key=semester_4%2Felectrical_machines_i%3Aoc-sc-5kva-200-400-primary) — Electrical Machines I, chapter 2, asked 2×

## Related in other subjects

- [20 kVA 2200/220 V, LV-side circuit](https://www.bctengineer.com/question.md?key=semester_4%2Felectrical_machine%3Atransformer-20kva-2200-220-lv-side) — Electrical Machine, chapter 2
- [20 kVA 2200/220 V tests, equivalent circuit LV side](https://www.bctengineer.com/question.md?key=semester_4%2Felectrical_machines%3Atf-20kva-2200-220-lv-equivalent) — Electrical Machines, chapter 2
- [10 kVA 200/400 V LV-side parameters](https://www.bctengineer.com/question.md?key=semester_4%2Felectrical_machine%3Atransformer-10kva-oc-sc-lv-circuit) — Electrical Machine, chapter 2
- [10 kVA 200/400 V tests, parameters on LV side](https://www.bctengineer.com/question.md?key=semester_4%2Felectrical_machines%3Atf-10kva-200-400-lv-params) — Electrical Machines, chapter 2