title: "33 kV, 15 MW line: efficiency and regulation"
subject: "Power System Analysis I"
chapter: 6
key: "semester_4/power_system_analysis_i:33kv-15mw-efficiency-regulation"
source: https://www.bctengineer.com/q/semester_4/power_system_analysis_i/33kv-15mw-efficiency-regulation
site: BCT Engineering
---

# 33 kV, 15 MW line: efficiency and regulation

Power System Analysis I · Chapter 6: Performance Analysis

- Asked in: 2072 Asoj, 6 marks
- Video: [Transmission line: efficiency and regulation](https://www.youtube.com/watch?v=CmoRX8gfGDs) — SHAHRIN BIN MD AYOB FKE
- Answer checked by Claude Opus 5.5 (high effort) on 2026-10-14
- Page: https://www.bctengineer.com/q/semester_4/power_system_analysis_i/33kv-15mw-efficiency-regulation
- Whole chapter: https://www.bctengineer.com/md/semester_4/power_system_analysis_i/chapter-6

## Question

A 3-phase, 50 Hz, 33 kV transmission line is delivering a load of 15 MW at 0.9 pf lagging. The line series impedance per phase is 5 + j18 Ω. Determine the power transmission efficiency and voltage regulation of the line. Construct the phasor diagram of currents and voltages in the line.

## Short answer

The transmission efficiency is 92.16% and voltage regulation is 20.82% (sending-end line voltage 39.87 kV). The phasor diagram shows VR as reference, I lagging by 25.84°, and VS leading VR by 10.23° with IR and IX drops added.

## Answer

Short line: $Z = 5 + j18\ \Omega$/phase, shunt capacitance neglected.

#### Current
$$
\begin{aligned}
V_R &= 33\,000/\sqrt3 = 19\,052.6\angle0^\circ\ \text{V} \\
I &= \frac{15\times10^6}{\sqrt3\times33\,000\times0.9} = 291.59\ \text{A},\quad \phi_R = 25.84^\circ\ \text{lag}
\end{aligned}
$$

#### Efficiency
$$
\begin{aligned}
P_{loss} &= 3I^2R = 3(291.59)^2(5) = 1.275\ \text{MW} \\
\eta &= \frac{15}{15 + 1.275}\times100 = 92.16\%
\end{aligned}
$$

#### Voltage regulation
$$
\begin{aligned}
IR &= 1458.0\angle-25.84^\circ\ \text{V},\quad IX = 5248.6\angle64.16^\circ\ \text{V} \\
V_S &= V_R + I(R + jX) = 19\,052.6 + 5447.4\angle48.63^\circ \\
&= 23\,018.5\angle10.23^\circ\ \text{V}
\end{aligned}
$$
Line value $= \sqrt3\times23.019 = 39.87$ kV.
$$
\%VR = \frac{23\,018.5 - 19\,052.6}{19\,052.6}\times100 = 20.82\%
$$

#### Phasor diagram (lagging load)
```text
                         Vs (23.02 kV, 10.23 deg)
                        /|
                       / | I*X (5.25 kV, leads I by 90)
                      /  |
                     /   |
     O-------------------+--> I*R (1.46 kV, along I)
      \        Vr (19.05 kV, reference)
       \
        \  phi_R = 25.84 deg
         v
          I (291.6 A)
```
- $V_R$ is the reference.
- $I$ lags $V_R$ by $\phi_R = 25.84^\circ$.
- $IR$ is drawn from the tip of $V_R$ parallel to $I$; $IX$ is drawn from its tip, perpendicular to $I$ (leading).
- $V_S$ joins $O$ to the end of $IX$ and leads $V_R$ by $\delta = 10.23^\circ$; $I$ lags $V_S$ by $36.07^\circ$ (sending pf 0.808 lag).

**Answer: Efficiency ≈ 92.16 %, regulation ≈ 20.82 % ($V_S$ = 39.87 kV).**

## Check yourself

The answer's key points as multiple-choice questions, with the correct option and why.

1. How is the load current found?
   A. I = P/(3 V_L)
   B. I = P/V_L
   C. I = P cos(phi)/V_L
   D. I = P/(sqrt3 V_L cos phi) = 291.59 A
   Answer: D. 15e6/(sqrt3 x 33000 x 0.9) = 291.59 A. (Key point: Current)

2. What gives the efficiency?
   A. 15/33
   B. 3I^2R = 1.275 MW and eta = 15/(15 + 1.275) = 92.16 %
   C. 3I^2X
   D. I^2R single phase
   Answer: B. Only R dissipates: 3 x 291.59^2 x 5 = 1.275 MW. (Key point: Efficiency)

3. In the phasor diagram for the lagging load, how are drops drawn?
   A. Both along V_R
   B. IX lags I
   C. IR along I, IX perpendicular leading I by 90 degrees, added to V_R
   D. IR perpendicular, IX along I
   Answer: C. V_S = V_R + IR (parallel to I) + jIX (leading I by 90 degrees). (Key point: Phasor diagram)

4. What is the regulation?
   A. (39.87 - 33)/39.87
   B. (33 - 39.87)/33
   C. 6.9 %
   D. (23018.5 - 19052.6)/19052.6 = 20.82 %
   Answer: D. Phase values: V_S = 23.02 kV, V_R = 19.05 kV. (Key point: Regulation)

## Related in Power System Analysis I

- [33 kV, 12 MW leading load: efficiency, zero regulation](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3A33kv-12mw-leading-efficiency) — Power System Analysis I, chapter 6, asked 2×
- [Compensation capacity for 15 MW, 33 kV load](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3Acompensation-capacity-15mw-33kv) — Power System Analysis I, chapter 6
- [70 km, 40 MW line: regulation and zero-regulation pf](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3A70km-40mw-regulation) — Power System Analysis I, chapter 6
- [450 km 400 kV line, 420 MW, 0.9 pf](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3A450km-400kv-420mw-090) — Power System Analysis I, chapter 5
- [Efficiency at 0.995 leading pf and zero regulation](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3Aleading-pf-efficiency-zero-regulation) — Power System Analysis I, chapter 6
- [Regulation and efficiency of 100 km, 110 kV line](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3Aregulation-efficiency-100km-110kv) — Power System Analysis I, chapter 6, asked 2×

## Related in other subjects

- [Current, pf, power and efficiency of 3.3 kV motor](https://www.bctengineer.com/question.md?key=semester_5%2Felectric_machines_ii%3Amotor-3-3kv-efficiency) — Electric Machines II, chapter 2
- [220 kV double circuit efficiency and regulation](https://www.bctengineer.com/question.md?key=semester_8%2Ftransmission_and_distribution_system_design%3Adouble-circuit-220kv-efficiency-regulation) — Transmission and Distribution System Design, chapter 4
- [Currents and efficiency of 132/11 kV transformer at 5 MW](https://www.bctengineer.com/question.md?key=semester_4%2Felectrical_machines_i%3Astar-delta-132-11kv-5mw-currents) — Electrical Machines I, chapter 2, asked 3×
- [Voltage regulation of transformer for lagging load](https://www.bctengineer.com/question.md?key=semester_4%2Felectrical_machines_i%3Avoltage-regulation-define-lagging-expression) — Electrical Machines I, chapter 2