# 450 km 400 kV line, 420 MW, 0.9 pf

Power System Analysis I · Chapter 5: Transmission Line Modeling

- Asked in: 2069 Poush, 10 marks
- Answer checked by Claude Opus 5.5 (high effort) on 2026-10-14
- Page: https://www.bctengineer.com/q/semester_4/power_system_analysis_i/450km-400kv-420mw-090
- Whole chapter: https://www.bctengineer.com/md/semester_4/power_system_analysis_i/chapter-5

## Question

A 450 km long, 50 Hz, 400 kV overhead transmission line has series resistance of 0.033 Ohm/km, series inductance of 1.067 mH/km and shunt capacitance of 0.0109 × 10⁻⁶ F/km. Compute the ABCD parameters, sending end active power, voltage and currents, and voltage regulation if the line is supplying a load of 420 MW at 0.9 power factor lagging. Also compute the power transmission efficiency of the line.

## Short answer

Using long-line model: A = D = 0.8861∠0.71°, B = 145.8∠84.60° Ω, C = 1.482×10⁻³∠90.22° S. Sending-end voltage = 467.27 kV, current = 546.3 A, active power = 436.24 MW. Voltage regulation = 31.84 %, efficiency = 96.28 %.

## Answer

**Given:** 50 Hz, 400 kV, $l = 450$ km; $r = 0.033\ \Omega$/km, $L = 1.067$ mH/km, $C = 0.0109\ \mu$F/km; load 420 MW at 0.9 p.f. lagging at 400 kV. Long-line model is used.

#### Step 1: Line constants

$$
\begin{aligned}
z &= 0.033 + j(2\pi\times50\times1.067\times10^{-3}) = 0.033 + j0.3352\ \Omega/\text{km} \\
y &= j2\pi\times50\times0.0109\times10^{-6} = j3.424\times10^{-6}\ \text{S/km} \\
Z &= zl = 14.85 + j150.84 = 151.6\angle 84.38^\circ\ \Omega, \quad Y = yl = j1.541\times10^{-3}\ \text{S}
\end{aligned}
$$

#### Step 2: ABCD parameters

$$
\begin{aligned}
\gamma l &= \sqrt{ZY} = 0.4833\angle 87.19^\circ = 0.02370 + j0.48271 \\
Z_c &= \sqrt{Z/Y} = 313.6\angle -2.81^\circ\ \Omega \\
A = D &= \cosh\gamma l = 0.88599 + j0.01100 = 0.8861\angle 0.71^\circ \\
B &= Z_c\sinh\gamma l = 145.8\angle 84.60^\circ\ \Omega \\
C &= \frac{\sinh\gamma l}{Z_c} = 1.482\times10^{-3}\angle 90.22^\circ\ \text{S}
\end{aligned}
$$

#### Step 3: Receiving-end values

$$
\begin{aligned}
V_R &= \frac{400}{\sqrt3} = 230.94\angle 0^\circ\ \text{kV} \\
I_R &= \frac{420\times10^6}{\sqrt3\times400\times10^3\times0.9} = 673.6\angle -25.84^\circ = 606.22 - j293.60\ \text{A}
\end{aligned}
$$

#### Step 4: Sending-end voltage and current

$$
\begin{aligned}
V_S &= AV_R + BI_R = (204{,}610 + j2541) + (50{,}925 + j83{,}948) \\
&= 255{,}540 + j86{,}489 = 269.78\angle 18.70^\circ\ \text{kV/phase} \\
V_{S(L)} &= \sqrt3\times269.78 = 467.27\ \text{kV} \\
I_S &= CV_R + DI_R = (-1.33 + j342.24) + (540.33 - j253.46) \\
&= 539.01 + j88.78 = 546.3\angle 9.35^\circ\ \text{A}
\end{aligned}
$$

#### Step 5: Sending-end power
p.f. $= \cos(18.70^\circ - 9.35^\circ) = 0.9867$ lagging

$$
P_S = 3|V_S||I_S|\cos\phi_S = 3\times269.78\times10^3\times546.3\times0.9867 = 436.24\ \text{MW}
$$

#### Step 6: Voltage regulation

$$
\begin{aligned}
V_{R(NL)} &= \frac{|V_S|}{|A|} = \frac{467.27}{0.8861} = 527.35\ \text{kV (line)} \\
\%\text{VR} &= \frac{527.35 - 400}{400}\times100 = 31.84\ \%
\end{aligned}
$$

#### Step 7: Efficiency

$$
\eta = \frac{P_R}{P_S}\times100 = \frac{420}{436.24}\times100 = 96.28\ \%
$$

**Answer:** $A = D = 0.8861\angle 0.71^\circ$, $B = 145.8\angle 84.60^\circ\ \Omega$, $C = 1.482\times10^{-3}\angle 90.22^\circ$ S; $V_S = 467.27$ kV, $I_S = 546.3$ A, $P_S = 436.24$ MW, regulation $= 31.84\%$, efficiency $= 96.28\%$.

## Check yourself

The answer's key points as multiple-choice questions, with the correct option and why.

1. What is IR for 420 MW, 400 kV, 0.9 p.f. lagging?
   A. About 673.6 A at -25.84°
   B. About 638 A at -18.19°
   C. About 606 A at 0°
   D. About 673.6 A at +25.84°
   Answer: A. IR = 420e6/(sqrt3 x 400e3 x 0.9) = 673.6 A, lagging by cos^-1(0.9) = 25.84°. (Key point: Receiving-end current at 0.9 p.f.)

2. How is the voltage regulation computed here?
   A. (VS - VR)/VR
   B. VR(NL) = |VS|/|A|, then (VR(NL) - VR(FL))/VR(FL) x 100
   C. (VR - VS)/VS
   D. |A| x 100
   Answer: B. At no load VS = A VR, so VR(NL) = 467.27/0.8861 = 527.35 kV and regulation is (527.35 - 400)/400 = 31.84%. (Key point: Voltage regulation method)

3. How is the transmission efficiency found?
   A. PR/PS x 100 = 420/436.24
   B. PS/PR x 100
   C. (VR/VS) x 100
   D. cos φ x 100
   Answer: A. Efficiency is output over input power: 420/436.24 = 96.28%. (Key point: Efficiency)

4. How is PS computed from the sending-end quantities?
   A. PS = 3 |VS| |IS| cos(angle VS - angle IS) using phase values
   B. PS = |VS(L)| |IS|
   C. PS = sqrt3 |VS| |IS| with phase VS
   D. PS = 3 |VS| |IS| cos(angle of VS)
   Answer: A. Three-phase power is 3 times per-phase VS IS times the cosine of the angle between them (9.35°), giving 436.24 MW. (Key point: Sending-end power)

## Related in Power System Analysis I

- [450 km 400 kV line, 420 MW, 0.95 pf](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3A450km-400kv-420mw-095) — Power System Analysis I, chapter 5
- [Voltage 150 km along a 400 km line](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3A400km-voltage-at-150km) — Power System Analysis I, chapter 5
- [400 km line at UPF: Zc, propagation, regulation](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3A400km-upf-zc-regulation) — Power System Analysis I, chapter 5
- [110 km, 110 kV line: sending end, regulation, efficiency](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3A110km-line-performance) — Power System Analysis I, chapter 6, asked 2×
- [280 km, 60 Hz line: nominal-π vs long line](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3A280km-60hz-nominal-pi-long) — Power System Analysis I, chapter 5, asked 2×
- [Nominal-T 100 km line, 50 MVA at 132 kV](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3Anominal-t-100km-50mva) — Power System Analysis I, chapter 6

## Related in other subjects

- [Conductor selection, 100 MW 70 km 132 kV](https://www.bctengineer.com/question.md?key=semester_8%2Ftransmission_and_distribution_system_design%3Aconductor-selection-100mw-70km-132kv) — Transmission and Distribution System Design, chapter 4
- [Inductance of 420 kV line, transposed and untransposed](https://www.bctengineer.com/question.md?key=semester_8%2Fhigh_voltage_engineering%3Ainductance-420kv-transposed) — High Voltage Engineering, chapter 5