# 8 km line receiving 15000 kVA at 33 kV

Power System Analysis I · Chapter 6: Performance Analysis

- Asked in: 2073 Bhadra, 8 marks
- Video: [Calculate sending end voltage & efficiency](https://www.youtube.com/watch?v=kV6ZJxx5OHA) — Deepak Narkhede
- Answer checked by Claude Opus 5.5 (high effort) on 2026-10-14
- Page: https://www.bctengineer.com/q/semester_4/power_system_analysis_i/8km-line-15000kva
- Whole chapter: https://www.bctengineer.com/md/semester_4/power_system_analysis_i/chapter-6

## Question

15000 kVA is received at 33 kV at 0.85 power factor lagging over an 8 km three-phase overhead transmission line. Each line has R = 0.29 ohm/km and X = 0.65 ohm/km. Calculate: (i) voltage at the sending end (ii) power factor at the sending end (iii) voltage regulation of the line (iv) efficiency of the transmission line.

## Short answer

Sending end voltage = 35.17 kV, sending end power factor = 0.828 lagging, voltage regulation = 6.58%, efficiency = 96.38%.

## Answer

Short line (8 km): shunt capacitance neglected.

#### Data
$$
\begin{aligned}
R &= 0.29\times8 = 2.32\ \Omega,\quad X = 0.65\times8 = 5.2\ \Omega \\
V_R &= 33\,000/\sqrt3 = 19\,052.6\ \text{V} \\
I &= \frac{15\,000\times10^3}{\sqrt3\times33\,000} = 262.43\ \text{A} \\
\cos\phi_R &= 0.85,\ \sin\phi_R = 0.527
\end{aligned}
$$

#### (i) Sending-end voltage
$$
\begin{aligned}
V_S &= V_R + I\angle-31.79^\circ\,(2.32 + j5.2) \\
&= 19\,052.6 + 1494.3\angle34.17^\circ \\
&= 20\,288.6 + j839.3 = 20\,306.3\angle2.37^\circ\ \text{V}
\end{aligned}
$$
Line value $= \sqrt3\times20\,306.3 = 35.17$ kV.

#### (ii) Sending-end pf
Angle between $V_S$ and $I$ $= 2.37^\circ + 31.79^\circ = 34.16^\circ$.
$$
\cos\phi_S = \cos34.16^\circ = 0.828\ \text{lagging}
$$

#### (iii) Voltage regulation
$$
\%VR = \frac{35.17 - 33}{33}\times100 = 6.58\%
$$

#### (iv) Efficiency
$$
\begin{aligned}
P_R &= 15\,000\times0.85 = 12\,750\ \text{kW} \\
P_{loss} &= 3I^2R = 3(262.43)^2(2.32) = 479.3\ \text{kW} \\
\eta &= \frac{12\,750}{12\,750 + 479.3}\times100 = 96.38\%
\end{aligned}
$$

**Answer: (i) 35.17 kV, (ii) 0.828 lagging, (iii) 6.58 %, (iv) 96.38 %.**

## Check yourself

The answer's key points as multiple-choice questions, with the correct option and why.

1. How is V_S obtained for this 8 km line?
   A. V_S = V_R - IZ
   B. V_S = V_R + IR only
   C. V_S = I Z
   D. V_S = V_R + I(R + jX) with I at -31.79 degrees (lagging)
   Answer: D. Short line: V_S = V_R + I Z with cos(phi) = 0.85 lagging, giving 35.17 kV line. (Key point: Sending voltage)

2. How is the sending-end pf found?
   A. cos of angle of V_S only
   B. cos of (delta + phi_R) = cos(2.37 + 31.79) = 0.828 lagging
   C. cos(31.79) = 0.85
   D. cos(delta) = 0.999
   Answer: B. The angle between V_S and I is the power angle plus the receiving pf angle, since I lags V_R by phi_R and V_S leads V_R by delta. (Key point: Sending pf)

3. What is the regulation?
   A. I R/V_S x 100
   B. (35.17 - 33)/33 = 6.58 %
   C. (35.17 - 33)/35.17
   D. (33 - 35.17)/33
   Answer: B. Short line: (V_S - V_R)/V_R using line values. (Key point: Regulation)

4. How is efficiency calculated?
   A. 12750/15000
   B. loss = 3I^2X
   C. 12750/(12750 + 479.3) = 96.38 % with loss = 3I^2R
   D. 15000/(15000 + 479)
   Answer: C. P_R = 15000 x 0.85 kW; copper loss = 3(262.43)^2(2.32) = 479.3 kW. (Key point: Efficiency)

## Related in Power System Analysis I

- [Power output with 46.85 kV sending, 33 kV receiving](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3Apower-output-46-85kv-33kv) — Power System Analysis I, chapter 6
- [110 km, 110 kV line: sending end, regulation, efficiency](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3A110km-line-performance) — Power System Analysis I, chapter 6, asked 2×
- [Receiving and sending end powers from ABCD, 132/134 kV](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3Aabcd-power-132kv-134kv) — Power System Analysis I, chapter 6
- [Voltage 150 km along a 400 km line](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3A400km-voltage-at-150km) — Power System Analysis I, chapter 5
- [Sending and receiving power, 140∠10° and 132 kV](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3Apower-140kv-132kv-a099) — Power System Analysis I, chapter 6
- [12 km 33 kV line: losses, zero-regulation capacitor](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3A12km-33kv-losses-zero-regulation) — Power System Analysis I, chapter 6

## Related in other subjects

- [Peterson coil for 33 kV 60 km line](https://www.bctengineer.com/question.md?key=semester_6%2Fswitchgear_and_protection%3Apeterson-coil-33kv-60km) — Switchgear and Protection, chapter 5, asked 6×
- [Initial line design for 200 MW over 120 km](https://www.bctengineer.com/question.md?key=semester_8%2Ftransmission_and_distribution_system_design%3Aline-design-200mw-120km) — Transmission and Distribution System Design, chapter 2
- [Received power: 100 MHz, 0.75 km](https://www.bctengineer.com/question.md?key=semester_6%2Fpropagation_and_antenna%3Areceived-power-100mhz-0-75km) — Propagation and Antenna, chapter 5
- [Received power: 15.5 km, 3.4 GHz, dish receiver](https://www.bctengineer.com/question.md?key=semester_6%2Fpropagation_and_antenna%3Amax-received-power-15-5km) — Propagation and Antenna, chapter 5