title: "Receiving and sending end powers from ABCD, 132/134 kV"
subject: "Power System Analysis I"
chapter: 6
key: "semester_4/power_system_analysis_i:abcd-power-132kv-134kv"
source: https://www.bctengineer.com/q/semester_4/power_system_analysis_i/abcd-power-132kv-134kv
site: BCT Engineering
---

# Receiving and sending end powers from ABCD, 132/134 kV

Power System Analysis I · Chapter 6: Performance Analysis

- Asked in: 2080 Chaitra, 4+6 marks
- Video: [Power system II _Unit01_Steps to draw receiving end circle diagram of transmission line](https://www.youtube.com/watch?v=qt0qW_Iahlg) — Elite Academy
- Answer checked by Claude Opus 5.5 (high effort) on 2026-10-14
- Page: https://www.bctengineer.com/q/semester_4/power_system_analysis_i/abcd-power-132kv-134kv
- Whole chapter: https://www.bctengineer.com/md/semester_4/power_system_analysis_i/chapter-6

## Question

A 50 Hz, three-phase overhead line has the following parameters: A = 0.98∠0.8°; B = 45∠74° Ω; VSL = 132∠10° kV, VRL = 134∠0° kV. Determine the receiving end active and reactive power, power factor and line losses. Also find out the sending end active and reactive power, power factor and voltage regulation of the line.

## Short answer

From ABCD parameters and voltages, using power-circle equations: receiving power 59.29 MW, −21.07 MVAr, pf 0.942 leading; sending power 68.59 MW, −27.65 MVAr, pf 0.927 leading; loss 9.30 MW; regulation 0.52 % (no-load voltage 134.69 kV).

## Answer

Use the power-circle equations (taking $D = A$). Let $A = |A|\angle\alpha$, $B = |B|\angle\beta$, $V_S$ leading $V_R$ by $\delta$. With line voltages in kV, powers come out directly in three-phase MW/MVAr.

Data: $|A| = 0.98$, $\alpha = 0.8^\circ$, $|B| = 45\ \Omega$, $\beta = 74^\circ$, $|V_S| = 132$ kV, $|V_R| = 134$ kV, $\delta = 10^\circ$.

Useful terms:
$$
\begin{aligned}
\frac{|V_S||V_R|}{|B|} &= \frac{132\times134}{45} = 393.07 \\
\frac{|A||V_R|^2}{|B|} &= \frac{0.98\times134^2}{45} = 391.04 \\
\frac{|A||V_S|^2}{|B|} &= \frac{0.98\times132^2}{45} = 379.46
\end{aligned}
$$
Angles: $\beta-\delta = 64^\circ$, $\beta-\alpha = 73.2^\circ$, $\beta+\delta = 84^\circ$.

#### Receiving end
$$
\begin{aligned}
P_R &= 393.07\cos64^\circ - 391.04\cos73.2^\circ = 59.29\ \text{MW} \\
Q_R &= 393.07\sin64^\circ - 391.04\sin73.2^\circ = -21.07\ \text{MVAr} \\
\text{pf}_R &= \frac{59.29}{\sqrt{59.29^2 + 21.07^2}} = 0.942
\end{aligned}
$$
$Q_R$ is negative, so reactive power flows from the receiving end into the line: the receiving-end pf is **0.942 leading**. This is expected because $|V_R| > |V_S|$.

#### Sending end
$$
\begin{aligned}
P_S &= 379.46\cos73.2^\circ - 393.07\cos84^\circ = 68.59\ \text{MW} \\
Q_S &= 379.46\sin73.2^\circ - 393.07\sin84^\circ = -27.65\ \text{MVAr} \\
\text{pf}_S &= \frac{68.59}{\sqrt{68.59^2 + 27.65^2}} = 0.927\ \text{(leading)}
\end{aligned}
$$

#### Line losses
$$
\begin{aligned}
P_{loss} &= P_S - P_R = 68.59 - 59.29 = 9.30\ \text{MW} \\
Q_S - Q_R &= -27.65 - (-21.07) = -6.59\ \text{MVAr}
\end{aligned}
$$
The negative reactive difference means the line, on net, generates about 6.59 MVAr (its charging exceeds its $I^2X$ absorption).

#### Voltage regulation
No-load receiving voltage $= |V_S|/|A| = 132/0.98 = 134.69$ kV.
$$
\%VR = \frac{134.69 - 134}{134}\times100 = 0.52\%
$$

**Answer: $P_R$ = 59.29 MW, $Q_R$ = −21.07 MVAr, pf 0.942 lead; $P_S$ = 68.59 MW, $Q_S$ = −27.65 MVAr, pf 0.927 lead; loss 9.30 MW; regulation 0.52 %.**

## Check yourself

The answer's key points as multiple-choice questions, with the correct option and why.

1. Which equation set gives receiving power for given V_S, V_R, delta?
   A. P_R = |VsVr/B| cos(beta - delta) - |A Vr^2/B| cos(beta - alpha), and the sine form for Q_R
   B. P_R = |VsVr/B| cos(beta + delta) - ...
   C. P_R = |Vs||Vr| sin(delta)/X only
   D. P_R = 3 V I cos(phi) with I from load
   Answer: A. These are the power-circle equations with line voltages giving three-phase MW. (Key point: Equations used)

2. Q_R = -21.07 MVAr. What does it mean?
   A. Load is lagging at 0.942
   B. Reactive power flows from the receiving end into the line; pf is leading (0.942)
   C. Line absorbs 21 MVAr
   D. Calculation is wrong
   Answer: B. Negative Q_R means leading load, consistent with |V_R| > |V_S|. (Key point: Negative Q_R)

3. How is regulation found here?
   A. (132 - 134)/132
   B. |V_S| x |A|
   C. (|V_S|/|A| - |V_R|)/|V_R| x 100 = 0.52 %
   D. (P_S - P_R)/P_S
   Answer: C. No-load voltage is 132/0.98 = 134.69 kV. (Key point: Regulation)

4. How are active losses calculated?
   A. P_R - P_S
   B. Q_S - Q_R
   C. |V_S| - |V_R|
   D. P_S - P_R = 68.59 - 59.29 = 9.30 MW
   Answer: D. Loss = sending-end minus receiving-end active power. (Key point: Line loss)

## Related in Power System Analysis I

- [Sending end active power from ABCD, 132/130.5 kV](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3Asending-power-132kv-130-5kv) — Power System Analysis I, chapter 6
- [220 kV line, 200 MW: sending end from ABCD](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3Aabcd-220kv-200mw) — Power System Analysis I, chapter 6
- [150 mile, 60 Hz line: ABCD and sending end](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3A150-mile-60hz-line-abcd) — Power System Analysis I, chapter 5
- [Sending and receiving power, 140∠10° and 132 kV](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3Apower-140kv-132kv-a099) — Power System Analysis I, chapter 6
- [Sending end from A = 0.98∠3°, B = 110∠75°](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3Aabcd-132kv-50mva-a098-3) — Power System Analysis I, chapter 6, asked 2×
- [Sending end from A = 0.98∠0.3°, B = 110∠75°](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3Aabcd-132kv-50mva-a098-0-3) — Power System Analysis I, chapter 6, asked 2×

## Related in other subjects

- [Fault at receiving end of 132 kV lines](https://www.bctengineer.com/question.md?key=semester_5%2Fpower_system_analysis_ii%3Afault-132kv-receiving-end-2071) — Power System Analysis II, chapter 3
- [Fault at receiving end of 220 kV lines](https://www.bctengineer.com/question.md?key=semester_5%2Fpower_system_analysis_ii%3Afault-220kv-two-generators) — Power System Analysis II, chapter 3
- [Fault at load end of overhead line](https://www.bctengineer.com/question.md?key=semester_5%2Fpower_system_analysis_ii%3Afault-load-end-33kv-line) — Power System Analysis II, chapter 3
- [Shunt reactors for 750 kV line ABCD](https://www.bctengineer.com/question.md?key=semester_8%2Fhigh_voltage_engineering%3Ashunt-reactor-abcd-750kv) — High Voltage Engineering, chapter 3