# Generator and load complex power conventions

Power System Analysis I · Chapter 3: Computational Technique

- Asked in: 2068 Bhadra, 2+3 marks
- Answer checked by Claude Opus 5.5 (high effort) on 2026-10-14
- Page: https://www.bctengineer.com/q/semester_4/power_system_analysis_i/generator-load-complex-power-convention
- Whole chapter: https://www.bctengineer.com/md/semester_4/power_system_analysis_i/chapter-3

## Question

How are generator and load complex powers expressed? What will happen if the convention of taking the conjugate of current is not followed? Explain with necessary derivation.

## Short answer

Complex power is S=VI*; for a generator current leaves the terminal so S is delivered, for a load current enters so S is absorbed. If the conjugate is not used, V*I gives P but reverses the sign of Q, while VI depends on the chosen reference angle and is physically meaningless.

## Answer

#### Generator and load complex power
Complex power is always written as $S = VI^* = P + jQ$. What it means depends on the assumed current direction.

- **Generator (source) convention:** the current leaves the + terminal. $S_G = VI^*$ is the power **delivered**. For an over-excited generator supplying a lagging load, $P_G > 0$ and $Q_G > 0$.
- **Load convention:** the current enters the + terminal. $S_L = VI^*$ is the power **absorbed**. For an inductive load $Z = R + jX$: $S_L = |I|^2Z = P_L + jQ_L$ with $Q_L > 0$.

At any bus, the net injected power is $S_i = S_{Gi} - S_{Li} = V_iI_i^*$. This is the form used in load-flow studies.

#### If the conjugate is not taken
Let $V = |V|\angle\theta_v$, $I = |I|\angle\theta_i$ and $\phi = \theta_v - \theta_i$.

**Case 1: $S = V^*I$**
$$
V^*I = |V||I|\angle(\theta_i - \theta_v) = |V||I|\cos\phi - j|V||I|\sin\phi = P - jQ
$$

P is correct, but the sign of Q is reversed. An inductive (lagging) load would show negative Q, as if it were supplying vars like a capacitor. Generators and loads would then disagree with the standard convention used in meters, capability charts and load-flow programs. The power triangle would also become the mirror image of the impedance triangle ($S = |I|^2(R - jX)$).

**Case 2: $S = VI$ (no conjugate at all)**
$$
VI = |V||I|\angle(\theta_v + \theta_i)
$$

The angle now depends on the **sum** of the phase angles. If the reference is changed by $\alpha$, then $VI$ becomes $|V||I|\angle(\theta_v + \theta_i + 2\alpha)$. So P and Q would change just because a different phasor was chosen as reference, which is physically meaningless. Taking the conjugate makes S depend only on the difference $\theta_v - \theta_i$, which is independent of the reference.

Example: $V = 100\angle30^\circ$ V and $I = 10\angle0^\circ$ A (lagging by 30°).
- $VI^* = 1000\angle30^\circ = 866 + j500$ VA. Correct: an inductive load absorbs 500 var.
- $V^*I = 866 - j500$ VA. Wrong sign of Q.
- $VI = 1000\angle30^\circ$ here, but with V as reference ($V = 100\angle0^\circ$, $I = 10\angle-30^\circ$) it becomes $1000\angle-30^\circ$. The result changes with the reference.

So the conjugate of current must be taken to get a unique, reference-independent S with the standard sign of Q.

## Check yourself

The answer's key points as multiple-choice questions, with the correct option and why.

1. In the generator convention, what does S = VI* represent?
   A. Power absorbed with Q < 0
   B. Power delivered by the source; an over-excited generator supplying a lagging load has P > 0 and Q > 0
   C. Only the apparent power
   D. Zero net power
   Answer: B. Current leaves the + terminal. (Key point: Generator convention)

2. In the load convention, what does S = VI* represent?
   A. Power absorbed; inductive load has Q > 0
   B. Power delivered
   C. Power lost in the source
   D. Always Q < 0
   Answer: A. Current enters the + terminal. (Key point: Load convention)

3. What happens if S = V*I is used?
   A. P changes sign
   B. Both are correct
   C. S becomes real
   D. P is right but Q has the wrong sign, so an inductive load shows negative Q
   Answer: D. V*I = P - jQ. (Key point: Without conjugate: V*I)

4. Why is S = VI unacceptable?
   A. It has no magnitude
   B. It always equals zero
   C. Its angle is the sum theta_v + theta_i, so P and Q change with the reference phasor
   D. Its angle is the power factor angle
   Answer: C. A reference shift of alpha adds 2 alpha. (Key point: Without any conjugate)

## Related in Power System Analysis I

- [Complex power and sign conventions](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3Acomplex-power-sign-conventions) — Power System Analysis I, chapter 3
- [Derivation and phasor diagram of complex power](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3Acomplex-power-derivation-phasor) — Power System Analysis I, chapter 3
- [Compensation does not reduce load reactive demand](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3Acompensation-does-not-reduce-load-q) — Power System Analysis I, chapter 6
- [Complex power and its significance](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3Acomplex-power-significance) — Power System Analysis I, chapter 3, asked 2×
- [Complex power and why VI* rather than V*I](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3Acomplex-power-vi-conjugate-why) — Power System Analysis I, chapter 3
- [Complex power, impedance and power triangles](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3Acomplex-power-impedance-power-triangle) — Power System Analysis I, chapter 3

## Related in other subjects

- [DT complex exponential periodic if rational](https://www.bctengineer.com/question.md?key=semester_4%2Fsignals_and_systems%3Adt-exponential-rational-frequency) — Signals and Systems, chapter 1
- [Power to 10 Ω load from shunt generator](https://www.bctengineer.com/question.md?key=semester_4%2Felectrical_machines_i%3Ashunt-gen-378-conductors-10ohm-load) — Electrical Machines I, chapter 3
- [Wave-wound shunt generator, power absorbed by load](https://www.bctengineer.com/question.md?key=semester_4%2Felectrical_machines%3Agen-shunt-378-conductors-load-power) — Electrical Machines, chapter 3
- [UH derivation from complex storms](https://www.bctengineer.com/question.md?key=semester_5%2Fengineering_hydrology%3Auh-complex-storms-procedure) — Engineering Hydrology, chapter 5