# Impedance diagram: three generators, j100 and j130 Ω lines

Power System Analysis I · Chapter 3: Computational Technique

- Asked in: 2070 Magh, 8 marks
- Answer checked by Claude Opus 5.5 (high effort) on 2026-10-14
- Page: https://www.bctengineer.com/q/semester_4/power_system_analysis_i/impedance-diagram-three-gens-j100-j130
- Whole chapter: https://www.bctengineer.com/md/semester_4/power_system_analysis_i/chapter-3

## Question

Compute the per unit values taking a common base and draw the impedance diagram of a power system shown in figure below. The system has the following data: Generators: G1: 25 MVA, 6.6 kV, X = 0.2 p.u.; G2: 15 MVA, 6.6 kV, X = 0.15 p.u.; G3: 30 MVA, 13.2 kV, X = 0.15 p.u. Transformers: T1: 30 MVA, 6.6/115 kV, X = 0.1 p.u.; T2: 15 MVA, 6.6/115 kV, X = 0.1 p.u.; T3: three 1-ph units of 10 MVA, 69/6.9 kV, X = 0.4 p.u. [Figure: G1 (Y, grounded) → T1 (Δ–Y grounded) → line j100 Ω → junction bus; from the junction T2 (Y grounded on bus side, Δ on generator side) up to G2; and line j130 Ω → T3 (Y–Y, grounded) → G3 (Y, grounded).]

## Short answer

Using a 30 MVA base with voltage bases 6.6/115/6.6/11.5 kV, per-unit reactances are: X_G1=0.24, X_G2=0.30, X_G3=0.1976, X_T1=0.10, X_T2=0.20, X_T3=0.432, X_L1=0.2268, X_L2=0.2949 pu.

## Answer

Common base: **30 MVA, 6.6 kV in the G1 circuit**. Base voltages in other zones follow the line-to-line ratios.

#### Base voltages
- G1 zone: 6.6 kV
- Line zone (T1 6.6/115 kV): 115 kV, $Z_b = \frac{115^2}{30} = 440.83\ \Omega$
- G2 zone (T2 115/6.6 kV): 6.6 kV
- G3 zone: T3 is a Y–Y bank of 69/6.9 kV units, so the line-to-line ratio is 119.5/11.95 kV (10 : 1). Then $V_b = 115/10 = 11.5$ kV

#### Per-unit values (30 MVA)
$$
\begin{aligned}
X_{G1} &= 0.2\times\frac{30}{25} = 0.24\ \text{pu}\\
X_{G2} &= 0.15\times\frac{30}{15} = 0.30\ \text{pu}\\
X_{G3} &= 0.15\times\frac{30}{30}\times\left(\frac{13.2}{11.5}\right)^2 = 0.1976\ \text{pu}\\
X_{T1} &= 0.1\times\frac{30}{30} = 0.10\ \text{pu}\\
X_{T2} &= 0.1\times\frac{30}{15} = 0.20\ \text{pu}\\
X_{T3} &= 0.4\times\frac{30}{3\times10}\times\left(\frac{11.95}{11.5}\right)^2 = 0.432\ \text{pu}\\
X_{L1} &= \frac{100}{440.83} = 0.2268\ \text{pu}\\
X_{L2} &= \frac{130}{440.83} = 0.2949\ \text{pu}
\end{aligned}
$$

| Element | X (pu, 30 MVA) |
|---|---|
| G1 | 0.2400 |
| G2 | 0.3000 |
| G3 | 0.1976 |
| T1 | 0.1000 |
| T2 | 0.2000 |
| T3 | 0.4320 |
| Line j100 Ω | 0.2268 |
| Line j130 Ω | 0.2949 |

#### Impedance diagram
```text
    j0.10   j0.2268       j0.2949   j0.432
 +--/\/\/---/\/\/----+----/\/\/-----/\/\/---+
 |   T1     line 1   |    line 2     T3     |
j0.24              j0.20 (T2)            j0.1976
 |                   |                      |
(E1)               j0.30 (G2)             (E3)
 |                   |                      |
 |                 (E2)                     |
 +-------------------+----------------------+
           reference (neutral) bus
```

**Answer:** $X_{G1}=0.24$, $X_{G2}=0.30$, $X_{G3}=0.1976$, $X_{T1}=0.10$, $X_{T2}=0.20$, $X_{T3}=0.432$, $X_{L1}=0.2268$, $X_{L2}=0.2949$ pu (base 30 MVA; 6.6 / 115 / 6.6 / 11.5 kV).

## Check yourself

The answer's key points as multiple-choice questions, with the correct option and why.

1. Which base is chosen?
   A. 30 MVA, 13.2 kV everywhere
   B. 30 MVA, 6.6 kV in the G1 circuit; other zones follow transformer ratios
   C. 25 MVA, 115 kV everywhere
   D. 10 MVA, 6.9 kV
   Answer: B. One MVA base and voltage bases changing at each transformer. (Key point: Common base)

2. How is the G3 zone base found, and what is it?
   A. 115 x 6.9/69 = 11.5 kV (line-to-line ratio 10:1)
   B. 13.2 kV, G3 rating
   C. 6.6 kV
   D. 115 kV
   Answer: A. T3 ratio is 10:1, so the base is 115/10. (Key point: G3 zone base)

3. Why is X_T2 = 0.20 pu?
   A. 0.1 x 15/30
   B. 0.1 unchanged
   C. 0.1 x (30/15)^2
   D. 0.1 x 30/15, converting from its 15 MVA rating to the 30 MVA base
   Answer: D. Only the MVA ratio is used because its voltage rating equals the base. (Key point: Transformer T2 conversion)

4. How is T3's X = 0.432 pu obtained?
   A. 0.4 x 30/10
   B. 0.4 x 10/30
   C. 0.4 x 30/(3x10) x (11.95/11.5)^2, using the three-phase rating 30 MVA and the voltage mismatch
   D. 0.4 unchanged
   Answer: C. Three 10 MVA units give 30 MVA; the rated 11.95 kV vs 11.5 kV base gives the squared correction. (Key point: T3 rating and voltage correction)

## Related in Power System Analysis I

- [Reactance diagram: 30 MVA, 6.6 kV base, three lines](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3Areactance-diagram-30mva-g1-motor) — Power System Analysis I, chapter 3
- [Per unit circuit of three-generator system, 30 MVA base](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3Apu-circuit-30mva-g1-g2-g3) — Power System Analysis I, chapter 3
- [Reactance diagram: 50 MVA, 13.8 kV base, three generators](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3Areactance-diagram-50mva-13-8kv) — Power System Analysis I, chapter 3
- [Impedance diagram: 25 MVA generator, two motors](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3Aimpedance-diagram-25mva-two-motors) — Power System Analysis I, chapter 3
- [Reactance diagram: three generators, 30 MVA 6.6 kV base](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3Areactance-diagram-30mva-three-generators) — Power System Analysis I, chapter 3
- [Reactance diagram: three generators, two 220 kV lines](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3Areactance-diagram-three-gens-two-lines) — Power System Analysis I, chapter 3

## Related in other subjects

- [Fault level: two 25 MVA generators, 50% reduction](https://www.bctengineer.com/question.md?key=semester_7%2Fpower_plant_equipment%3Afault-two-25mva-50-percent) — Power Plant Equipment, chapter 4
- [Fault through impedance at bus 2](https://www.bctengineer.com/question.md?key=semester_5%2Fpower_system_analysis_ii%3Afault-impedance-bus2-actual-currents) — Power System Analysis II, chapter 3
- [Fault level: four 25 MVA generators, bus reactor](https://www.bctengineer.com/question.md?key=semester_7%2Fpower_plant_equipment%3Afault-four-25mva-bus-reactor) — Power Plant Equipment, chapter 4
- [Fault level: two 50 MVA generators, 50% reduction](https://www.bctengineer.com/question.md?key=semester_7%2Fpower_plant_equipment%3Afault-two-50mva-50-percent) — Power Plant Equipment, chapter 4