# Nominal-π derivation, losses and UPF phasor diagram

Power System Analysis I · Chapter 5: Transmission Line Modeling

- Asked in: 2078 Chaitra, 4+1+2 marks
- Video: [5. Phasor diagram of medium transmission line nominal π method](https://www.youtube.com/watch?v=wpxhHJraBaM) — Bookforum
- Answer checked by Claude Opus 5.5 (high effort) on 2026-10-14
- Page: https://www.bctengineer.com/q/semester_4/power_system_analysis_i/nominal-pi-200km-derivation-losses
- Whole chapter: https://www.bctengineer.com/md/semester_4/power_system_analysis_i/chapter-5

## Question

For a 3-ph, 200 km long transmission line, derive an expression relating sending end voltage and current to receiving end voltage and current using the nominal-π model. Also write down the expressions for determining active and reactive power losses in the line. Construct a phasor diagram of currents and voltages for a unity power factor load at the receiving end.

## Short answer

For a 200 km line (medium), nominal-π ABCD: A=D=1+ZY/2, B=Z, C=Y(1+ZY/4). Active loss P_loss=3|I_L|²R, reactive loss Q_loss=3|I_L|²X−3(ωC/2)(|V_S|²+|V_R|²). Phasor diagram for unity pf: V_R reference, I_R in phase; I_C2 leads V_R 90°; I_L=I_R+I_C2; V_S=V_R+I_LR+jI_LX; I_C1 leads V_S90°; I_S=I_L+I_C1.

## Answer

A 200 km line is a **medium line**, so its shunt capacitance cannot be ignored. In the nominal-Π model the total series impedance $Z = R + jX$ is lumped in the middle and $Y/2$ is placed at each end (all quantities per phase).

```text
 IS       IL    Z = R + jX        IR
 o-->--+-----[ R ]--[ jX ]-----+-->--o
       |                       |
 VS  [Y/2] Ic1           Ic2 [Y/2]  VR
       |                       |
 o-----+-----------------------+-----o
```

#### Relation between sending and receiving quantities
Current through the receiving-end shunt: $I_{C2} = \frac{Y}{2}V_R$

Series current: $I_L = I_R + \frac{Y}{2}V_R$

$$
\begin{aligned}
V_S &= V_R + ZI_L = \left(1 + \frac{ZY}{2}\right)V_R + ZI_R \\
I_S &= I_L + \frac{Y}{2}V_S = Y\left(1 + \frac{ZY}{4}\right)V_R + \left(1 + \frac{ZY}{2}\right)I_R
\end{aligned}
$$

In matrix form:

$$
\begin{bmatrix} V_S \\ I_S \end{bmatrix} = \begin{bmatrix} 1 + \frac{ZY}{2} & Z \\ Y\left(1 + \frac{ZY}{4}\right) & 1 + \frac{ZY}{2} \end{bmatrix}\begin{bmatrix} V_R \\ I_R \end{bmatrix}
$$

#### Active and reactive power losses (3-phase)
With $Y/2 = j\omega C/2$ at each end:

$$
\begin{aligned}
P_{loss} &= 3|I_L|^2 R = P_S - P_R \\
Q_{loss} &= 3|I_L|^2X - 3\frac{\omega C}{2}\left(|V_S|^2 + |V_R|^2\right) = Q_S - Q_R
\end{aligned}
$$

The first term of $Q_{loss}$ is the reactive power absorbed by the series inductance. The second is the reactive power generated by the two shunt capacitances. A negative $Q_{loss}$ means the line supplies net reactive power, which is normal at light load.

#### Phasor diagram for unity p.f. load
Take $V_R$ as reference; $I_R$ is in phase with $V_R$.
1. $I_{C2}$ leads $V_R$ by 90°.
2. $I_L = I_R + I_{C2}$ leads $V_R$ slightly.
3. $V_S = V_R + I_LR + jI_LX$: $I_LR$ is parallel to $I_L$, $I_LX$ is perpendicular to $I_L$.
4. $I_{C1}$ leads $V_S$ by 90°; $I_S = I_L + I_{C1}$.

```text
                  IS
         IC1 ^   ^         VS
              \  |  IL   / |
               \ | /    /  | IL.X
          IC2 ^ \|/    /   |
              | /   d /____|
              |/    /  IL.R
   O------------------------> VR , IR
```

At unity p.f. the $I_LX$ drop is almost at right angles to $V_R$, so $|V_S|$ is only slightly greater than $|V_R|$ while the load angle $\delta$ is noticeable. $I_S$ leads $I_R$ because of the two charging currents.

## Check yourself

The answer's key points as multiple-choice questions, with the correct option and why.

1. Why is a nominal-Π model used for a 200 km line?
   A. It is a medium line, so shunt capacitance cannot be ignored
   B. It is a short line so capacitance is zero
   C. It is a long line needing distributed parameters
   D. Only Π models can handle 3-phase lines
   Answer: A. 200 km is in the 80-250 km medium range where lumped shunt capacitance is needed. (Key point: Why nominal-Π for 200 km)

2. The current through the series impedance in the nominal-Π model is:
   A. IL = IR - (Y/2)VR
   B. IL = IR
   C. IL = IS + (Y/2)VS
   D. IL = IR + (Y/2)VR
   Answer: D. The receiving-end shunt current (Y/2)VR adds to IR before flowing in the series arm. (Key point: Series current IL)

3. The active power loss in the Π line is:
   A. 3|IL|^2 R
   B. 3|IR|^2 X
   C. 3|VS|^2 / R
   D. 3 wC |VR|^2
   Answer: A. Only R dissipates power, carrying IL, so Ploss = 3|IL|^2 R = PS - PR. (Key point: Active power loss)

4. Qloss = 3|IL|^2 X - 3(wC/2)(|VS|^2 + |VR|^2). A negative Qloss means:
   A. The line absorbs net reactive power
   B. The line has zero resistance
   C. The line supplies net reactive power, as at light load
   D. The load is purely resistive
   Answer: C. The shunt capacitances generate more reactive power than the series inductance absorbs. (Key point: Reactive loss and sign)

5. In the unity p.f. phasor diagram, IS compared with IR:
   A. IS leads IR because of the two charging currents
   B. IS lags IR
   C. IS is in phase with IR
   D. IS equals IR in magnitude
   Answer: A. IC1 and IC2 lead the voltages by 90°, so IS leads IR. (Key point: Phasor diagram at unity pf)

## Related in Power System Analysis I

- [Long line sending end voltage derivation](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3Along-line-sending-voltage-derivation) — Power System Analysis I, chapter 5
- [Nominal-T derivation, phasor, losses, regulation](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3Anominal-t-derivation-losses) — Power System Analysis I, chapter 5
- [Nominal-π phasor, sending end, regulation, efficiency](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3Anominal-pi-phasor-regulation-efficiency) — Power System Analysis I, chapter 5
- [280 km, 60 Hz line: nominal-π vs long line](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3A280km-60hz-nominal-pi-long) — Power System Analysis I, chapter 5, asked 2×
- [Power delivered from sending end data, nominal-π](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3Anominal-pi-power-delivered) — Power System Analysis I, chapter 5
- [110 km, 110 kV line: sending end, regulation, efficiency](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3A110km-line-performance) — Power System Analysis I, chapter 6, asked 2×

## Related in other subjects

- [Receiving-end voltage infinite at 1500 km](https://www.bctengineer.com/question.md?key=semester_8%2Fhigh_voltage_engineering%3Alossless-line-1500km-infinite-voltage) — High Voltage Engineering, chapter 3
- [Expression for receiving-end shunt compensation](https://www.bctengineer.com/question.md?key=semester_8%2Fhigh_voltage_engineering%3Ashunt-compensation-xp-expression) — High Voltage Engineering, chapter 3
- [Ybus with nominal π model, line lengths](https://www.bctengineer.com/question.md?key=semester_5%2Fpower_system_analysis_ii%3Aybus-km-lines-pi-model) — Power System Analysis II, chapter 1, asked 2×
- [Fault level at end of two 200 km lines](https://www.bctengineer.com/question.md?key=semester_5%2Fpower_system_analysis_ii%3Afault-two-stations-132kv-200km) — Power System Analysis II, chapter 3, asked 2×