# Nominal-π phasor, sending end, regulation, efficiency

Power System Analysis I · Chapter 5: Transmission Line Modeling

- Asked in: 2079 Chaitra, 8 marks
- Video: [5. Phasor diagram of medium transmission line nominal π method](https://www.youtube.com/watch?v=wpxhHJraBaM) — Bookforum
- Answer checked by Claude Opus 5.5 (high effort) on 2026-10-14
- Page: https://www.bctengineer.com/q/semester_4/power_system_analysis_i/nominal-pi-phasor-regulation-efficiency
- Whole chapter: https://www.bctengineer.com/md/semester_4/power_system_analysis_i/chapter-5

## Question

Draw the phasor diagram for a nominal π circuit of a medium transmission line. Derive expressions for sending end voltage, current, voltage regulation and efficiency.

## Short answer

In nominal-π model, half shunt admittance Y/2 at each end of series impedance Z. Sending voltage: V_S=(1+ZY/2)V_R+Z I_R; current: I_S=Y(1+ZY/4)V_R+(1+ZY/2)I_R. Voltage regulation: %VR=(|V_S|/|1+ZY/2|−|V_R|)/|V_R|×100. Efficiency: η=P_R/(P_R+3|I_L|²R) where I_L=I_R+Y V_R/2.

## Answer

In the **nominal-Π model** of a medium line, the total series impedance $Z = R + jX$ is in the middle and half the shunt admittance, $Y/2 = j\omega C/2$, is connected at each end.

```text
 IS       IL    Z = R + jX        IR
 o-->--+-----[ R ]--[ jX ]-----+-->--o
       |                       |
 VS  [Y/2] Ic1           Ic2 [Y/2]  VR
       |                       |
 o-----+-----------------------+-----o
```

#### Phasor diagram (lagging load, $V_R$ as reference)
Construction:
1. Draw $V_R$ along the reference axis and $I_R$ lagging by $\phi_R$.
2. $I_{C2} = j\frac{\omega C}{2}V_R$ leads $V_R$ by 90°.
3. $I_L = I_R + I_{C2}$.
4. From the tip of $V_R$ add $I_L R$ (parallel to $I_L$) and $I_L X$ (90° ahead of $I_L$) to get $V_S$.
5. $I_{C1} = j\frac{\omega C}{2}V_S$ leads $V_S$ by 90°; $I_S = I_L + I_{C1}$.

```text
          IC2 ^           IL.X  /VS
              |              | /
              |              |/ IL.R
   O-----------------------> VR
    \ \  phiR
     \  \ IL     (IS = IL + IC1,
      v   v       IC1 is 90 deg ahead of VS)
      IR
```

#### Sending-end voltage

$$
\begin{aligned}
I_L &= I_R + \frac{Y}{2}V_R \\
V_S &= V_R + Z I_L = V_R + Z\left(I_R + \frac{Y}{2}V_R\right) \\
V_S &= \left(1 + \frac{ZY}{2}\right)V_R + Z I_R
\end{aligned}
$$

#### Sending-end current

$$
\begin{aligned}
I_S &= I_L + \frac{Y}{2}V_S \\
&= I_R + \frac{Y}{2}V_R + \frac{Y}{2}\left[\left(1 + \frac{ZY}{2}\right)V_R + ZI_R\right] \\
I_S &= Y\left(1 + \frac{ZY}{4}\right)V_R + \left(1 + \frac{ZY}{2}\right)I_R
\end{aligned}
$$

So $A = D = 1 + ZY/2$, $B = Z$, $C = Y(1 + ZY/4)$.

#### Voltage regulation
At no load ($I_R = 0$), $V_{R(NL)} = V_S/A$. Hence

$$
\%\,\text{VR} = \frac{|V_S|/|A| - |V_R|}{|V_R|}\times 100 = \frac{\left|V_S\right| - \left|1 + \frac{ZY}{2}\right|\left|V_R\right|}{\left|1 + \frac{ZY}{2}\right|\left|V_R\right|}\times100
$$

Note: $|V_S|/|A|$ is used, not $|V_S|$, because the shunt capacitance raises the no-load receiving voltage (Ferranti effect).

#### Efficiency
Only the series resistance carries loss, and it carries current $I_L$:

$$
\begin{aligned}
P_{loss} &= 3|I_L|^2 R \\
\eta &= \frac{P_R}{P_R + 3|I_L|^2R}\times100 = \frac{3|V_R||I_R|\cos\phi_R}{3|V_S||I_S|\cos\phi_S}\times100
\end{aligned}
$$

## Check yourself

The answer's key points as multiple-choice questions, with the correct option and why.

1. In the nominal-Π model, where is the shunt admittance placed?
   A. All of Y at the middle
   B. All of Y at the receiving end
   C. Y/2 at each end, with Z in the middle
   D. Y/2 in each arm with Z at the sending end
   Answer: C. Nominal-Π lumps Z in the middle and puts Y/2 at each end. (Key point: Nominal-Π structure)

2. Which is the sending-end voltage in the nominal-Π model?
   A. VS = (1 + ZY/2) VR + Z IR
   B. VS = VR + Z IR only
   C. VS = (1 + ZY) VR + Z IR/2
   D. VS = VR + Y IR
   Answer: A. IL = IR + (Y/2)VR and VS = VR + Z IL give VS = (1 + ZY/2)VR + Z IR. (Key point: Sending-end voltage)

3. In the regulation formula, the no-load receiving voltage is |VS|/|A| because:
   A. A equals the load power factor
   B. At no load IR = 0 so VS = A VR, and shunt capacitance raises VR (Ferranti effect)
   C. A is always 1
   D. Regulation is defined with VS as the base
   Answer: B. With IR = 0, VS = A VR, so VR(NL) = VS/A; capacitance causes a rise at no load. (Key point: No-load voltage in regulation)

4. In the nominal-Π efficiency, copper loss is 3|IL|^2 R. IL is:
   A. The receiving-end load current IR
   B. The sending-end current IS
   C. The current through the series impedance, IR + (Y/2)VR
   D. The current in the sending-end capacitor
   Answer: C. Only the series resistance has loss and it carries IL = IR + IC2. (Key point: Loss current in Π)

5. The constant C of the nominal-Π model is:
   A. Z(1 + ZY/4)
   B. Y
   C. 1 + ZY/2
   D. Y(1 + ZY/4)
   Answer: D. IS = Y(1 + ZY/4)VR + (1 + ZY/2)IR. (Key point: Sending-end current)

## Related in Power System Analysis I

- [Nominal-T derivation, phasor, losses, regulation](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3Anominal-t-derivation-losses) — Power System Analysis I, chapter 5
- [110 km, 110 kV line: sending end, regulation, efficiency](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3A110km-line-performance) — Power System Analysis I, chapter 6, asked 2×
- [Nominal-π derivation, losses and UPF phasor diagram](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3Anominal-pi-200km-derivation-losses) — Power System Analysis I, chapter 5
- [Power delivered from sending end data, nominal-π](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3Anominal-pi-power-delivered) — Power System Analysis I, chapter 5
- [Long line sending end voltage derivation](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3Along-line-sending-voltage-derivation) — Power System Analysis I, chapter 5
- [220 kV line, 200 MW: sending end from ABCD](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3Aabcd-220kv-200mw) — Power System Analysis I, chapter 6

## Related in other subjects

- [220 kV double circuit efficiency and regulation](https://www.bctengineer.com/question.md?key=semester_8%2Ftransmission_and_distribution_system_design%3Adouble-circuit-220kv-efficiency-regulation) — Transmission and Distribution System Design, chapter 4
- [Equivalent circuit, efficiency and regulation of 5 kVA transformer](https://www.bctengineer.com/question.md?key=semester_4%2Felectrical_machines_i%3Aoc-sc-5kva-220-400-lv) — Electrical Machines I, chapter 2
- [Derive input impedance of transmission line](https://www.bctengineer.com/question.md?key=semester_3%2Felectromagnetism%3Aderive-input-impedance-line) — Electromagnetism, chapter 5
- [Salient pole generator phasor diagram in per unit](https://www.bctengineer.com/question.md?key=semester_5%2Felectric_machines_ii%3Asalient-generator-phasor-pu) — Electric Machines II, chapter 1