title: "Nominal-T 100 km line, 20 MW at 110 kV"
subject: "Power System Analysis I"
chapter: 5
key: "semester_4/power_system_analysis_i:nominal-t-100km-20mw"
source: https://www.bctengineer.com/q/semester_4/power_system_analysis_i/nominal-t-100km-20mw
site: BCT Engineering
---

# Nominal-T 100 km line, 20 MW at 110 kV

Power System Analysis I · Chapter 5: Transmission Line Modeling

- Asked in: 2071 Bhadra, 6 marks
- Video: [Medium Transmission Line: T eq. ckt: 1st problem on Sending end voltage, current & power factor](https://www.youtube.com/watch?v=El7seSAY75M) — Gargi Basu
- Answer checked by Claude Opus 5.5 (high effort) on 2026-10-14
- Page: https://www.bctengineer.com/q/semester_4/power_system_analysis_i/nominal-t-100km-20mw
- Whole chapter: https://www.bctengineer.com/md/semester_4/power_system_analysis_i/chapter-5

## Question

A 100 km long 3-phase 50 Hz transmission line is nominal-T modelled. The resistance and reactance are 0.2 Ω per phase per km and j0.4 per phase per km respectively. The shunt admittance is j2.5 × 10⁻⁶ S/phase per km. Calculate current and voltage at the sending end if the line delivers 20 MW at 110 kV and at 0.9 p.f. lagging.

## Short answer

Total Z=20+j40 Ω, Y=j2.5×10⁻⁴ S. Receiving V_R=63.51 kV, I_R=116.6∠-25.84° A. Nominal-T: mid-point V_C=65.59∠1.39° kV, I_S=110.1∠-18.23° A, V_S=67.39∠2.84° kV/phase (116.73 kV line).

## Answer

**Given:** $l = 100$ km, $z = 0.2 + j0.4\ \Omega$/km, $y = j2.5\times10^{-6}$ S/km; load 20 MW at 110 kV, 0.9 p.f. lagging; nominal-T model.

#### Step 1: Total parameters

$$
\begin{aligned}
Z &= (0.2 + j0.4)\times100 = 20 + j40\ \Omega, \quad \frac{Z}{2} = 10 + j20\ \Omega \\
Y &= j2.5\times10^{-6}\times100 = j2.5\times10^{-4}\ \text{S}
\end{aligned}
$$

#### Step 2: Receiving-end values

$$
\begin{aligned}
V_R &= \frac{110}{\sqrt3} = 63.51\angle 0^\circ\ \text{kV} \\
I_R &= \frac{20\times10^6}{\sqrt3\times110\times10^3\times0.9} = 116.6\angle -25.84^\circ = 104.97 - j50.84\ \text{A}
\end{aligned}
$$

```text
 IS     Z/2            Z/2     IR
 o-->--[R/2 jX/2]--+--[R/2 jX/2]-->--o
                   |
 VS              [ Y ] Ic   (VC)     VR
                   |
 o-----------------+-----------------o
```

#### Step 3: Mid-point voltage

$$
\begin{aligned}
V_C &= V_R + I_R\frac{Z}{2} = 63{,}509 + (104.97 - j50.84)(10 + j20) \\
&= 65{,}575 + j1591 = 65.59\angle 1.39^\circ\ \text{kV}
\end{aligned}
$$

#### Step 4: Shunt current and sending-end current

$$
\begin{aligned}
I_C &= YV_C = j2.5\times10^{-4}(65{,}575 + j1591) = -0.40 + j16.39\ \text{A} \\
I_S &= I_R + I_C = 104.58 - j34.45 = 110.1\angle -18.23^\circ\ \text{A}
\end{aligned}
$$

#### Step 5: Sending-end voltage

$$
\begin{aligned}
V_S &= V_C + I_S\frac{Z}{2} = 65{,}575 + j1591 + (104.58 - j34.45)(10 + j20) \\
&= 67{,}310 + j3338 = 67.39\angle 2.84^\circ\ \text{kV/phase} \\
V_{S(L)} &= \sqrt3\times67.39 = 116.73\ \text{kV}
\end{aligned}
$$

Check with ABCD: $A = 1 + ZY/2 = 0.995\angle 0.14^\circ$, $B = Z(1 + ZY/4) = 44.61\angle 63.51^\circ\ \Omega$, $C = Y$; $AV_R + BI_R$ gives the same $V_S$.

Sending-end p.f. $= \cos(2.84^\circ + 18.23^\circ) = 0.9331$ lagging; $P_S = 20.77$ MW.

**Answer:** $I_S = 110.1\angle -18.23^\circ$ A, $V_S = 116.73$ kV (line) $= 67.39\angle 2.84^\circ$ kV per phase.

## Check yourself

The answer's key points as multiple-choice questions, with the correct option and why.

1. For the 100 km line with z = 0.2 + j0.4 Ω/km and y = j2.5e-6 S/km, what are Z/2 and Y?
   A. Z/2 = 10 + j20 Ω, Y = j2.5e-4 S
   B. Z/2 = 20 + j40 Ω, Y = j2.5e-4 S
   C. Z/2 = 10 + j20 Ω, Y = j1.25e-4 S
   D. Z/2 = 0.1 + j0.2 Ω, Y = j2.5e-6 S
   Answer: A. Z = 100z = 20 + j40 Ω so Z/2 = 10 + j20 Ω; Y = 100y = j2.5e-4 S (the whole Y at the middle in the T model). (Key point: Total line parameters)

2. What is IR for 20 MW at 110 kV and 0.9 p.f. lagging?
   A. About 105 A at 0°
   B. About 116.6 A at -25.84°
   C. About 202 A at -25.84°
   D. About 116.6 A at +25.84°
   Answer: B. IR = 20e6/(sqrt3 x 110e3 x 0.9) = 116.6 A, lagging by cos^-1(0.9) = 25.84°. (Key point: Receiving-end current)

3. What is the correct sequence of calculation for the nominal-T circuit?
   A. VS = VR + IR Z, then IC, then IS
   B. VC = VR + IR Z/2, IC = Y VC, IS = IR + IC, VS = VC + IS Z/2
   C. IC = Y VR, IS = IR + IC, VS = VR + IS Z
   D. VC = VR - IR Z/2, then VS = VC - IS Z/2
   Answer: B. First find the mid-point voltage VC, then the shunt current, then IS, and finally VS = VC + IS(Z/2). (Key point: Order of calculation in the T model)

4. With VS = 67.39 kV per phase, what is the sending-end line voltage?
   A. 67.39 kV
   B. About 116.7 kV
   C. About 39 kV
   D. About 202 kV
   Answer: B. VS(L) = sqrt3 x 67.39 = 116.73 kV. (Key point: Result VS line value)

## Related in Power System Analysis I

- [Nominal-T 100 km line, 50 MVA at 132 kV](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3Anominal-t-100km-50mva) — Power System Analysis I, chapter 6
- [280 km, 60 Hz line: nominal-π vs long line](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3A280km-60hz-nominal-pi-long) — Power System Analysis I, chapter 5, asked 2×
- [Regulation and efficiency of 100 km, 110 kV line](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3Aregulation-efficiency-100km-110kv) — Power System Analysis I, chapter 6, asked 2×
- [110 km, 110 kV line: sending end, regulation, efficiency](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3A110km-line-performance) — Power System Analysis I, chapter 6, asked 2×
- [450 km 400 kV line, 420 MW, 0.9 pf](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3A450km-400kv-420mw-090) — Power System Analysis I, chapter 5
- [300 km line: short line vs nominal-π](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3A300km-short-vs-nominal-pi) — Power System Analysis I, chapter 5, asked 2×

## Related in other subjects

- [Conductor selection, 100 MW 70 km 132 kV](https://www.bctengineer.com/question.md?key=semester_8%2Ftransmission_and_distribution_system_design%3Aconductor-selection-100mw-70km-132kv) — Transmission and Distribution System Design, chapter 4
- [6° phase shift per 100 km of lossless line](https://www.bctengineer.com/question.md?key=semester_8%2Fhigh_voltage_engineering%3Aphase-shift-6-degree-100km) — High Voltage Engineering, chapter 3
- [Insulator discs per string, 180 MW over 200 km](https://www.bctengineer.com/question.md?key=semester_8%2Ftransmission_and_distribution_system_design%3Ainsulator-discs-180mw-200km) — Transmission and Distribution System Design, chapter 3
- [Conductor selection, 100 MW 80 km, no corona](https://www.bctengineer.com/question.md?key=semester_8%2Ftransmission_and_distribution_system_design%3Aconductor-selection-100mw-80km-corona) — Transmission and Distribution System Design, chapter 4