# Nominal-T derivation, phasor, losses, regulation

Power System Analysis I · Chapter 5: Transmission Line Modeling

- Asked in: 2073 Magh, 8 marks
- Video: [ABCD parameters of medium transmission line by Nominal T method explained by Irfan Mujawar](https://www.youtube.com/watch?v=HzHGlzKCBPI) — Dr. Irfan Mujawar
- Answer checked by Claude Opus 5.5 (high effort) on 2026-10-14
- Page: https://www.bctengineer.com/q/semester_4/power_system_analysis_i/nominal-t-derivation-losses
- Whole chapter: https://www.bctengineer.com/md/semester_4/power_system_analysis_i/chapter-5

## Question

Starting from a suitable point, derive expressions relating sending end voltage and current for a medium length transmission line using the nominal-T model. Also construct the phasor diagram and expressions to compute power loss in the line, voltage regulation and efficiency.

## Short answer

Nominal-T: half series impedance Z/2 in each arm, shunt Y at centre. VS = (1+ZY/2)VR + Z(1+ZY/4)IR, IS = Y VR + (1+ZY/2)IR. Power loss Ploss = 3(|IR|²+|IS|²)R/2. Regulation uses no-load VR = |VS|/|A|. Efficiency = PR/(PR+Ploss). Phasor diagram builds VC then IS and VS.

## Answer

In the **nominal-T model** of a medium line, the total shunt admittance $Y = j\omega C$ is placed at the middle of the line, and half the series impedance ($Z/2$) is placed in each arm. Values are per phase.

```text
 IS     Z/2            Z/2     IR
 o-->--[R/2 jX/2]--+--[R/2 jX/2]-->--o
                   |
 VS              [ Y ] Ic   (VC)     VR
                   |
 o-----------------+-----------------o
```

#### Sending-end voltage and current
**Step 1:** Voltage across the shunt (mid-point):

$$
V_C = V_R + \frac{Z}{2}I_R
$$

**Step 2:** Shunt current and sending current:

$$
\begin{aligned}
I_C &= YV_C = YV_R + \frac{ZY}{2}I_R \\
I_S &= I_R + I_C = YV_R + \left(1 + \frac{ZY}{2}\right)I_R
\end{aligned}
$$

**Step 3:** Sending-end voltage:

$$
\begin{aligned}
V_S &= V_C + \frac{Z}{2}I_S = V_R + \frac{Z}{2}I_R + \frac{Z}{2}\left[YV_R + \left(1 + \frac{ZY}{2}\right)I_R\right] \\
V_S &= \left(1 + \frac{ZY}{2}\right)V_R + Z\left(1 + \frac{ZY}{4}\right)I_R
\end{aligned}
$$

So $A = D = 1 + \frac{ZY}{2}$, $B = Z\left(1 + \frac{ZY}{4}\right)$, $C = Y$.

#### Phasor diagram (lagging load, $V_R$ reference)
1. $I_R$ lags $V_R$ by $\phi_R$.
2. $V_C = V_R + I_R\frac{R}{2} + jI_R\frac{X}{2}$.
3. $I_C$ leads $V_C$ by 90°; $I_S = I_R + I_C$.
4. $V_S = V_C + I_S\frac{R}{2} + jI_S\frac{X}{2}$.

```text
                 IC ^          /| VS
                    |   VC   / IS.X/2
                    |   /|  /
                    |  / |IR.X/2
                    | /  /IR.R/2
   O-----------------------> VR
     \  \ phiR
      \   v IS  (IS = IR + IC)
       v
       IR
```

#### Power loss

$$
\begin{aligned}
P_{loss} &= 3\left(|I_R|^2 + |I_S|^2\right)\frac{R}{2} \\
Q_{loss} &= 3\left(|I_R|^2 + |I_S|^2\right)\frac{X}{2} - 3|V_C|^2\omega C
\end{aligned}
$$

#### Voltage regulation
No-load receiving voltage $= |V_S|/|A|$:

$$
\%\text{VR} = \frac{|V_S|/|A| - |V_R|}{|V_R|}\times100, \quad |A| = \left|1 + \frac{ZY}{2}\right|
$$

#### Efficiency

$$
\eta = \frac{P_R}{P_R + P_{loss}}\times100 = \frac{3|V_R||I_R|\cos\phi_R}{3|V_R||I_R|\cos\phi_R + 3\left(|I_R|^2 + |I_S|^2\right)\frac{R}{2}}\times100
$$

## Check yourself

The answer's key points as multiple-choice questions, with the correct option and why.

1. In the nominal-T model:
   A. Y/2 is at each end
   B. Y is at the middle and Z/2 is in each arm
   C. All of Z is at the middle
   D. Y is at the receiving end
   Answer: B. Z/2 in each arm and the full shunt Y at the midpoint. (Key point: T-model structure)

2. ABCD of the nominal T are:
   A. A = D = 1 + ZY/2, B = Z, C = Y(1 + ZY/4)
   B. A = D = 1, B = Z, C = 0
   C. A = D = 1 + ZY/2, B = Z(1 + ZY/4), C = Y
   D. A = 1 + ZY/4, B = Y, C = Z
   Answer: C. The T has B = Z(1 + ZY/4) and C = Y; the Π has the reverse. (Key point: T constants)

3. In the T phasor diagram, IC leads which voltage by 90°?
   A. VR
   B. VS
   C. IR
   D. VC, the voltage across the shunt
   Answer: D. IC = Y VC leads VC by 90°; then IS = IR + IC. (Key point: Phasor diagram step)

4. The active power loss of the nominal T is:
   A. 3(|IR|^2 + |IS|^2)(R/2)
   B. 3|IR|^2 R
   C. 3|IS|^2 R
   D. 3|VC|^2 / R
   Answer: A. Two arms of resistance R/2 carry IR and IS. (Key point: Power loss)

5. Percent regulation is:
   A. (|VS| - |VR|)/|VR| x 100
   B. (|VS|/|A| - |VR|)/|VR| x 100
   C. (|VR| - |VS|)/|VS| x 100
   D. |A| / |VS| x 100
   Answer: B. No-load receiving voltage is |VS|/|A|, with |A| = |1 + ZY/2|. (Key point: Regulation formula)

## Related in Power System Analysis I

- [Nominal-π derivation, losses and UPF phasor diagram](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3Anominal-pi-200km-derivation-losses) — Power System Analysis I, chapter 5
- [Nominal-π phasor, sending end, regulation, efficiency](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3Anominal-pi-phasor-regulation-efficiency) — Power System Analysis I, chapter 5
- [Long line sending end voltage derivation](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3Along-line-sending-voltage-derivation) — Power System Analysis I, chapter 5
- [Power delivered from sending end data, nominal-π](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3Anominal-pi-power-delivered) — Power System Analysis I, chapter 5
- [Nominal-T relations, losses and Ferranti condition](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3Anominal-t-derivation-losses-ferranti) — Power System Analysis I, chapter 5
- [Model validity and nominal-π ABCD with phasor](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3Along-model-validity-nominal-pi) — Power System Analysis I, chapter 5

## Related in other subjects

- [Power loss change on doubling line length](https://www.bctengineer.com/question.md?key=semester_8%2Ftransmission_and_distribution_system_design%3Apower-loss-doubling-line-length) — Transmission and Distribution System Design, chapter 7
- [Ybus with nominal π model, line lengths](https://www.bctengineer.com/question.md?key=semester_5%2Fpower_system_analysis_ii%3Aybus-km-lines-pi-model) — Power System Analysis II, chapter 1, asked 2×