# Per unit values: 100 MVA generator, two motors

Power System Analysis I · Chapter 3: Computational Technique

- Asked in: 2069 Poush, 8 marks
- Video: [Per Unit Impedance Diagram Numerical 2 - Representation of Power System Components - Power System 1](https://www.youtube.com/watch?v=xtRmpGhwhyg) — Ekeeda
- Answer checked by Claude Opus 5.5 (high effort) on 2026-10-14
- Page: https://www.bctengineer.com/q/semester_4/power_system_analysis_i/per-unit-100mva-6kv-two-motors
- Whole chapter: https://www.bctengineer.com/md/semester_4/power_system_analysis_i/chapter-3

## Question

Compute the per unit values of a power system shown in figure below taking the common base of the generator. [Figure: G (100 MVA, 6 kV, X = 6%, Y grounded) → T1 (Δ–Y grounded, 120 MVA, 6.6/132 kV, X = 4%) → transmission line (10 + j50) Ω → T2 (Y grounded on line side, Δ on motor side, 120 MVA, 6.6/132 kV; no reactance printed) → bus feeding motors M1 (50 MVA, 6 kV, X = 6%) and M2 (40 MVA, 6 kV, X = 6%).]

## Short answer

On a 100 MVA, 6/120/6 kV base: generator j0.06 pu, each transformer j0.0403 pu (T2 assumed identical, 4%), line 0.0694+j0.3472 pu, motor M1 j0.12 pu, motor M2 j0.15 pu.

## Answer

Common base: **100 MVA, 6 kV** in the generator circuit. The reactance of T2 is not printed; it is taken equal to T1, **X = 4 %** on 120 MVA, 6.6/132 kV (an identical transformer).

#### Base voltages
- Generator zone: $V_{b1} = 6$ kV
- Line zone (T1 6.6/132 kV): $V_{b2} = 6\times\frac{132}{6.6} = 120$ kV, $Z_{b2} = \frac{120^2}{100} = 144\ \Omega$
- Motor zone (T2 132/6.6 kV): $V_{b3} = 120\times\frac{6.6}{132} = 6$ kV

#### Per-unit values (100 MVA)
$$
\begin{aligned}
X_G &= 0.06\times\frac{100}{100} = 0.06\ \text{pu}\\
X_{T1} &= 0.04\times\frac{100}{120}\times\left(\frac{6.6}{6}\right)^2 = 0.0403\ \text{pu}\\
Z_{line} &= \frac{10 + j50}{144} = 0.0694 + j0.3472\ \text{pu}\\
X_{T2} &= 0.04\times\frac{100}{120}\times\left(\frac{6.6}{6}\right)^2 = 0.0403\ \text{pu}\\
X_{M1} &= 0.06\times\frac{100}{50}\times\left(\frac{6}{6}\right)^2 = 0.12\ \text{pu}\\
X_{M2} &= 0.06\times\frac{100}{40} = 0.15\ \text{pu}
\end{aligned}
$$

| Element | Base kV | pu value |
|---|---|---|
| G | 6 | j0.06 |
| T1 | 6 / 120 | j0.0403 |
| Line | 120 | 0.0694 + j0.3472 |
| T2 (assumed 4 %) | 120 / 6 | j0.0403 |
| M1 | 6 | j0.12 |
| M2 | 6 | j0.15 |

#### Impedance diagram
```text
    j0.0403  0.0694+j0.3472  j0.0403
 +--/\/\/-------/\/\/--------/\/\/--+-------+
 |   T1          line          T2   |       |
j0.06                             j0.12   j0.15
 |                                  |       |
(Eg)                             (Em1)   (Em2)
 |                                  |       |
 +----------------------------------+-------+
              reference bus
```

**Answer:** $X_G = 0.06$, $X_{T1} = X_{T2} = 0.0403$, $Z_{line} = 0.0694 + j0.3472$, $X_{M1} = 0.12$, $X_{M2} = 0.15$ pu on 100 MVA (6 / 120 / 6 kV).

## Check yourself

The answer's key points as multiple-choice questions, with the correct option and why.

1. What is the base voltage in the line zone?
   A. 132 kV
   B. 6 x 132/6.6 = 120 kV
   C. 6 kV
   D. 6.6 kV
   Answer: B. Use the transformer ratio on the generator base. (Key point: Line zone base voltage)

2. How is the line (10 + j50) Ω converted?
   A. Divide by Zb = 120^2/100 = 144 Ω: 0.0694 + j0.3472 pu
   B. Divide by 132^2/100
   C. Divide by 6^2/100
   D. Multiply by 144
   Answer: A. Zb = kV^2/MVA. (Key point: Line impedance)

3. Why is X_T1 = 0.0403 pu?
   A. 0.04 x 120/100
   B. 0.04 unchanged
   C. 0.04 x (6/6.6)^2
   D. 0.04 x 100/120 x (6.6/6)^2, correcting MVA and voltage
   Answer: D. Transformer rated 6.6 kV on a 6 kV base. (Key point: T1 conversion)

4. T2 reactance is missing. What is assumed?
   A. Zero
   B. Equal to the motors
   C. Equal to T1, 4% on 120 MVA, giving 0.0403 pu
   D. 10%
   Answer: C. It is an identical transformer. (Key point: T2 assumption)

## Related in Power System Analysis I

- [Per unit circuit of three-generator system, 30 MVA base](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3Apu-circuit-30mva-g1-g2-g3) — Power System Analysis I, chapter 3
- [Reactance diagram: 90 MVA generator (15%), two motors](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3Areactance-diagram-90mva-generator-15) — Power System Analysis I, chapter 3, asked 2×
- [Reactance diagram: 90 MVA generator (25%), two motors](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3Areactance-diagram-90mva-generator-25) — Power System Analysis I, chapter 3, asked 2×
- [Impedance diagram: 25 MVA generator, two motors](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3Aimpedance-diagram-25mva-two-motors) — Power System Analysis I, chapter 3
- [Impedance diagram, 100 MVA 132 kV base, with load](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3Aimpedance-diagram-100mva-132kv-load) — Power System Analysis I, chapter 3
- [Reactance diagram: 300 MVA, 20 kV generator, two motors](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3Areactance-diagram-300mva-20kv) — Power System Analysis I, chapter 3

## Related in other subjects

- [Differential protection: 11 kV, 100 MVA generator](https://www.bctengineer.com/question.md?key=semester_6%2Fswitchgear_and_protection%3Agenerator-differential-11kv-6-ohm) — Switchgear and Protection, chapter 7
- [Generator-reactor system fault MVA](https://www.bctengineer.com/question.md?key=semester_5%2Fpower_system_analysis_ii%3Agenerator-reactor-fault-mva) — Power System Analysis II, chapter 3
- [L-L fault through Zf with two motors](https://www.bctengineer.com/question.md?key=semester_5%2Fpower_system_analysis_ii%3All-fault-motors-zf-new) — Power System Analysis II, chapter 5
- [Fault at receiving end of 132 kV lines](https://www.bctengineer.com/question.md?key=semester_5%2Fpower_system_analysis_ii%3Afault-132kv-receiving-end-2071) — Power System Analysis II, chapter 3