title: "Reactance diagram: 30 MVA, 6.6 kV base, three lines"
subject: "Power System Analysis I"
chapter: 3
key: "semester_4/power_system_analysis_i:reactance-diagram-30mva-g1-motor"
source: https://www.bctengineer.com/q/semester_4/power_system_analysis_i/reactance-diagram-30mva-g1-motor
site: BCT Engineering
---

# Reactance diagram: 30 MVA, 6.6 kV base, three lines

Power System Analysis I · Chapter 3: Computational Technique

- Asked in: 2073 Magh, 10 marks
- Video: [Impedance and Reactance diagram Problem-3 | Power System Analysis | PSA | per unit Reactance diagram](https://www.youtube.com/watch?v=TQ8W4-l9S2I) — Simple n Easy Learning
- Answer checked by Claude Opus 5.5 (high effort) on 2026-10-14
- Page: https://www.bctengineer.com/q/semester_4/power_system_analysis_i/reactance-diagram-30mva-g1-motor
- Whole chapter: https://www.bctengineer.com/md/semester_4/power_system_analysis_i/chapter-3

## Question

Compute the per unit values taking power base of 30 MVA and 6.6 kV in the circuit of generator G1 and draw the reactance diagram of a power system shown in figure below. The system has the following data: G1: 25 MVA, 6.6 kV, X = 0.2 p.u.; G2: 15 MVA, 6.6 kV, X = 0.15 p.u.; M: 30 MVA, 13.2 kV, X = 0.15 p.u.; T1: 30 MVA, 6.6/115 kV, X = 0.1 p.u.; T2: 15 MVA, 6.6/115 kV, X = 0.1 p.u. [Figure: G1 (Y, grounded) → T1 (Y grounded–Y grounded) → bus; Line-1 from this bus to a junction; Line-3 from the junction to a bus feeding T3 (Y grounded on line side, Δ on motor side) → motor M; Line-2 from the junction down to a bus feeding T2 (grounded windings) → G2 (Y, grounded). No line impedances or T3 rating are printed.]

## Short answer

Using 30 MVA base, XG1=0.24, XG2=0.30, XM=0.15, XT1=0.10, XT2=0.20 pu; assume T3 is 30 MVA, 115/13.2 kV, X=0.10 pu. Line zone base is 115 kV, Zb=440.83 ohm, so each line reactance in pu is X(ohm)/440.83. Draw the reactance diagram with these series reactances and grounded generator references.

## Answer

Base: 30 MVA and 6.6 kV in the G1 circuit. The line impedances and the T3 rating are not printed, so T3 is assumed to be **30 MVA, 115/13.2 kV, X = 0.1 pu**, and the line reactances are kept as symbols $X_1, X_2, X_3$ (Ω).

#### Base voltages
- G1 zone: 6.6 kV
- Line zone (T1 6.6/115 kV): 115 kV, $Z_b = \frac{115^2}{30} = 440.83\ \Omega$
- G2 zone (T2 115/6.6 kV): 6.6 kV
- Motor zone (T3 115/13.2 kV): 13.2 kV

#### Per-unit values (30 MVA base)
$$
\begin{aligned}
X_{G1} &= 0.2\times\frac{30}{25} = 0.24\ \text{pu}\\
X_{G2} &= 0.15\times\frac{30}{15} = 0.30\ \text{pu}\\
X_{M} &= 0.15\times\frac{30}{30}\times\left(\frac{13.2}{13.2}\right)^2 = 0.15\ \text{pu}\\
X_{T1} &= 0.1\times\frac{30}{30} = 0.10\ \text{pu}\\
X_{T2} &= 0.1\times\frac{30}{15} = 0.20\ \text{pu}\\
X_{T3} &= 0.10\ \text{pu (assumed rating)}\\
X_{Line\,k} &= \frac{X_k}{440.83}\ \text{pu}
\end{aligned}
$$

For example, a line reactance of 100 Ω would be $100/440.83 = 0.2268$ pu.

| Element | X (pu, 30 MVA) |
|---|---|
| G1 | 0.24 |
| G2 | 0.30 |
| Motor M | 0.15 |
| T1 | 0.10 |
| T2 | 0.20 |
| T3 (assumed) | 0.10 |
| Lines 1, 2, 3 | $X_k/440.83$ |

#### Reactance diagram
```text
     j0.10   jXL1      jXL3    j0.10
 +---/\/\/---/\/\/--+--/\/\/---/\/\/---+
 |    T1     Line1  |  Line3    T3     |
j0.24               |                 j0.15
 |                jXL2 (Line2)         |
(E1)                |                 (Em)
 |                 j0.20 (T2)          |
 |                  |                  |
 |                 j0.30 (G2)          |
 |                  |                  |
 |                 (E2)                |
 +------------------+------------------+
           reference (neutral) bus
```

**Answer:** $X_{G1}=0.24$, $X_{G2}=0.30$, $X_M=0.15$, $X_{T1}=0.10$, $X_{T2}=0.20$, $X_{T3}=0.10$ pu, and each line $= X(\Omega)/440.83$ pu on the 30 MVA, 115 kV base.

## Check yourself

The answer's key points as multiple-choice questions, with the correct option and why.

1. T3 is assumed 115/13.2 kV. What is the motor-zone base voltage?
   A. 6.6 kV
   B. 115 kV
   C. 13.2 kV
   D. 11.5 kV
   Answer: C. 115 x 13.2/115 = 13.2 kV. (Key point: Motor zone base)

2. What is X_G2 on the 30 MVA base?
   A. 0.15
   B. 0.30
   C. 0.20
   D. 0.075
   Answer: B. 0.15 x 30/15 = 0.30, no voltage correction as 6.6 kV equals base. (Key point: G2 reactance)

3. How is each line reactance converted?
   A. X/440.83
   B. X x 440.83
   C. X/115
   D. X/30
   Answer: A. Zb = 115^2/30 = 440.83 Ω. (Key point: Line pu)

## Related in Power System Analysis I

- [Per unit circuit of three-generator system, 30 MVA base](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3Apu-circuit-30mva-g1-g2-g3) — Power System Analysis I, chapter 3
- [Reactance diagram: three generators, 30 MVA 6.6 kV base](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3Areactance-diagram-30mva-three-generators) — Power System Analysis I, chapter 3
- [Reactance diagram: 20 MVA generator, 15 kV/25 MVA base](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3Areactance-diagram-20mva-15kv-25mva) — Power System Analysis I, chapter 3
- [Reactance diagram: 90 MVA generator (25%), two motors](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3Areactance-diagram-90mva-generator-25) — Power System Analysis I, chapter 3, asked 2×
- [Reactance diagram: 50 MVA, 13.8 kV base, three generators](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3Areactance-diagram-50mva-13-8kv) — Power System Analysis I, chapter 3
- [Per unit values: 100 MVA generator, two motors](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3Aper-unit-100mva-6kv-two-motors) — Power System Analysis I, chapter 3

## Related in other subjects

- [Generator-reactor system fault MVA](https://www.bctengineer.com/question.md?key=semester_5%2Fpower_system_analysis_ii%3Agenerator-reactor-fault-mva) — Power System Analysis II, chapter 3
- [Neutral reactance for 15 MVA generator](https://www.bctengineer.com/question.md?key=semester_5%2Fpower_system_analysis_ii%3Aneutral-reactance-15mva) — Power System Analysis II, chapter 5
- [Block diagram reduction with G1, G2, H1, H2, feedforward](https://www.bctengineer.com/question.md?key=semester_3%2Fcontrol_systems%3Abdr-g1g2-h1h2-ff-unity) — Control Systems, chapter 3, asked 2×
- [Salient pole generator phasor diagram in per unit](https://www.bctengineer.com/question.md?key=semester_5%2Felectric_machines_ii%3Asalient-generator-phasor-pu) — Electric Machines II, chapter 1