# Reactance diagram: three generators, 30 MVA 6.6 kV base

Power System Analysis I · Chapter 3: Computational Technique

- Asked in: 2077 Chaitra, 8 marks
- Video: [Impedance and Reactance diagram Problem-3 | Power System Analysis | PSA | per unit Reactance diagram](https://www.youtube.com/watch?v=TQ8W4-l9S2I) — Simple n Easy Learning
- Answer checked by Claude Opus 5.5 (high effort) on 2026-10-14
- Page: https://www.bctengineer.com/q/semester_4/power_system_analysis_i/reactance-diagram-30mva-three-generators
- Whole chapter: https://www.bctengineer.com/md/semester_4/power_system_analysis_i/chapter-3

## Question

Draw the reactance diagram with all values in p.u. on a base of 30 MVA, 6.6 kV in the circuit of generator G1. Required data are as follows: G1: 25 MVA, 6.6 kV, j0.2 p.u.; G2: 15 MVA, 6.6 kV, j0.15 p.u.; G3: 30 MVA, 13.2 kV, j0.15 p.u.; T1: 30 MVA, 6.6 (delta) kV/115 (star) kV, j0.1 p.u.; T2: 15 MVA, 6.6 (delta) kV/115 (star) kV, j0.1 p.u.; T3: single phase units each rated 10 MVA, 69/6.9 kV, j0.1 p.u. [Figure: G1 (Y, grounded) → T1 (Δ–Y grounded) → line j120 Ω → junction bus; from the junction, T2 (Y grounded on HV side, Δ on LV side) up to G2 (Y, grounded); and a line j90 Ω → T3 (Y–Y, grounded) → G3 (Y, grounded).]

## Short answer

On 30 MVA base, Vb=6.6 kV at G1, 115 kV in line, 11.5 kV at G3. Reactances: G1 j0.24, T1 j0.10, line (j120 Ω) j0.272, T2 j0.20, G2 j0.30, line (j90 Ω) j0.204, T3 j0.108, G3 j0.1976.

## Answer

#### Base values
- $S_b = 30$ MVA, and $V_b = 6.6$ kV in the G1 circuit.
- Line section (through T1, 6.6/115 kV): $V_b = 115$ kV, so $Z_b = 115^2/30 = 440.83\ \Omega$.
- G2 circuit (through T2, 115/6.6 kV): $V_b = 6.6$ kV.
- T3 is a Y–Y bank of single-phase 69/6.9 kV units. Its line ratio is $\sqrt3\times69 = 119.5$ kV / $\sqrt3\times6.9 = 11.95$ kV, and its rating is $3\times10 = 30$ MVA.
- G3 circuit: $V_b = 115\times\dfrac{11.95}{119.5} = 11.5$ kV.

#### Per-unit reactances
$$
\begin{aligned}
G_1&: 0.2\times\frac{30}{25} = 0.24\\
G_2&: 0.15\times\frac{30}{15} = 0.30\\
G_3&: 0.15\times\frac{30}{30}\left(\frac{13.2}{11.5}\right)^2 = 0.1976\\
T_1&: 0.1\times\frac{30}{30} = 0.10\\
T_2&: 0.1\times\frac{30}{15} = 0.20\\
T_3&: 0.1\times\frac{30}{30}\left(\frac{119.5}{115}\right)^2 = 0.1080\\
\text{Line } j120&: \frac{120}{440.83} = 0.2722\\
\text{Line } j90&: \frac{90}{440.83} = 0.2042
\end{aligned}
$$

| Element | p.u. (30 MVA base) |
|---|---|
| G1 | j0.24 |
| T1 | j0.10 |
| Line (j120 Ω) | j0.2722 |
| T2 | j0.20 |
| G2 | j0.30 |
| Line (j90 Ω) | j0.2042 |
| T3 | j0.108 |
| G3 | j0.1976 |

#### Reactance diagram
```text
 j0.24  j0.10   j0.2722        j0.2042  j0.108  j0.1976
+-/\/\--/\/\----/\/\----+(J)+---/\/\----/\/\----/\/\--+
|                        |                            |
(E1)                   j0.20 (T2)                   (E3)
|                        |                            |
|                      j0.30 (G2)                     |
|                        |                            |
|                      (E2)                           |
+------------------- reference -----------------------+
```

Here J is the junction bus. Winding connections and earthing do not affect these positive-sequence reactances.

## Check yourself

The answer's key points as multiple-choice questions, with the correct option and why.

1. With 6.6 kV base at G1 and T1 6.6/115 kV, what is the base voltage of the line section, and Zb at 30 MVA?
   A. 6.6 kV; 1.45 Ω
   B. 115 kV; 440.83 Ω
   C. 115 kV; 13225 Ω
   D. 69 kV; 158.7 Ω
   Answer: B. Vb = 115 kV and Zb = 115^2/30 = 440.83 Ω. (Key point: Base voltage in line zone)

2. T3 consists of single-phase 69/6.9 kV, 10 MVA units in Y-Y. What are its three-phase rating and line ratio?
   A. 10 MVA, 69/6.9 kV
   B. 30 MVA, 119.5/11.95 kV
   C. 30 MVA, 69/6.9 kV
   D. 10 MVA, 119.5/11.95 kV
   Answer: B. Rating is 3x10 = 30 MVA and the line ratio is sqrt(3)x69 / sqrt(3)x6.9 = 119.5/11.95 kV. (Key point: Y-Y bank of single-phase units)

3. What is the base voltage in the G3 circuit?
   A. 13.2 kV
   B. 6.6 kV
   C. 11.5 kV
   D. 6.9 kV
   Answer: C. Vb = 115 x 11.95/119.5 = 11.5 kV, so G3 (13.2 kV rated) needs (13.2/11.5)^2 correction. (Key point: Base of G3 circuit)

4. Do the Δ/Y windings and grounding change the positive-sequence reactance diagram?
   A. Yes, they add zero-sequence impedances
   B. Yes, Δ doubles the reactance
   C. No, they do not affect these positive-sequence reactances
   D. Only the grounding changes it
   Answer: C. Connections and earthing only matter for zero-sequence; the diagram uses positive-sequence reactances. (Key point: Effect of connections)

## Related in Power System Analysis I

- [Reactance diagram: 50 MVA, 13.8 kV base, three generators](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3Areactance-diagram-50mva-13-8kv) — Power System Analysis I, chapter 3
- [Reactance diagram: 30 MVA, 6.6 kV base, three lines](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3Areactance-diagram-30mva-g1-motor) — Power System Analysis I, chapter 3
- [Per unit circuit of three-generator system, 30 MVA base](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3Apu-circuit-30mva-g1-g2-g3) — Power System Analysis I, chapter 3
- [Reactance diagram: 20 MVA generator, 15 kV/25 MVA base](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3Areactance-diagram-20mva-15kv-25mva) — Power System Analysis I, chapter 3
- [Reactance diagram: three generators, two 220 kV lines](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3Areactance-diagram-three-gens-two-lines) — Power System Analysis I, chapter 3
- [Impedance diagram: three generators, j100 and j130 Ω lines](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3Aimpedance-diagram-three-gens-j100-j130) — Power System Analysis I, chapter 3

## Related in other subjects

- [Neutral reactance for 15 MVA generator](https://www.bctengineer.com/question.md?key=semester_5%2Fpower_system_analysis_ii%3Aneutral-reactance-15mva) — Power System Analysis II, chapter 5
- [Fault level: two 25 MVA generators, 50% reduction](https://www.bctengineer.com/question.md?key=semester_7%2Fpower_plant_equipment%3Afault-two-25mva-50-percent) — Power Plant Equipment, chapter 4
- [Generator-reactor system fault MVA](https://www.bctengineer.com/question.md?key=semester_5%2Fpower_system_analysis_ii%3Agenerator-reactor-fault-mva) — Power System Analysis II, chapter 3
- [Short circuit MVA of feeder circuit breaker](https://www.bctengineer.com/question.md?key=semester_5%2Fpower_system_analysis_ii%3Afeeder-cb-short-circuit-mva) — Power System Analysis II, chapter 3, asked 2×