# Reactance diagram: 50 MVA, 13.8 kV base, three generators

Power System Analysis I · Chapter 3: Computational Technique

- Asked in: 2075 Baisakh, 6 marks
- Video: [Problem #2 | Impedance & Reactance diagram | PSA](https://www.youtube.com/watch?v=Mq3pAkxuIjc) — FOR STUDENTS
- Answer checked by Claude Opus 5.5 (high effort) on 2026-10-14
- Page: https://www.bctengineer.com/q/semester_4/power_system_analysis_i/reactance-diagram-50mva-13-8kv
- Whole chapter: https://www.bctengineer.com/md/semester_4/power_system_analysis_i/chapter-3

## Question

Draw the reactance diagram using a base of 50 MVA and 13.8 kV on generator G1 of a given single line diagram of a power system. The ratings of the generators and transformers are given below: G1: 20 MVA, 13.8 kV, X" = 20%; G2: 30 MVA, 18 kV, X" = 20%; G3: 30 MVA, 20 kV, X" = 20%; T1: 25 MVA, 220/13.8 kV, X = 10%; T2: 3 single phase units each rated 10 MVA, 127/18 kV, X = 10%; T3: 35 MVA, 220/22 kV, X = 10%. [Figure: G1 (Y, grounded) → T1 (Δ on generator side, Y grounded on HV side) → line Section 1, j80 Ω [?] → central bus; from the central bus T2 (Y on HV side, Δ on LV side) → G2; and line Section 2, j100 Ω → T3 (Y grounded on HV side, Δ on LV side) → G3.]

## Short answer

On 50 MVA base, Vb=13.8 kV (G1), 220 kV (line, Zb=968 Ω), 18 kV (G2), 22 kV (G3). Per-unit reactances: G1 j0.5, G2 j0.3333, G3 j0.2755, T1 j0.2, T2 j0.1667, T3 j0.1429, line L1 (j80 Ω) j0.0826, L2 (j100 Ω) j0.1033.

## Answer

All reactances are converted to a common base of 50 MVA; base voltages follow the transformer line-to-line ratios starting from 13.8 kV at G1.

#### Base values
- G1 zone: $V_b = 13.8$ kV
- Line zone (T1 13.8/220 kV): $V_b = 220$ kV, $Z_b = \frac{220^2}{50} = 968\ \Omega$
- G2 zone: T2 is a Y–Δ bank of 127/18 kV units, line-to-line ratio $\sqrt{3}\times127/18 = 220/18$ kV, so $V_b = 220\times\frac{18}{220} = 18$ kV
- G3 zone (T3 220/22 kV): $V_b = 22$ kV

Formula: $X_{new} = X_{old}\,\frac{S_{b,new}}{S_{old}}\left(\frac{V_{old}}{V_{b,new}}\right)^2$

#### Per-unit values
$$
\begin{aligned}
X_{G1} &= 0.2\times\frac{50}{20} = 0.5\ \text{pu}\\
X_{G2} &= 0.2\times\frac{50}{30}\times\left(\frac{18}{18}\right)^2 = 0.3333\ \text{pu}\\
X_{G3} &= 0.2\times\frac{50}{30}\times\left(\frac{20}{22}\right)^2 = 0.2755\ \text{pu}\\
X_{T1} &= 0.1\times\frac{50}{25} = 0.2\ \text{pu}\\
X_{T2} &= 0.1\times\frac{50}{3\times10} = 0.1667\ \text{pu}\\
X_{T3} &= 0.1\times\frac{50}{35} = 0.1429\ \text{pu}\\
X_{L1} &= \frac{80}{968} = 0.0826\ \text{pu}\\
X_{L2} &= \frac{100}{968} = 0.1033\ \text{pu}
\end{aligned}
$$

| Element | X (pu, 50 MVA base) |
|---|---|
| G1 | 0.5000 |
| G2 | 0.3333 |
| G3 | 0.2755 |
| T1 | 0.2000 |
| T2 | 0.1667 |
| T3 | 0.1429 |
| Line section 1 (j80 Ω) | 0.0826 |
| Line section 2 (j100 Ω) | 0.1033 |

#### Reactance diagram
```text
   j0.2   j0.0826        j0.1033   j0.1429
 +-/\/\/--/\/\/---+------/\/\/------/\/\/--+
 |  T1     L1     |        L2         T3   |
j0.5           j0.1667 (T2)              j0.2755
 |                |                        |
(E1)           j0.3333                   (E3)
 |                |                        |
 |              (E2)                       |
 |                |                        |
 +----------------+------------------------+
            reference (neutral) bus
```

**Answer:** $X_{G1}=0.5$, $X_{G2}=0.333$, $X_{G3}=0.276$, $X_{T1}=0.2$, $X_{T2}=0.167$, $X_{T3}=0.143$, $X_{L1}=0.0826$ and $X_{L2}=0.1033$ pu on 50 MVA, with base voltages 13.8, 220, 18 and 22 kV.

## Check yourself

The answer's key points as multiple-choice questions, with the correct option and why.

1. T2 is three 10 MVA, 127/18 kV single-phase units in Y-Δ. What is the G2 zone base voltage?
   A. 18 kV
   B. 127 kV
   C. 31 kV
   D. 13.8 kV
   Answer: A. Line ratio is 220/18 kV, so Vb = 220 x 18/220 = 18 kV. (Key point: Base voltage G2 zone)

2. What MVA rating is used for T2?
   A. 10 MVA
   B. 30 MVA
   C. 50 MVA
   D. 127 MVA
   Answer: B. Three units of 10 MVA make 30 MVA, giving X = 0.1 x 50/30 = 0.1667. (Key point: T2 rating)

3. Why is X_G3 multiplied by (20/22)^2?
   A. G3 rating 20 kV differs from the 22 kV base of its zone
   B. T3 is Y-Δ
   C. The line is at 220 kV
   D. Because 50/30 is not 1
   Answer: A. Rated 20 kV vs base 22 kV needs the voltage-squared correction: 0.2x50/30x(20/22)^2 = 0.2755. (Key point: G3 correction)

4. What is the p.u. reactance of the j80 Ω line?
   A. 80/968 = 0.0826
   B. 80/484 = 0.165
   C. 80/220 = 0.364
   D. 80x968
   Answer: A. Zb = 220^2/50 = 968 Ω. (Key point: Line per unit)

## Related in Power System Analysis I

- [Reactance diagram: three generators, 30 MVA 6.6 kV base](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3Areactance-diagram-30mva-three-generators) — Power System Analysis I, chapter 3
- [Per unit circuit of three-generator system, 30 MVA base](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3Apu-circuit-30mva-g1-g2-g3) — Power System Analysis I, chapter 3
- [Reactance diagram: 30 MVA, 6.6 kV base, three lines](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3Areactance-diagram-30mva-g1-motor) — Power System Analysis I, chapter 3
- [Reactance diagram: 20 MVA generator, 15 kV/25 MVA base](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3Areactance-diagram-20mva-15kv-25mva) — Power System Analysis I, chapter 3
- [Reactance diagram: 300 MVA, 20 kV generator, two motors](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3Areactance-diagram-300mva-20kv) — Power System Analysis I, chapter 3
- [Reactance diagram: three generators, two 220 kV lines](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3Areactance-diagram-three-gens-two-lines) — Power System Analysis I, chapter 3

## Related in other subjects

- [Fault level: two 50 MVA generators, 50% reduction](https://www.bctengineer.com/question.md?key=semester_7%2Fpower_plant_equipment%3Afault-two-50mva-50-percent) — Power Plant Equipment, chapter 4
- [Generator-reactor system fault MVA](https://www.bctengineer.com/question.md?key=semester_5%2Fpower_system_analysis_ii%3Agenerator-reactor-fault-mva) — Power System Analysis II, chapter 3
- [Fault level: two 25 MVA generators, 50% reduction](https://www.bctengineer.com/question.md?key=semester_7%2Fpower_plant_equipment%3Afault-two-25mva-50-percent) — Power Plant Equipment, chapter 4
- [Neutral reactance for 15 MVA generator](https://www.bctengineer.com/question.md?key=semester_5%2Fpower_system_analysis_ii%3Aneutral-reactance-15mva) — Power System Analysis II, chapter 5