title: "Reactance diagram: 90 MVA generator (25%), two motors"
subject: "Power System Analysis I"
chapter: 3
key: "semester_4/power_system_analysis_i:reactance-diagram-90mva-generator-25"
source: https://www.bctengineer.com/q/semester_4/power_system_analysis_i/reactance-diagram-90mva-generator-25
site: BCT Engineering
---

# Reactance diagram: 90 MVA generator (25%), two motors

Power System Analysis I · Chapter 3: Computational Technique

- Asked in: 2075 Bhadra, 8 marks
- Video: [How to find the perunit impedance of each element in electric electric power system using MATLAB??](https://www.youtube.com/watch?v=0VquSwY6zng) — Electrical Engineering simplified
- Answer checked by Claude Opus 5.5 (high effort) on 2026-10-14
- Page: https://www.bctengineer.com/q/semester_4/power_system_analysis_i/reactance-diagram-90mva-generator-25
- Whole chapter: https://www.bctengineer.com/md/semester_4/power_system_analysis_i/chapter-3

## Question

A 90 MVA, 11 kV 3-phase generator has a reactance of 25%. The generator supplies two motors through transformers and transmission line shown in figure below. The transformer T1 is a 3-phase, 100 MVA, 10/132 kV, 6% reactance. The transformer T2 is composed of three single phase units each rated at 30 MVA, 66/10 kV with 5% reactance. The connection of T1 and T2 are shown in figure. The motors are rated at 50 MVA and 40 MVA, both 10 kV and 20% reactance. Taking the generator rating as base, draw the per unit reactance diagram. The reactance of the line is 100 Ω. [Figure: G1 → T1 (Δ on generator side, Y grounded on line side) → Line → T2 (Y grounded on line side, Δ on motor side) → bus feeding M1 (Y, grounded) and M2 (Δ).]

## Short answer

On 90 MVA base: X_G=0.25, X_T1=0.0446, X_line=0.4269, X_T2=0.0310, X_M1=0.2231, X_M2=0.2789 pu. Base voltages: 11 kV, 145.2 kV, 12.70 kV.

## Answer

Base: 90 MVA and 11 kV in the generator circuit (generator rating). Base voltages in other zones follow the line-to-line turns ratios.

#### Base voltages
- Generator zone: $V_{b1} = 11$ kV
- Line zone (T1 is 10/132 kV): $V_{b2} = 11\times\frac{132}{10} = 145.2$ kV
- T2: three single-phase 66/10 kV units connected Y (line side) – Δ (motor side), so line-to-line ratio is $66\sqrt{3}/10 = 114.32/10$ kV. Motor zone:

$$
V_{b3} = 145.2\times\frac{10}{114.32} = 12.70\ \text{kV}
$$

$$
Z_{b2} = \frac{145.2^2}{90} = 234.26\ \Omega
$$

#### Per-unit reactances (on 90 MVA)
$$
\begin{aligned}
X_G &= 0.25\ \text{pu}\\
X_{T1} &= 0.06\times\frac{90}{100}\times\left(\frac{10}{11}\right)^2 = 0.0446\ \text{pu}\\
X_{line} &= \frac{100}{234.26} = 0.4269\ \text{pu}\\
X_{T2} &= 0.05\times\frac{90}{3\times30}\times\left(\frac{10}{12.70}\right)^2 = 0.0310\ \text{pu}\\
X_{M1} &= 0.2\times\frac{90}{50}\times\left(\frac{10}{12.70}\right)^2 = 0.2231\ \text{pu}\\
X_{M2} &= 0.2\times\frac{90}{40}\times\left(\frac{10}{12.70}\right)^2 = 0.2789\ \text{pu}
\end{aligned}
$$

| Element | X (pu, 90 MVA base) |
|---|---|
| Generator | 0.2500 |
| T1 | 0.0446 |
| Line (100 Ω) | 0.4269 |
| T2 | 0.0310 |
| Motor M1 | 0.2231 |
| Motor M2 | 0.2789 |

#### Reactance diagram
```text
     j0.0446   j0.4269   j0.0310
 +---/\/\/-----/\/\/-----/\/\/---+--------+
 |    T1        line       T2    |        |
j0.25                         j0.2231  j0.2789
 |                               |        |
(Eg)                           (Em1)    (Em2)
 |                               |        |
 +-------------------------------+--------+
            reference bus
```

**Answer:** On 90 MVA base: $X_G = 0.25$, $X_{T1} = 0.0446$, $X_{line} = 0.4269$, $X_{T2} = 0.0310$, $X_{M1} = 0.2231$, $X_{M2} = 0.2789$ pu; base voltages 11 kV, 145.2 kV and 12.70 kV.

## Check yourself

The answer's key points as multiple-choice questions, with the correct option and why.

1. T1 is 10/132 kV and T2 is Y-Δ 66/10 kV single-phase units. What is the motor-zone base?
   A. 10 kV
   B. 11 kV
   C. 12.70 kV
   D. 145.2 kV
   Answer: C. Line zone 145.2 kV, T2 ratio 114.32/10 gives 12.70 kV. (Key point: Motor zone base voltage)

2. What is T2's line-to-line ratio?
   A. 66/10 kV
   B. 66sqrt(3)/10 = 114.32/10 kV
   C. 66/(10 sqrt(3)) kV
   D. 198/10 kV
   Answer: B. The Y side is sqrt(3) x 66 = 114.32 kV. (Key point: T2 line ratio)

3. Why is X_T1 = 0.06 x 90/100 x (10/11)^2?
   A. Rated 10 kV of T1 LV winding differs from the 11 kV base
   B. T1 is a delta transformer
   C. Line is 145.2 kV
   D. The generator has 25%
   Answer: A. Both MVA and voltage corrections are required. (Key point: T1 correction)

4. What is the line p.u. reactance?
   A. 100/234.26 = 0.4269
   B. 100/90
   C. 100/145.2
   D. 100/121
   Answer: A. Zb = 145.2^2/90 = 234.26 Ω. (Key point: Line Zb)

## Close variants set in other exams

- [Reactance diagram: 90 MVA generator (15%), two motors](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3Areactance-diagram-90mva-generator-15) — Power System Analysis I, chapter 3, asked 2×

## Related in Power System Analysis I

- [Reactance diagram: 300 MVA, 20 kV generator, two motors](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3Areactance-diagram-300mva-20kv) — Power System Analysis I, chapter 3
- [Impedance diagram: 25 MVA generator, two motors](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3Aimpedance-diagram-25mva-two-motors) — Power System Analysis I, chapter 3
- [Reactance diagram: 20 MVA generator, 15 kV/25 MVA base](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3Areactance-diagram-20mva-15kv-25mva) — Power System Analysis I, chapter 3
- [Reactance diagram: 100 MVA base, two parallel paths](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3Areactance-diagram-90mva-two-paths) — Power System Analysis I, chapter 3
- [Per unit values: 100 MVA generator, two motors](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3Aper-unit-100mva-6kv-two-motors) — Power System Analysis I, chapter 3
- [Reactance diagram: two generators, two motors, j50 Ω line](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3Areactance-diagram-two-gens-two-motors) — Power System Analysis I, chapter 3

## Related in other subjects

- [Design: 100 kVA 11/132 kV transformer with winding data](https://www.bctengineer.com/question.md?key=semester_5%2Felectric_machine_design%3Adesign-100kva-11-132kv) — Electric Machine Design, chapter 3, asked 3×
- [L-L fault through Zf with two motors](https://www.bctengineer.com/question.md?key=semester_5%2Fpower_system_analysis_ii%3All-fault-motors-zf-new) — Power System Analysis II, chapter 5
- [Differential protection: 11 kV, 100 MVA generator](https://www.bctengineer.com/question.md?key=semester_6%2Fswitchgear_and_protection%3Agenerator-differential-11kv-6-ohm) — Switchgear and Protection, chapter 7
- [IDMT relays across 132/11 kV transformer (3500 A)](https://www.bctengineer.com/question.md?key=semester_6%2Fswitchgear_and_protection%3Aidmt-132-11kv-3500a) — Switchgear and Protection, chapter 7