title: "Reactance diagram of eight-bus system"
subject: "Power System Analysis I"
chapter: 3
key: "semester_4/power_system_analysis_i:reactance-diagram-eight-bus"
source: https://www.bctengineer.com/q/semester_4/power_system_analysis_i/reactance-diagram-eight-bus
site: BCT Engineering
---

# Reactance diagram of eight-bus system

Power System Analysis I · Chapter 3: Computational Technique

- Asked in: 2069 Bhadra, 6 marks
- Video: [Problem #2 | Impedance & Reactance diagram | PSA](https://www.youtube.com/watch?v=Mq3pAkxuIjc) — FOR STUDENTS
- Answer checked by Claude Opus 5.5 (high effort) on 2026-10-14
- Page: https://www.bctengineer.com/q/semester_4/power_system_analysis_i/reactance-diagram-eight-bus
- Whole chapter: https://www.bctengineer.com/md/semester_4/power_system_analysis_i/chapter-3

## Question

Construct a reactance diagram for the system given below and express all the reactances in per unit system. G1, G2: 10 MVA, 11.5 kV, 10%; G3: 15 MVA, 11.5 kV, 12%; T1, T2: 10 MVA, 11/66 kV, 10%; T3: 15 MVA, 11/66, 15%; T4: 35 MVA, 66/11 kV, 18%; L1 = L2 = L3 = L4 = j20 Ω/ph. [Figure: G1 (bus 1) → T1 → bus 2; G2 (bus 3) → T2 → bus 4; line L2 from bus 2 to bus 6, L1 from bus 2 to bus 4, L3 from bus 4 to bus 7, L4 from bus 6 to bus 7; T3 between bus 6 and bus 5 feeding G3; T4 between bus 7 and bus 8 feeding motor M (no motor rating printed).]

## Short answer

Base 10 MVA, 11 kV generator side, 66 kV lines. Per-unit reactances: X_G1 = X_G2 = 0.1093, X_G3 = 0.0874, X_T1 = X_T2 = X_T3 = 0.10, X_T4 = 0.0514, each line 0.0459 pu. Motor reactance is unspecified.

## Answer

**Choice of base:** 10 MVA, with 11 kV in the generator circuits (the transformer LV rating) and 66 kV on the lines. The motor rating is not printed, so its reactance is left as $X_M$ (pu on its own rating). Its value on the common base is $X_M\frac{10}{S_M}\left(\frac{V_M}{11}\right)^2$.

$$
Z_{b,66} = \frac{66^2}{10} = 435.6\ \Omega
$$

#### Per-unit reactances (10 MVA base)
$$
\begin{aligned}
X_{G1} = X_{G2} &= 0.10\times\frac{10}{10}\times\left(\frac{11.5}{11}\right)^2 = 0.1093\ \text{pu}\\
X_{G3} &= 0.12\times\frac{10}{15}\times\left(\frac{11.5}{11}\right)^2 = 0.0874\ \text{pu}\\
X_{T1} = X_{T2} &= 0.10\ \text{pu}\\
X_{T3} &= 0.15\times\frac{10}{15} = 0.10\ \text{pu}\\
X_{T4} &= 0.18\times\frac{10}{35} = 0.0514\ \text{pu}\\
X_{L1} = X_{L2} = X_{L3} = X_{L4} &= \frac{20}{435.6} = 0.0459\ \text{pu}
\end{aligned}
$$

| Element | X (pu, 10 MVA) |
|---|---|
| G1, G2 | 0.1093 each |
| G3 | 0.0874 |
| T1, T2 | 0.1000 each |
| T3 | 0.1000 |
| T4 | 0.0514 |
| L1 to L4 | 0.0459 each |

#### Reactance diagram
```text
 (E1)-j0.1093-[1]-j0.10-[2]---j0.0459(L2)---[6]
                         |                   |
                   j0.0459(L1)          j0.0459(L4)
                         |                   |
 (E2)-j0.1093-[3]-j0.10-[4]---j0.0459(L3)---[7]

 [6]-j0.10(T3)-[5]-j0.0874-(E3)
 [7]-j0.0514(T4)-[8]-jXM-(Em)

 All sources (E1, E2, E3, Em) return to the
 common reference (neutral) bus.
```

**Answer:** On 10 MVA (11 kV / 66 kV bases): $X_{G1} = X_{G2} = 0.1093$, $X_{G3} = 0.0874$, $X_{T1} = X_{T2} = X_{T3} = 0.10$, $X_{T4} = 0.0514$, and each line 0.0459 pu.

## Check yourself

The answer's key points as multiple-choice questions, with the correct option and why.

1. Which bases are used?
   A. 10 MVA, 66 kV everywhere
   B. 10 MVA, 11 kV in generator circuits and 66 kV on lines
   C. 35 MVA, 11 kV on lines
   D. 15 MVA, 11.5 kV on lines
   Answer: B. Transformer ratios 11/66 define the zones. (Key point: Choice of base)

2. Why is X_G1 = 0.1093 pu rather than 0.10?
   A. The generator rating 11.5 kV differs from the 11 kV base: 0.10 x (11.5/11)^2
   B. The MVA is different
   C. The line impedance modifies it
   D. T1 reactance is added
   Answer: A. pu reactance scales with (kV_rated/kV_base)^2. (Key point: Generator correction)

3. How is a 20 Ω line converted to pu?
   A. 20/66 = 0.303
   B. 20/10 = 2
   C. 20 x 435.6
   D. 20/435.6 = 0.0459 pu, using Zb = 66^2/10
   Answer: D. Zb = 435.6 Ω. (Key point: Line reactance)

4. The motor rating is missing. How is its X handled?
   A. Taken as zero
   B. Taken equal to G3
   C. Left as X_M, converted by X_M x 10/S_M x (V_M/11)^2
   D. Taken as the T4 value
   Answer: C. General change-of-base formula. (Key point: Motor reactance)

## Related in Power System Analysis I

- [Reactance diagram: G, T1, j18 Ω line, T2, M](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3Areactance-diagram-g-t1-t2-m) — Power System Analysis I, chapter 3
- [Per unit circuit of three-generator system, 30 MVA base](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3Apu-circuit-30mva-g1-g2-g3) — Power System Analysis I, chapter 3
- [Reactance diagram: 30 MVA, 6.6 kV base, three lines](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3Areactance-diagram-30mva-g1-motor) — Power System Analysis I, chapter 3
- [Reactance diagram: three generators, 30 MVA 6.6 kV base](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3Areactance-diagram-30mva-three-generators) — Power System Analysis I, chapter 3
- [Reactance diagram: 50 MVA, 13.8 kV base, three generators](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3Areactance-diagram-50mva-13-8kv) — Power System Analysis I, chapter 3
- [Reactance diagram: 90 MVA generator (15%), two motors](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3Areactance-diagram-90mva-generator-15) — Power System Analysis I, chapter 3, asked 2×

## Related in other subjects

- [Fault MVA at bus 5 with inductive lines](https://www.bctengineer.com/question.md?key=semester_5%2Fpower_system_analysis_ii%3Afault-mva-bus5-mh-lines) — Power System Analysis II, chapter 3, asked 2×
- [Design: 500 kVA 66/11 kV power transformer](https://www.bctengineer.com/question.md?key=semester_5%2Felectric_machine_design%3Adesign-500kva-66-11kv) — Electric Machine Design, chapter 3, asked 6×
- [Design: 4000 kVA 66/11 kV power transformer](https://www.bctengineer.com/question.md?key=semester_5%2Felectric_machine_design%3Adesign-4000kva-66-11kv) — Electric Machine Design, chapter 3, asked 5×
- [Block diagram reduction with G1, G2, H1, H2, feedforward](https://www.bctengineer.com/question.md?key=semester_3%2Fcontrol_systems%3Abdr-g1g2-h1h2-ff-unity) — Control Systems, chapter 3, asked 2×