# Reactance diagram: three generators, two 220 kV lines

Power System Analysis I · Chapter 3: Computational Technique

- Asked in: 2076 Baisakh, 10 marks
- Video: [Impedance and Reactance diagram Problem-3 | Power System Analysis | PSA | per unit Reactance diagram](https://www.youtube.com/watch?v=TQ8W4-l9S2I) — Simple n Easy Learning
- Answer checked by Claude Opus 5.5 (high effort) on 2026-10-14
- Page: https://www.bctengineer.com/q/semester_4/power_system_analysis_i/reactance-diagram-three-gens-two-lines
- Whole chapter: https://www.bctengineer.com/md/semester_4/power_system_analysis_i/chapter-3

## Question

Draw the reactance diagram of the following figure with its equivalent per unit system. Take base MVA = 100 MVA and base voltage = 11 kV for generator. Compute the reactance diagram. [Figure: G1 → T1 and G2 → T2 feed a common 220 kV bus at the sending side; Line-1 and Line-2 run in parallel from there to a receiving bus, which feeds G3 through T3. Data: G1 100 MVA, 11 kV, X = 25%; G2 100 MVA, 11 kV, X = 20%; G3 100 MVA, 11 kV, X = 20%; T1 100 MVA, 11/220 kV, X = 6%; T2 100 MVA, 11/220 kV, X = 7%; T3 100 MVA, 220/11 kV, X = 7%; Line-1 100 MVA, 220 kV, X = 10%; Line-2 100 MVA, 220 kV, X = 10%.]

## Short answer

Base 100 MVA, 11 kV at generators, 220 kV line. All components rated at base MVA and matching voltage, so per-unit reactances equal percent/100: G1 j0.25, G2 j0.20, G3 j0.20, T1 j0.06, T2 j0.07, T3 j0.07, each line j0.10 (parallel combination j0.05).

## Answer

#### Base values
- $S_b = 100$ MVA, and $V_b = 11$ kV in the generator circuits.
- Line section (through 11/220 kV transformers): $V_b = 220$ kV, so $Z_b = 220^2/100 = 484\ \Omega$.
- G3 circuit (through T3, 220/11 kV): $V_b = 11$ kV.

#### Conversion to the common base
$$
X_{pu,new} = X_{pu,old}\times\frac{S_{b,new}}{S_{b,old}}\times\left(\frac{V_{b,old}}{V_{b,new}}\right)^2
$$

Every component is rated at 100 MVA, and its rated voltage equals the base voltage of its section. Both correction factors are therefore 1, and each p.u. value equals its percentage reactance divided by 100.

| Element | Rating | Calculation | p.u. reactance |
|---|---|---|---|
| G1 | 100 MVA, 11 kV, 25 % | $0.25\times1\times1$ | j0.25 |
| G2 | 100 MVA, 11 kV, 20 % | $0.20\times1\times1$ | j0.20 |
| G3 | 100 MVA, 11 kV, 20 % | $0.20\times1\times1$ | j0.20 |
| T1 | 100 MVA, 11/220 kV, 6 % | $0.06\times1\times1$ | j0.06 |
| T2 | 100 MVA, 11/220 kV, 7 % | $0.07\times1\times1$ | j0.07 |
| T3 | 100 MVA, 220/11 kV, 7 % | $0.07\times1\times1$ | j0.07 |
| Line 1 | 100 MVA, 220 kV, 10 % | $0.10\times1\times1$ | j0.10 |
| Line 2 | 100 MVA, 220 kV, 10 % | $0.10\times1\times1$ | j0.10 |

In ohms, each line is $0.10\times484 = 48.4\ \Omega$.

#### Reactance diagram
```text
 j0.25  j0.06          j0.10 (L1)
+-/\/\--/\/\--+------+--/\/\--+------+ j0.07  j0.20
|             |      |        |      +--/\/\--/\/\--+
(E1)          |      +--/\/\--+                     |
|             |        j0.10 (L2)                  (E3)
|  j0.20 j0.07|                                     |
+-/\/\--/\/\--+                                     |
|                                                   |
(E2)                                                |
+----------------------- reference -----------------+
```

#### Simplified values (useful for fault studies)
- The two lines in parallel: $j0.10\,\|\,j0.10 = j0.05$.
- G1–T1 branch: $j0.31$. G2–T2 branch: $j0.27$.
- These two branches in parallel: $\dfrac{0.31\times0.27}{0.58} = j0.1443$.
- G3–T3 branch: $j0.27$.

## Check yourself

The answer's key points as multiple-choice questions, with the correct option and why.

1. Why is each p.u. value simply the percentage divided by 100?
   A. All reactances are already on 100 MVA and the rated voltage equals the section base voltage
   B. Percent and p.u. are always equal
   C. The lines have no reactance
   D. Transformers are ignored
   Answer: A. Both S_new/S_old and (V_old/V_new)^2 factors equal 1. (Key point: Correction factors)

2. What are the base voltage and Zb for the line section?
   A. 11 kV; 1.21 Ω
   B. 220 kV; 484 Ω
   C. 220 kV; 48.4 Ω
   D. 110 kV; 121 Ω
   Answer: B. Zb = 220^2/100 = 484 Ω. (Key point: Line zone base)

3. What is the combined reactance of two parallel j0.10 lines?
   A. j0.20
   B. j0.10
   C. j0.05
   D. j0.025
   Answer: C. 0.10 || 0.10 = 0.05 p.u. (Key point: Parallel lines)

4. The G1-T1 branch is j0.31 and G2-T2 is j0.27. What is their parallel value?
   A. j0.58
   B. j0.1443
   C. j0.04
   D. j0.29
   Answer: B. 0.31x0.27/0.58 = 0.1443. (Key point: G1-T1 and G2-T2 in parallel)

## Related in Power System Analysis I

- [Reactance diagram: 50 MVA, 13.8 kV base, three generators](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3Areactance-diagram-50mva-13-8kv) — Power System Analysis I, chapter 3
- [Reactance diagram: 30 MVA, 6.6 kV base, three lines](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3Areactance-diagram-30mva-g1-motor) — Power System Analysis I, chapter 3
- [Per unit circuit of three-generator system, 30 MVA base](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3Apu-circuit-30mva-g1-g2-g3) — Power System Analysis I, chapter 3
- [Reactance diagram: three generators, 30 MVA 6.6 kV base](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3Areactance-diagram-30mva-three-generators) — Power System Analysis I, chapter 3
- [Reactance diagram: 100 MVA base, two parallel paths](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3Areactance-diagram-90mva-two-paths) — Power System Analysis I, chapter 3
- [Reactance diagram: 90 MVA generator (25%), two motors](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3Areactance-diagram-90mva-generator-25) — Power System Analysis I, chapter 3, asked 2×

## Related in other subjects

- [Fault at receiving end of 220 kV lines](https://www.bctengineer.com/question.md?key=semester_5%2Fpower_system_analysis_ii%3Afault-220kv-two-generators) — Power System Analysis II, chapter 3
- [Differential protection: 11 kV, 100 MVA generator](https://www.bctengineer.com/question.md?key=semester_6%2Fswitchgear_and_protection%3Agenerator-differential-11kv-6-ohm) — Switchgear and Protection, chapter 7
- [Generator-reactor system fault MVA](https://www.bctengineer.com/question.md?key=semester_5%2Fpower_system_analysis_ii%3Agenerator-reactor-fault-mva) — Power System Analysis II, chapter 3
- [Fault level: two 50 MVA generators, 50% reduction](https://www.bctengineer.com/question.md?key=semester_7%2Fpower_plant_equipment%3Afault-two-50mva-50-percent) — Power Plant Equipment, chapter 4