title: "Short line 40 km, 381 MVA: regulation and efficiency"
subject: "Power System Analysis I"
chapter: 6
key: "semester_4/power_system_analysis_i:short-line-40km-381mva"
source: https://www.bctengineer.com/q/semester_4/power_system_analysis_i/short-line-40km-381mva
site: BCT Engineering
---

# Short line 40 km, 381 MVA: regulation and efficiency

Power System Analysis I · Chapter 6: Performance Analysis

- Asked in: 2075 Baisakh, 6 marks
- Video: [Three Phase Short Transmission Line Explained | Voltage Regulation, Efficiency & Numerical](https://www.youtube.com/watch?v=GKOllJ9gurw) — Electrology
- Answer checked by Claude Opus 5.5 (high effort) on 2026-10-14
- Page: https://www.bctengineer.com/q/semester_4/power_system_analysis_i/short-line-40km-381mva
- Whole chapter: https://www.bctengineer.com/md/semester_4/power_system_analysis_i/chapter-6

## Question

A 220 kV, three phase transmission line is 40 km long. The resistance per phase is 0.15 Ω per km and the inductance per phase is 1.3263 mH per km. The shunt capacitance is negligible. Use the short line model to find the voltage and power at the sending end and the voltage regulation and efficiency when the line is supplying a three phase load of 381 MVA at 0.8 power factor lagging at 220 kV.

## Short answer

Sending end line voltage is 246.2 kV, three-phase power 322.8 MW + j278.6 MVAr. Voltage regulation is 11.91% and efficiency 94.43%, based on short-line model with Z=6+j16.667 Ω.

## Answer

Short-line model: shunt capacitance neglected, $I_S = I_R$.

#### Line impedance
$$
\begin{aligned}
R &= 0.15\times40 = 6\ \Omega \\
X &= 2\pi(50)(1.3263\times10^{-3})(40) = 16.667\ \Omega \\
Z &= 6 + j16.667\ \Omega
\end{aligned}
$$

#### Receiving end
$$
\begin{aligned}
V_R &= \frac{220}{\sqrt3} = 127.02\angle0^\circ\ \text{kV} \\
I_R &= \frac{381\times10^6}{\sqrt3\times220\times10^3} = 999.87\angle-36.87^\circ\ \text{A}
\end{aligned}
$$

#### Sending-end voltage
$$
\begin{aligned}
V_S &= V_R + I_R Z = 127.02 + (0.99987\angle-36.87^\circ)(17.71\angle70.20^\circ) \\
&= 127.02 + 17.71\angle33.33^\circ \\
&= 142.15\angle3.93^\circ\ \text{kV (phase)}
\end{aligned}
$$
Line value $= \sqrt3\times142.15 = 246.21$ kV.

#### Sending-end power
$$
\begin{aligned}
S_S &= 3V_S I_S^* = 3(142.15\angle3.93^\circ)(0.99987\angle36.87^\circ) \\
&= 322.80 + j278.59\ \text{MVA}
\end{aligned}
$$
Sending-end pf $= \cos(40.80^\circ) = 0.757$ lagging.

#### Regulation
$$
\%VR = \frac{246.21 - 220}{220}\times100 = 11.91\%
$$

#### Efficiency
Receiving power $P_R = 381\times0.8 = 304.8$ MW.
$$
\eta = \frac{304.8}{322.80}\times100 = 94.43\%
$$
(Check: loss $= 3I^2R = 3(999.87)^2(6) = 18.0$ MW.)

**Answer: $V_S$ = 246.2 kV (line), $S_S$ = 322.8 MW + j278.6 MVAr, regulation 11.91 %, efficiency 94.43 %.**

## Check yourself

The answer's key points as multiple-choice questions, with the correct option and why.

1. What does the short-line model assume here?
   A. Resistance neglected
   B. Shunt capacitance neglected, so I_S = I_R
   C. Half the capacitance at each end
   D. Capacitance at the middle only
   Answer: B. With shunt capacitance negligible, the sending current equals the receiving current and V_S = V_R + I_R Z. (Key point: Short line model)

2. How is the sending-end voltage obtained?
   A. V_S = V_R - I_R Z using line voltage
   B. V_S = V_R + I_R Z per phase (142.15 kV phase, 246.21 kV line)
   C. V_S = I_R Z only
   D. V_S = V_R / (1 + Z)
   Answer: B. Per phase V_S = 127.02 + 17.71 angle 33.33 deg = 142.15 angle 3.93 deg kV; multiply by sqrt(3) for the line value. (Key point: Sending voltage)

3. How is voltage regulation calculated for this short line?
   A. (142.15 - 246.21)/142.15
   B. I R / V_S
   C. (246.21 - 220)/220 x 100 = 11.91 %
   D. (220 - 246.21)/246.21 x 100
   Answer: C. Short line has A = 1, so regulation = (V_S - V_R)/V_R using consistent (line) values. (Key point: Regulation)

4. How is efficiency found?
   A. 304.8 MW / 381 MW
   B. P_R / P_S = 304.8/322.8 = 94.43 %, with P_R = 381 x 0.8
   C. 381 / 322.8
   D. Q_S / Q_R
   Answer: B. Output is the real power 381 x 0.8 = 304.8 MW and input is P_S = 322.8 MW; the difference 18 MW equals 3I^2R. (Key point: Efficiency)

## Related in Power System Analysis I

- [400 km long line, 60 MVA at 220 kV](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3Along-line-400km-60mva) — Power System Analysis I, chapter 5
- [Regulation and efficiency of 100 km, 110 kV line](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3Aregulation-efficiency-100km-110kv) — Power System Analysis I, chapter 6, asked 2×
- [110 km, 110 kV line: sending end, regulation, efficiency](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3A110km-line-performance) — Power System Analysis I, chapter 6, asked 2×
- [Capacitor for zero regulation, 70 km 220 kV line](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3A70km-220kv-zero-regulation-capacitor) — Power System Analysis I, chapter 6
- [Equivalent-T of 300 km long line](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3Along-line-equivalent-t-300km) — Power System Analysis I, chapter 5
- [Nominal-T 100 km line, 50 MVA at 132 kV](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3Anominal-t-100km-50mva) — Power System Analysis I, chapter 6

## Related in other subjects

- [220 kV double circuit efficiency and regulation](https://www.bctengineer.com/question.md?key=semester_8%2Ftransmission_and_distribution_system_design%3Adouble-circuit-220kv-efficiency-regulation) — Transmission and Distribution System Design, chapter 4
- [Surge impedance and velocity of 220 kV line](https://www.bctengineer.com/question.md?key=semester_8%2Fhigh_voltage_engineering%3Asurge-impedance-220kv-200km) — High Voltage Engineering, chapter 3, asked 2×
- [Restriking voltage numerical (6.6 kV, 8 mH)](https://www.bctengineer.com/question.md?key=semester_6%2Fswitchgear_and_protection%3Arestriking-6-6kv-8mh) — Switchgear and Protection, chapter 6, asked 2×
- [Restriking voltage numerical (11 kV, 10 mH)](https://www.bctengineer.com/question.md?key=semester_6%2Fswitchgear_and_protection%3Arestriking-11kv-10mh) — Switchgear and Protection, chapter 6, asked 2×