# Static compensation to hold sending end at 140 kV

Power System Analysis I · Chapter 6: Performance Analysis

- Asked in: 2074 Bhadra, 6 marks
- Answer checked by Claude Opus 5.5 (high effort) on 2026-10-14
- Page: https://www.bctengineer.com/q/semester_4/power_system_analysis_i/static-compensation-140kv
- Whole chapter: https://www.bctengineer.com/md/semester_4/power_system_analysis_i/chapter-6

## Question

A 3-phase 132 kV overhead line delivers 50 MVA at 132 kV and 0.8 pf lagging. The constants of the line are A = 0.983∠3°, B = 110∠75° Ω per phase. Determine the capacity of the static compensation equipment at the receiving end to reduce the sending end voltage to 140 kV for the same load condition.

## Short answer

A capacitive compensator of approximately 35 MVAr must be installed at the receiving end to reduce the sending end voltage to 140 kV for the same load.

## Answer

Data: $|A| = 0.983$, $\alpha = 3^\circ$, $|B| = 110\ \Omega$, $\beta = 75^\circ$, $V_R$ = 132 kV, load 50 MVA at 0.8 lag = 40 MW + j30 MVAr. With line kV, powers are three-phase.

Without compensation, $V_S = AV_R + B(P - jQ)/V_R = 165.6$ kV, which is too high. We need $|V_S| = 140$ kV with the same 40 MW load.

#### Receiving-end power-circle equations
$$
\begin{aligned}
P_R &= \frac{|V_S||V_R|}{|B|}\cos(\beta-\delta) - \frac{|A||V_R|^2}{|B|}\cos(\beta-\alpha) \\
Q_R &= \frac{|V_S||V_R|}{|B|}\sin(\beta-\delta) - \frac{|A||V_R|^2}{|B|}\sin(\beta-\alpha)
\end{aligned}
$$
$$
\frac{140\times132}{110} = 168.0,\qquad \frac{0.983\times132^2}{110} = 155.71,\qquad \beta-\alpha = 72^\circ
$$

#### Find $\delta$ from $P_R$ = 40 MW
$$
\begin{aligned}
40 &= 168.0\cos(75^\circ-\delta) - 155.71\cos72^\circ \\
40 &= 168.0\cos(75^\circ-\delta) - 48.12 \\
\cos(75^\circ-\delta) &= 0.5245 \Rightarrow 75^\circ-\delta = 58.37^\circ,\ \delta = 16.63^\circ
\end{aligned}
$$

#### Reactive power the line delivers
$$
\begin{aligned}
Q_R &= 168.0\sin58.37^\circ - 155.71\sin72^\circ \\
&= 143.04 - 148.09 = -5.05\ \text{MVAr}
\end{aligned}
$$
So the line can deliver no lagging VAr; it actually needs 5.05 MVAr from the receiving end.

#### Compensator rating
Load requires 30 MVAr lagging. The compensator must supply:
$$
Q_C = 30 - (-5.05) = 35.05\ \text{MVAr}
$$

**Answer: Static (capacitive) compensator of about 35 MVAr at the receiving end.**

## Check yourself

The answer's key points as multiple-choice questions, with the correct option and why.

1. What is held fixed and what is found to size the compensator?
   A. delta fixed at 0
   B. |V_R| is varied
   C. |V_S| = 140 kV and P_R = 40 MW fixed; find delta then the Q_R the line can deliver
   D. Q_R fixed at 30; find P
   Answer: C. Using the power-circle equations with |V_S| = 140 kV, P_R = 40 MW gives delta = 16.63 deg and then Q_R. (Key point: Method)

2. What is the line's Q_R at |V_S| = 140 kV and what does it mean?
   A. +30 MVAr; no compensator needed
   B. -5.05 MVAr; line cannot supply lagging VAr, needs 5.05 from the receiving end
   C. +5.05 MVAr; load Q reduced
   D. 0 MVAr; unity pf
   Answer: B. Q_R = 143.04 - 148.09 = -5.05 MVAr: the line delivers no lagging VAr at that sending voltage. (Key point: Result for Q_R)

## Related in Power System Analysis I

- [Sending end from A = 0.98∠3°, B = 110∠75°](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3Aabcd-132kv-50mva-a098-3) — Power System Analysis I, chapter 6, asked 2×
- [Sending end from A = 0.98∠0.3°, B = 110∠75°](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3Aabcd-132kv-50mva-a098-0-3) — Power System Analysis I, chapter 6, asked 2×
- [Nominal-T 100 km line, 50 MVA at 132 kV](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3Anominal-t-100km-50mva) — Power System Analysis I, chapter 6
- [110 km, 110 kV line: sending end, regulation, efficiency](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3A110km-line-performance) — Power System Analysis I, chapter 6, asked 2×
- [Sending end active power from ABCD, 132/130.5 kV](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3Asending-power-132kv-130-5kv) — Power System Analysis I, chapter 6
- [Sending and receiving power, 140∠10° and 132 kV](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3Apower-140kv-132kv-a099) — Power System Analysis I, chapter 6

## Related in other subjects

- [Fault at load end of overhead line](https://www.bctengineer.com/question.md?key=semester_5%2Fpower_system_analysis_ii%3Afault-load-end-33kv-line) — Power System Analysis II, chapter 3
- [Fault at receiving end of 132 kV lines](https://www.bctengineer.com/question.md?key=semester_5%2Fpower_system_analysis_ii%3Afault-132kv-receiving-end-2071) — Power System Analysis II, chapter 3
- [Currents and efficiency of 132/11 kV transformer at 5 MW](https://www.bctengineer.com/question.md?key=semester_4%2Felectrical_machines_i%3Astar-delta-132-11kv-5mw-currents) — Electrical Machines I, chapter 2, asked 3×