# Inductance of unsymmetrical transposed line

Power System Analysis I · Chapter 4: Line Parameter Calculations

- Asked in: 2068 Bhadra, 5 marks
- Video: [Inductance calculations for unsymmetrical 3-phase system](https://www.youtube.com/watch?v=T3d27nmIoVI) — Upendra Bhusan
- Answer checked by Claude Opus 5.5 (high effort) on 2026-10-14
- Page: https://www.bctengineer.com/q/semester_4/power_system_analysis_i/unsymmetrical-inductance-10mm
- Whole chapter: https://www.bctengineer.com/md/semester_4/power_system_analysis_i/chapter-4

## Question

A 3-phase, 50 Hz, overhead line has three phase conductors with the following configuration. Compute the inductance per phase per km if each of the phase conductors is round solid of 10 mm diameter. Assume completely transposed line. [Figure: conductors a, b, c at the corners of a triangle with Dab = 4.5 m, Dbc = 5.5 m, Dca = 7.5 m.]

## Short answer

Deq = 5.7044 m, r' = 0.7788×5 = 3.894 mm. Per-phase inductance L = 2×10⁻⁷ ln(Deq/r') = 1.458 mH/km.

## Answer

For a completely transposed line with unsymmetrical spacing, the inductance per phase is $L = 2\times10^{-7}\ln(D_{eq}/r')$ H/m, where $D_{eq} = \sqrt[3]{D_{ab}D_{bc}D_{ca}}$.

```text
          a
         / \
   4.5 m/   \7.5 m
       /     \
      b-------c
        5.5 m
```

**Data:** diameter 10 mm, $r = 5$ mm $= 0.005$ m, $r' = 0.7788 \times 0.005 = 0.003894$ m.

#### Equivalent spacing

$$
D_{eq} = \sqrt[3]{4.5 \times 5.5 \times 7.5} = \sqrt[3]{185.625} = 5.7044\ \text{m}
$$

#### Inductance per phase

$$
\begin{aligned}
L &= 2\times10^{-7}\ln\frac{5.7044}{0.003894} = 2\times10^{-7}\times7.2896 \\
&= 1.4579\times10^{-6}\ \text{H/m} = 1.458\ \text{mH/km}
\end{aligned}
$$

**Answer:** $L = 1.458$ mH per phase per km.

## Check yourself

The answer's key points as multiple-choice questions, with the correct option and why.

1. With D_ab = 4.5, D_bc = 5.5 and D_ca = 7.5 m, D_eq is:
   A. cube root of (4.5 x 5.5 x 7.5) = 5.70 m
   B. Average 5.83 m
   C. 7.5 m
   D. 4.5 m
   Answer: A. Geometric mean for a transposed line. (Key point: D_eq)

2. Inductance per phase per metre is:
   A. 2e-7 ln(D_eq / r)
   B. 2e-7 ln(r' / D_eq)
   C. 2e-7 ln(D_eq / r') with r' = 0.7788r
   D. 2e-7 ln(D_eq) r'
   Answer: C. r' accounts for internal flux linkage. (Key point: Formula)

## Related in Power System Analysis I

- [Inductance and capacitance of 4-conductor bundle line](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3Aquad-bundle-220kv-l-c) — Power System Analysis I, chapter 4
- [Transposition and inductance of transposed line](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3Atransposition-inductance-derivation) — Power System Analysis I, chapter 4, asked 2×
- [Inductance of twin-bundle line, 16 mm radius](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3Atwin-bundle-150km-16mm) — Power System Analysis I, chapter 4, asked 3×
- [Inductance of composite-conductor single-phase line](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3Asingle-phase-composite-conductors) — Power System Analysis I, chapter 4
- [330 kV quad-bundle line: inductance and charging](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3Aquad-bundle-330kv-6m) — Power System Analysis I, chapter 4
- [Charging current of 60 Hz horizontal 132 kV line](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3Ahorizontal-60hz-132kv-charging) — Power System Analysis I, chapter 4

## Related in other subjects

- [Inductance of 420 kV line, transposed and untransposed](https://www.bctengineer.com/question.md?key=semester_8%2Fhigh_voltage_engineering%3Ainductance-420kv-transposed) — High Voltage Engineering, chapter 5
- [6° phase shift per 100 km of lossless line](https://www.bctengineer.com/question.md?key=semester_8%2Fhigh_voltage_engineering%3Aphase-shift-6-degree-100km) — High Voltage Engineering, chapter 3
- [Minimum spacing for 30 mm conductors (m = 0.95)](https://www.bctengineer.com/question.md?key=semester_8%2Fhigh_voltage_engineering%3Acorona-spacing-30mm-0-95) — High Voltage Engineering, chapter 5, asked 4×
- [Inductance matrix of 500 kV bundled line](https://www.bctengineer.com/question.md?key=semester_8%2Fhigh_voltage_engineering%3Ainductance-matrix-500kv) — High Voltage Engineering, chapter 5, asked 3×