# Zero regulation for 40 MW leading load

Power System Analysis I · Chapter 6: Performance Analysis

- Asked in: 2071 Bhadra, 6 marks
- Video: [Condition for Maximum/Zero Voltage Regulation | Analysis of Objective-2 | GATE/ESE/ISRO/BARC](https://www.youtube.com/watch?v=VsmL4LIlY2E) — ELECTRICAL ENGINEERING CONCEPTS
- Answer checked by Claude Opus 5.5 (high effort) on 2026-10-14
- Page: https://www.bctengineer.com/q/semester_4/power_system_analysis_i/zero-regulation-40mw-leading
- Whole chapter: https://www.bctengineer.com/md/semester_4/power_system_analysis_i/chapter-6

## Question

A 50 Hz, 3-phase, 132 kV overhead line is supplying a load of 40 MW at 0.9 p.f. leading. The line has series impedance of 12 + j36 Ω/phase. How can the voltage regulation of the line be made zero?

## Short answer

The present regulation is −0.78%. To make it zero, absorb approximately 3.93 MVAr using a shunt reactor at the receiving end, bringing the net power factor to about 0.933 leading.

## Answer

Short line: $Z = 12 + j36\ \Omega$, $V_R$ = 132 kV, load 40 MW at 0.9 pf **leading**.

#### Present regulation
$$
\begin{aligned}
I &= \frac{40\times10^6}{\sqrt3\times132\,000\times0.9} = 194.39\ \text{A},\quad \phi = 25.84^\circ\ \text{lead} \\
V_S &= 76\,210.2 + 194.39\angle25.84^\circ\,(12 + j36) \\
&= 75\,613.9\angle5.55^\circ\ \text{V} \Rightarrow 130.97\ \text{kV (line)} \\
\%VR &= \frac{130.97 - 132}{132}\times100 = -0.78\%
\end{aligned}
$$
The regulation is **negative**: the load is too leading, so the receiving-end voltage is higher than the sending-end voltage.

#### Condition for zero regulation
Approximate condition: $R\cos\phi - X\sin\phi = 0$, i.e. $\tan\phi = R/X = 1/3$, giving pf $= 0.949$ leading.

Exact condition $|V_S| = |V_R| = 132$ kV with $P$ = 40 MW (line kV, MW, MVAr):
$$
(V_R^2 + RP + XQ)^2 + (XP - RQ)^2 = V_R^4
$$
$$
(17\,424 + 480 + 36Q)^2 + (1440 - 12Q)^2 = 17\,424^2
$$
Taking the root nearer zero:
$$
Q = -15.44\ \text{MVAr}\quad(\text{pf} = 0.933\ \text{leading})
$$

#### How to make it zero
The load now supplies $Q_L = -40\tan25.84^\circ = -19.37$ MVAr (leading). The leading VAr must be reduced to 15.44 MVAr, so connect a **shunt reactor** at the receiving end of
$$
Q_{reactor} = 19.37 - 15.44 = 3.93\ \text{MVAr}
$$
$$
L_{ph} = \frac{V_L^2}{\omega Q} = \frac{132\,000^2}{314.16\times3.93\times10^6} = 14.1\ \text{H (star)}
$$
(Alternatively, reduce the excitation of a synchronous load/condenser so that it draws less leading current.)

**Answer: Regulation is now −0.78 %. It is made zero by absorbing ≈ 3.9 MVAr with a shunt reactor at the receiving end, bringing the net pf to ≈ 0.933 leading.**

## Check yourself

The answer's key points as multiple-choice questions, with the correct option and why.

1. Why is the regulation -0.78 % negative?
   A. Load is lagging
   B. Line has high resistance
   C. V_S is zero
   D. Load is too leading so V_R exceeds V_S
   Answer: D. A strongly leading load raises voltage at receiving end above sending voltage. (Key point: Present regulation)

2. What is added to make regulation zero?
   A. Shunt capacitor
   B. Shunt reactor to absorb some leading VAr
   C. Series resistor
   D. Larger conductor
   Answer: B. The load is too leading, so VAr must be absorbed. (Key point: Remedy)

3. How much leading Q is allowed for zero regulation, and rating of reactor?
   A. Q = -40; reactor 20.6 MVAr
   B. Q = -15.44 MVAr (pf 0.933 leading); reactor about 3.93 MVAr
   C. Q = -19.37; reactor 0
   D. Q = 0; reactor 19.37 MVAr
   Answer: B. Solving |V_S| = |V_R| gives Q = -15.44; load supplies 19.37, difference 3.93 MVAr. (Key point: Exact condition)

4. What does the approximate condition give?
   A. pf = 1
   B. pf = 0.5
   C. tan(phi) = R/X = 1/3, pf = 0.949 leading
   D. pf = 0.9 lagging
   Answer: C. R cos(phi) = X sin(phi) gives tan(phi) = 12/36. (Key point: Approximate method)

## Close variants set in other exams

- [33 kV, 12 MW leading load: efficiency, zero regulation](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3A33kv-12mw-leading-efficiency) — Power System Analysis I, chapter 6, asked 2×

## Related in Power System Analysis I

- [Efficiency at 0.995 leading pf and zero regulation](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3Aleading-pf-efficiency-zero-regulation) — Power System Analysis I, chapter 6
- [Capacitor for zero regulation, 70 km 220 kV line](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3A70km-220kv-zero-regulation-capacitor) — Power System Analysis I, chapter 6
- [70 km, 40 MW line: regulation and zero-regulation pf](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3A70km-40mw-regulation) — Power System Analysis I, chapter 6
- [12 km 33 kV line: losses, zero-regulation capacitor](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3A12km-33kv-losses-zero-regulation) — Power System Analysis I, chapter 6
- [33 kV, 15 MW line: efficiency and regulation](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3A33kv-15mw-efficiency-regulation) — Power System Analysis I, chapter 6
- [12 km line at 32.5 kV: regulation and capacitor](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3A12km-32-5kv-regulation-capacitor) — Power System Analysis I, chapter 6

## Related in other subjects

- [Conductor selection, 100 MW 70 km 132 kV](https://www.bctengineer.com/question.md?key=semester_8%2Ftransmission_and_distribution_system_design%3Aconductor-selection-100mw-70km-132kv) — Transmission and Distribution System Design, chapter 4
- [Currents and efficiency of 132/11 kV transformer at 5 MW](https://www.bctengineer.com/question.md?key=semester_4%2Felectrical_machines_i%3Astar-delta-132-11kv-5mw-currents) — Electrical Machines I, chapter 2, asked 3×
- [Currents and efficiency of 132/11 kV transformer at 4 MW](https://www.bctengineer.com/question.md?key=semester_4%2Felectrical_machines_i%3Astar-delta-132-11kv-4mw-currents) — Electrical Machines I, chapter 2, asked 3×