# Distribution transformer efficiency and number of tubes

Electric Machine Design · Chapter 3: Transformer Design

- Asked in: 2078 Kartik, 3+3 marks; 2070 Chaitra, 4+4 marks (asked 2 times)
- Video: [5EE4-05 Lecture 5 - Unit 2 - EMD - Design for minimum losses or maximum efficiency - Gauri Shankar](https://www.youtube.com/watch?v=6Rigbbw2ah8) — MITRC LECTURE
- Answer checked by Claude Sonnet 5.5 on 2026-10-14
- Page: https://www.bctengineer.com/q/semester_5/electric_machine_design/distribution-efficiency-cooling-tubes
- Whole chapter: https://www.bctengineer.com/md/semester_5/electric_machine_design/chapter-3

## Question

Why are distribution transformers designed to have maximum efficiency at loads much lower than full load? Derive the expression for calculating the number of tubes to be provided in a transformer tank.

## Short answer

Distribution transformers are designed for maximum all-day efficiency because they are energized 24 h with varying load; iron loss is constant, copper loss varies with load square. Placing maximum efficiency at 50–70% load reduces total energy losses. Required cooling tubes: n_t = (1/(8.8πd_t l_t))[(P_i+P_c)/θ – 12.5S_t] where d_t,l_t are tube diameter and length, S_t plain wall area, θ permissible oil temperature rise.

## Answer

#### Why maximum efficiency at less than full load
A distribution transformer stays energised for 24 hours but its load changes through the day and is often light (night hours). So the important figure is **all-day (energy) efficiency**:

$$
\eta_{all\ day} = \frac{\text{kWh output in 24 h}}{\text{kWh output} + \text{kWh losses in 24 h}}
$$

- Iron loss $P_i$ occurs for all 24 hours, whatever the load.
- Copper loss $P_c$ occurs only in proportion to (load)², and is large only for a few peak hours.

Maximum efficiency occurs when copper loss = iron loss, i.e. at load fraction $x = \sqrt{P_i/P_{c,FL}}$. By keeping $P_i$ small (lower $B_m$, good-quality steel) the maximum efficiency is placed at about 50–70% of full load, where the transformer runs most of the time. This minimises total energy loss in a day.

#### Number of cooling tubes
Let
- $P_i + P_c$ = total full-load loss (W)
- $S_t$ = dissipating surface of plain tank walls (m²)
- $\theta$ = permissible mean temperature rise of oil (°C)

A plain tank wall dissipates by radiation ≈ 6 W/m²°C and by convection ≈ 6.5 W/m²°C, total 12.5 W/m²°C:

$$
\theta = \frac{P_i + P_c}{12.5\,S_t}
$$

If this $\theta$ is too high, tubes are added. Let the tube area be $xS_t$. Tubes do not add to radiation much (they screen each other), but they improve convection by about 35%:

$$
6.5 \times 1.35 \approx 8.8\ \text{W/m}^2{}^\circ\text{C}
$$

Heat dissipated with tubes:

$$
\begin{aligned}
P_i + P_c &= \theta\left[12.5\,S_t + 8.8\,xS_t\right]\\
xS_t &= \frac{1}{8.8}\left(\frac{P_i + P_c}{\theta} - 12.5\,S_t\right)
\end{aligned}
$$

If each tube has diameter $d_t$ and length $l_t$, its surface is $\pi d_tl_t$, so

$$
n_t = \frac{xS_t}{\pi d_tl_t} = \frac{1}{8.8\,\pi d_tl_t}\left(\frac{P_i + P_c}{\theta} - 12.5\,S_t\right)
$$

Round $n_t$ up to the next whole number. Usually $\theta$ = 35 °C (mean oil rise), tube diameter 50 mm and spacing 75 mm.

## Check yourself

The answer's key points as multiple-choice questions, with the correct option and why.

1. Why is maximum efficiency of a distribution transformer placed at below full load?
   A. Copper loss is zero at night
   B. Full-load efficiency cannot be calculated
   C. Iron loss exists all 24 h while load is mostly light, so iron loss is kept small
   D. Regulation is better at low load
   Answer: C. All-day efficiency is improved by low iron loss, which is present all day. (Key point: Why low-load maximum efficiency)

2. Maximum efficiency occurs at load fraction x equal to:
   A. Pc,FL / Pi
   B. sqrt(Pi / Pc,FL)
   C. Pi x Pc,FL
   D. (Pi / Pc,FL)^2
   Answer: B. Copper loss x^2 Pc,FL equals iron loss Pi when x = sqrt(Pi/Pc,FL). (Key point: Condition for maximum efficiency)

3. How do tubes mainly improve heat dissipation in the derivation?
   A. They raise radiation by 35%
   B. They improve convection by about 35% (6.5 x 1.35 = 8.8 W/m2 C)
   C. They remove the tank walls
   D. They reduce iron loss
   Answer: B. Tubes screen each other so radiation gain is negligible, but convection improves about 35%. (Key point: Tube effect on dissipation)

4. The number of tubes is:
   A. nt = (Pi+Pc)/(12.5 St theta)
   B. nt = 8.8 pi dt lt/(Pi+Pc)
   C. nt = theta St/(Pi+Pc)
   D. nt = (1/8.8 pi dt lt)((Pi+Pc)/theta - 12.5 St)
   Answer: D. Tube area from the heat balance divided by the area of one tube, pi dt lt. (Key point: Tube count expression)

## Related in Electric Machine Design

- [Reasons: distribution efficiency and LV placement](https://www.bctengineer.com/question.md?key=semester_5%2Felectric_machine_design%3Adistribution-efficiency-lv-placement) — Electric Machine Design, chapter 3
- [Design: 150 kVA 11000/440 V transformer with tubes](https://www.bctengineer.com/question.md?key=semester_5%2Felectric_machine_design%3Adesign-150kva-11000-440-tubes) — Electric Machine Design, chapter 3
- [Design: 500 kVA single phase transformer with tubes](https://www.bctengineer.com/question.md?key=semester_5%2Felectric_machine_design%3Adesign-500kva-single-phase-tubes) — Electric Machine Design, chapter 3, asked 2×
- [Temperature rise and tubes for 500 kVA transformer](https://www.bctengineer.com/question.md?key=semester_5%2Felectric_machine_design%3Atank-tubes-500kva-single-phase) — Electric Machine Design, chapter 3, asked 2×
- [Design: 25 kVA transformer frame, regulation, tubes](https://www.bctengineer.com/question.md?key=semester_5%2Felectric_machine_design%3Adesign-25kva-cooling-tubes) — Electric Machine Design, chapter 3, asked 2×
- [Design: 25 kVA 11000/433 V distribution transformer](https://www.bctengineer.com/question.md?key=semester_5%2Felectric_machine_design%3Adesign-25kva-11000-433) — Electric Machine Design, chapter 3

## Related in other subjects

- [500 kVA transformer efficiency full/half load](https://www.bctengineer.com/question.md?key=semester_4%2Felectrical_machine%3Atransformer-500kva-efficiency-full-half) — Electrical Machine, chapter 2
- [Full-load efficiency of 500 kVA transformer](https://www.bctengineer.com/question.md?key=semester_4%2Felectrical_machines_i%3A500kva-90pc-half-load-full-load) — Electrical Machines I, chapter 2
- [Full-load and half-load efficiency of 100 kVA transformer](https://www.bctengineer.com/question.md?key=semester_4%2Felectrical_machines_i%3A100kva-1200w-960w-efficiency) — Electrical Machines I, chapter 2
- [100 kVA transformer efficiency at full and half load](https://www.bctengineer.com/question.md?key=semester_4%2Felectrical_machines%3Atf-100kva-efficiency-full-half-load) — Electrical Machines, chapter 2