# Power transfer and pf of motor on infinite bus

Electric Machines II · Chapter 2: Three Phase Synchronous Motor

- Asked in: 2071 Shrawan, 6 marks
- Video: [EM || Example 6.3 (4th ed) || Synchronous Motors || The infinite bus](https://www.youtube.com/watch?v=F7bq8JR0zVk) — Electrical Engineering Academy
- Answer checked by Claude Sonnet 5.5 on 2026-10-14
- Page: https://www.bctengineer.com/q/semester_5/electric_machines_ii/motor-infinite-bus-power-transfer
- Whole chapter: https://www.bctengineer.com/md/semester_5/electric_machines_ii/chapter-2

## Question

A 3 phase, 10 MVA, 2300 V, 60 Hz synchronous motor has Xs = 0.9 pu and negligible stator resistance. The motor is connected to infinite bus. If terminal voltage, Vt = 2300∠0 V and excitation emf Ef = 3450∠120 V [printed "3450V<120"]. Determine power transfer and power factor of machine. Also draw phasor diagram.

## Short answer

With Ef = 1.5∠120° pu, power transfer = 1.443 pu = 14.43 MW delivered to bus (generating); power factor = 0.596 leading. If Ef angle is -120°, motor absorbs 14.43 MW at 0.596 lagging.

## Answer

**Reading of data:** $V_t = 2300$ V and $E_f = 3450$ V are taken as line values (the rating is 2300 V line), with $E_f$ at $+120^\circ$ as printed. Work in per unit on 10 MVA, 2300 V.

$$
\begin{aligned}
V_t &= \frac{2300}{2300} = 1\angle0^\circ\ \text{pu},\quad E_f = \frac{3450}{2300}\angle120^\circ = 1.5\angle120^\circ = -0.75 + j1.299\ \text{pu} \\
Z_{base} &= \frac{2300^2}{10\times10^6} = 0.529\ \Omega,\quad X_s = 0.9 \times 0.529 = 0.4761\ \Omega \\
I_{base} &= \frac{10\times10^6}{\sqrt3 \times 2300} = 2510.2\ \text{A}
\end{aligned}
$$

#### Power transfer

$$
P = \frac{V_tE_f}{X_s}\sin\delta = \frac{1 \times 1.5}{0.9}\sin120^\circ = 1.4434\ \text{pu} = 14.43\ \text{MW}
$$

#### Current and power factor

Using the motor equation $\vec V_t = \vec E_f + jX_s\vec I_a$:

$$
\begin{aligned}
\vec I_a &= \frac{\vec V_t - \vec E_f}{jX_s} = \frac{1.75 - j1.299}{j0.9} = -1.4434 - j1.9444 \\
&= 2.4216\angle -126.59^\circ\ \text{pu} = 6079\ \text{A} \\
\vec S &= \vec V_t\vec I_a^{*} = -1.4434 + j1.9444\ \text{pu}
\end{aligned}
$$

The real part is **negative**: since $E_f$ **leads** $V_t$, the machine is not taking power; it is **delivering 14.43 MW** to the bus, i.e. acting as a generator. Taking the generated current $-\vec I_a = 2.4216\angle 53.41^\circ$ pu, it leads $V_t$ by $53.41^\circ$:

$$
\text{pf} = \cos53.41^\circ = 0.596\ \text{leading}
$$

```text
        Ef (1.5 pu)
          \
           \ at 120 deg from Vt
            \
             O-----------> Vt (1.0 pu)
              \
               \  Ia (motor convention)
                v at -126.6 deg
 jXs.Ia = Vt - Ef joins tip of Ef to tip of Vt
 Ia(gen) = -Ia leads Vt by 53.4 deg
```

**Note:** with $\delta = 120^\circ$ the machine is beyond the steady-state limit ($90^\circ$) and the current (2.42 pu) is far above rating, so this point is not a stable working point. If the angle was meant as $-120^\circ$ (motor action, $E_f$ lagging), the same magnitudes result: the motor **absorbs 14.43 MW** at a pf of **0.596 lagging**.

**Answer:** Power transferred $= 1.443$ pu $= 14.43$ MW; power factor $= 0.596$ (leading as printed, i.e. generating; lagging if $E_f$ is at $-120^\circ$).

## Check yourself

The answer's key points as multiple-choice questions, with the correct option and why.

1. Which formula gives the power transferred here?
   A. P = Vt Ef sin(delta)/Xs = 1.5/0.9 x sin 120 = 1.443 pu
   B. P = Vt Ef cos(delta)/Xs
   C. P = Vt^2/Xs
   D. P = 3 Vt Ia
   Answer: A. P = (1 x 1.5/0.9) sin120 degrees = 1.443 pu = 14.43 MW. (Key point: Power transfer formula)

2. Because Ef leads Vt (delta = +120 degrees), what is the machine doing?
   A. Absorbing 14.43 MW as a motor
   B. Delivering power to the bus, acting as a generator
   C. Running as a synchronous condenser with zero power
   D. Supplying no reactive power
   Answer: B. The real part of S = Vt Ia* is negative with the motor convention, so power flows to the bus. (Key point: Direction of power flow)

3. Why is this not a stable working point?
   A. Because Vt is too large
   B. Because delta = 120 degrees exceeds the 90 degree steady-state limit and the current (2.42 pu) is far above rating
   C. Because Xs is zero
   D. Because the frequency is 60 Hz
   Answer: B. Beyond 90 degrees the steady-state stability limit is passed. (Key point: Stability)

## Related in Electric Machines II

- [Generator on infinite bus with 15% excitation rise](https://www.bctengineer.com/question.md?key=semester_5%2Felectric_machines_ii%3Agenerator-infinite-bus-excitation-15) — Electric Machines II, chapter 1
- [25 MVA salient pole motor maximum power](https://www.bctengineer.com/question.md?key=semester_5%2Felectric_machines_ii%3Asalient-motor-25mva-max-power) — Electric Machines II, chapter 2, asked 3×
- [30 MVA salient pole motor maximum power](https://www.bctengineer.com/question.md?key=semester_5%2Felectric_machines_ii%3Asalient-motor-30mva-max-power) — Electric Machines II, chapter 2, asked 3×
- [20 MVA salient pole motor maximum power](https://www.bctengineer.com/question.md?key=semester_5%2Felectric_machines_ii%3Asalient-motor-20mva-max-power) — Electric Machines II, chapter 2, asked 3×
- [Current, pf, power and efficiency of 3.3 kV motor](https://www.bctengineer.com/question.md?key=semester_5%2Felectric_machines_ii%3Amotor-3-3kv-efficiency) — Electric Machines II, chapter 2
- [Salient pole motor excitation and reluctance power](https://www.bctengineer.com/question.md?key=semester_5%2Felectric_machines_ii%3Asalient-motor-50mva-pu) — Electric Machines II, chapter 2

## Related in other subjects

- [Sync generator terminal voltage, leading pf](https://www.bctengineer.com/question.md?key=semester_4%2Felectrical_machine%3Async-generator-1200kva-leading-voltage) — Electrical Machine, chapter 6, asked 2×
- [Critical clearing angle/time, fault at infinite bus](https://www.bctengineer.com/question.md?key=semester_5%2Fpower_system_analysis_ii%3Acritical-clearing-infinite-bus-h5) — Power System Analysis II, chapter 6
- [Generator reactive power at constant terminal voltage](https://www.bctengineer.com/question.md?key=semester_5%2Fpower_system_analysis_ii%3Agenerator-reactive-power-infinite-bus) — Power System Analysis II, chapter 1
- [5 MVA alternator: regulation and pf for zero regulation](https://www.bctengineer.com/question.md?key=semester_4%2Felectrical_machines%3Aalt-5mva-11kv-regulation-zero) — Electrical Machines, chapter 6