# Critical clearing angle/time, fault at infinite bus

Power System Analysis II · Chapter 6: Power System Stability

- Asked in: 2082 Baishakh, 8 marks
- Video: [Critical Clearing Angle | Power system Stability analysis | Transient Stability](https://www.youtube.com/watch?v=9NS0Bv_nyOk) — Simple n Easy Learning
- Answer checked by Claude Sonnet 5.5 on 2026-10-14
- Page: https://www.bctengineer.com/q/semester_5/power_system_analysis_ii/critical-clearing-infinite-bus-h5
- Whole chapter: https://www.bctengineer.com/md/semester_5/power_system_analysis_ii/chapter-6

## Question

A 50 Hz synchronous generator connected to infinite bus as shown in the figure below has a H constant of 5 p.u. Under normal condition (just before disturbance), the generator injects 1 p.u. real power to the infinite bus with generator excitation voltage of 1.1 p.u. and infinite bus voltage 1 p.u. Suddenly a 3-phase bolted fault occurs at the infinite bus. Compute the critical fault clearing angle and critical fault clearing time for system to be transient stable. [Figure: generator X = 10%, transformer X = 5%, two parallel lines each X = 0.8 pu, to the infinite bus]

## Short answer

Pre-fault Pmax=2 pu, delta0=30°. During fault Pe=0. Equal area gives delta_cr=79.56°. Then t_cr = sqrt(2H(delta_cr-delta0)/(pi f Pm)) = 0.235 s.

## Answer

**Data:** $H = 5$ MJ/MVA, $f = 50$ Hz, $P_m = 1$ pu, $E = 1.1$ pu, $V = 1$ pu, $X_g = 0.10$, $X_T = 0.05$, two parallel lines of $0.8$ pu each.

**Assumption:** the fault is a temporary fault at the infinite bus. After it is cleared, the network is the same as before the fault.

#### Step 1: Pre-fault power-angle curve

$$
\begin{aligned}
X_1 &= 0.10 + 0.05 + \frac{0.8}{2} = 0.55\ \text{pu} \\
P_{max1} &= \frac{EV}{X_1} = \frac{1.1\times 1}{0.55} = 2.0\ \text{pu} \\
\delta_0 &= \sin^{-1}\frac{1}{2.0} = 30^\circ = 0.5236\ \text{rad}
\end{aligned}
$$

#### Step 2: During and after the fault

A bolted fault at the infinite bus makes $V = 0$, so $P_{max2} = 0$ and $P_e = 0$ during the fault.

After clearing, $P_{max3} = P_{max1} = 2.0$ pu. Then

$$
\delta_{max} = 180^\circ - \delta_0 = 150^\circ = 2.618\ \text{rad}
$$

#### Step 3: Critical clearing angle (equal areas)

$$
\begin{aligned}
A_1 &= P_m(\delta_{cr}-\delta_0) \\
A_2 &= \int_{\delta_{cr}}^{\delta_{max}}(P_{max}\sin\delta - P_m)\,d\delta
\end{aligned}
$$

Setting $A_1 = A_2$ gives

$$
\begin{aligned}
\cos\delta_{cr} &= (\pi - 2\delta_0)\sin\delta_0 - \cos\delta_0 \\
&= (3.1416 - 1.0472)(0.5) - 0.8660 \\
&= 0.1812 \\
\delta_{cr} &= 79.56^\circ = 1.3886\ \text{rad}
\end{aligned}
$$

#### Step 4: Critical clearing time

With $P_e = 0$ during the fault, the swing equation is $\dfrac{H}{\pi f}\dfrac{d^2\delta}{dt^2} = P_m$. Integrating twice:

$$
\delta = \delta_0 + \frac{\pi f P_m}{2H}t^2 \;\Rightarrow\; t_{cr} = \sqrt{\frac{2H(\delta_{cr}-\delta_0)}{\pi f P_m}}
$$

$$
t_{cr} = \sqrt{\frac{2\times 5\times(1.3886-0.5236)}{\pi\times 50\times 1}} = \sqrt{0.05507} = 0.2347\ \text{s}
$$

**Answer: Critical clearing angle $\delta_{cr} = 79.56^\circ$; critical clearing time $t_{cr} = 0.235$ s (about 11.7 cycles).**

## Check yourself

The answer's key points as multiple-choice questions, with the correct option and why.

1. What are Pmax1 and delta0 for E = 1.1, V = 1, X = 0.55 and Pm = 1 pu?
   A. Pmax1 = 2.0 pu, delta0 = 30 degrees
   B. Pmax1 = 1.0 pu, delta0 = 90 degrees
   C. Pmax1 = 2.0 pu, delta0 = 60 degrees
   D. Pmax1 = 0.55 pu, delta0 = 30 degrees
   Answer: A. Pmax1 = 1.1/0.55 = 2.0 pu and delta0 = asin(1/2) = 30 degrees. (Key point: Pre-fault power angle)

2. Why is Pe = 0 during a bolted fault at the infinite bus?
   A. The generator trips
   B. V becomes 0, so Pmax2 = EV/X = 0
   C. The reactance becomes infinite
   D. Pm becomes zero
   Answer: B. The bus voltage V is zero, so no power is transferred during the fault. (Key point: Fault at infinite bus)

3. With Pe = 0 during the fault, the critical clearing time is:
   A. sqrt(pi f Pm / (2H(dcr - d0)))
   B. 2H(dcr - d0)/(pi f Pm)
   C. sqrt(2H(dcr - d0)/(pi f Pm))
   D. (dcr - d0) / (pi f)
   Answer: C. Integrating (H/pi f) d2delta/dt2 = Pm twice gives delta = d0 + (pi f Pm/2H) t^2. (Key point: Critical clearing time formula)

## Related in Power System Analysis II

- [Critical clearing, fault at infinite bus, H = 6](https://www.bctengineer.com/question.md?key=semester_5%2Fpower_system_analysis_ii%3Acritical-clearing-fault-infinite-bus-h6) — Power System Analysis II, chapter 6
- [Critical clearing angle and time, H = 2](https://www.bctengineer.com/question.md?key=semester_5%2Fpower_system_analysis_ii%3Acritical-clearing-h2-parallel-lines) — Power System Analysis II, chapter 6
- [Critical clearing time and angle, fault at P](https://www.bctengineer.com/question.md?key=semester_5%2Fpower_system_analysis_ii%3Acritical-clearing-time-point-p-h5) — Power System Analysis II, chapter 6
- [Critical clearing for temporary sending-end fault](https://www.bctengineer.com/question.md?key=semester_5%2Fpower_system_analysis_ii%3Acritical-clearing-temporary-fault-new) — Power System Analysis II, chapter 6
- [Initial rotor angle and critical clearing angle](https://www.bctengineer.com/question.md?key=semester_5%2Fpower_system_analysis_ii%3Arotor-angle-critical-clearing-2076) — Power System Analysis II, chapter 6
- [Critical clearing angle, Pmax 2, 0.5, 1.5](https://www.bctengineer.com/question.md?key=semester_5%2Fpower_system_analysis_ii%3Acritical-clearing-angle-pmax-two) — Power System Analysis II, chapter 6

## Related in other subjects

- [Generator on infinite bus with 15% excitation rise](https://www.bctengineer.com/question.md?key=semester_5%2Felectric_machines_ii%3Agenerator-infinite-bus-excitation-15) — Electric Machines II, chapter 1
- [Why infinite bus frequency and voltage stay constant](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3Ainfinite-bus-constant-frequency) — Power System Analysis I, chapter 1
- [Power transfer and pf of motor on infinite bus](https://www.bctengineer.com/question.md?key=semester_5%2Felectric_machines_ii%3Amotor-infinite-bus-power-transfer) — Electric Machines II, chapter 2
- [Time of critical DO deficit, 50 l/s city](https://www.bctengineer.com/question.md?key=semester_6%2Fsanitary_engineering%3Acritical-do-time-city-50ls) — Sanitary Engineering, chapter 6, asked 2×