# Fault level at end of two 200 km lines

Power System Analysis II · Chapter 3: Power System Fault Calculation

- Asked in: 2082 Baishakh, 8 marks; 2068 Chaitra (asked 2 times)
- Video: [Fault Analysis by Thevenin theorem | Solved Problem - 4 | Numericals | Power System Analysis | PSA](https://www.youtube.com/watch?v=dFepZEBPrr8) — Simple n Easy Learning
- Answer checked by Claude Sonnet 5.5 on 2026-10-14
- Page: https://www.bctengineer.com/q/semester_5/power_system_analysis_ii/fault-two-stations-132kv-200km
- Whole chapter: https://www.bctengineer.com/md/semester_5/power_system_analysis_ii/chapter-3

## Question

Figure below shows generating stations feeding a 132-kV system. Determine the total fault current and fault MVA level for a 3-phase to ground bolted fault at the point marked by F. Consider the line is 200 km long. [Figure: G1 100 MVA, 11 kV, X = 15% feeding transformer T1 100 MVA, 11/132 kV, X = 10%; G2 50 MVA, 11 kV, X = 10% feeding transformer T2 50 MVA, 11/132 kV, X = 8%; both transformers feed the 132 kV bus, from which two parallel lines L1 and L2, each X = 0.2 Ω/phase/km and 200 km long, run to the fault point F]

## Short answer

On 100 MVA base: G1 0.15, T1 0.10, G2 0.20, T2 0.16, parallel lines 0.1148 pu. Thevenin reactance at F = 0.2623 pu. Fault current = 1.667 kA, fault MVA = 381.2 MVA.

## Answer

A bolted three-phase fault is balanced, so only the positive-sequence reactance diagram is needed. Base: 100 MVA, 11 kV on the generator side and 132 kV on the line side. Pre-fault voltage is taken as 1.0 pu and pre-fault load current is neglected (usual assumption for fault level calculation). As described, both transformers feed a common 132 kV bus, and two parallel 200 km lines run from that bus to F.

#### Per-unit reactances
$X_{new} = X_{old}\dfrac{S_{new}}{S_{old}}$ (voltage bases match the ratings):

| Element | Rating | Given | On 100 MVA (pu) |
|---|---|---|---|
| G1 | 100 MVA | 15% | 0.15 |
| T1 | 100 MVA | 10% | 0.10 |
| G2 | 50 MVA | 10% | $0.10 \times 2 = 0.20$ |
| T2 | 50 MVA | 8% | $0.08 \times 2 = 0.16$ |

Line: $X_L = 0.2 \times 200 = 40\ \Omega$ per line.

$$
\begin{aligned}
Z_{base} &= \frac{132^2}{100} = 174.24\ \Omega \\
X_L &= \frac{40}{174.24} = 0.2296\ \text{pu}
\end{aligned}
$$

#### Reactance diagram
```text
 E=1 --[G1 j0.15]--[T1 j0.10]--+
                               |   +--[L1]--+
                            132 kV |        |-- F
                               |   +--[L2]--+
 E=1 --[G2 j0.20]--[T2 j0.16]--+
```

#### Thevenin reactance at F
$$
\begin{aligned}
X_{G1T1} &= 0.15 + 0.10 = 0.25 \\
X_{G2T2} &= 0.20 + 0.16 = 0.36 \\
X_{gen} &= \frac{0.25 \times 0.36}{0.25 + 0.36} = 0.1475 \\
X_{lines} &= \frac{0.2296}{2} = 0.1148 \\
X_{th} &= 0.1475 + 0.1148 = 0.2623\ \text{pu}
\end{aligned}
$$

#### Fault current and fault MVA
$$
\begin{aligned}
I_f &= \frac{1}{X_{th}} = \frac{1}{0.2623} = 3.8121\ \text{pu} \\
I_{base} &= \frac{100 \times 10^6}{\sqrt{3} \times 132 \times 10^3} = 437.39\ \text{A} \\
I_f &= 3.8121 \times 437.39 = 1667.3\ \text{A} \\
\text{Fault MVA} &= \frac{S_{base}}{X_{th}} = \frac{100}{0.2623} = 381.21\ \text{MVA}
\end{aligned}
$$

**Answer:** total fault current $\approx 1.667$ kA (at 132 kV), fault level $\approx 381.2$ MVA.

## Check yourself

The answer's key points as multiple-choice questions, with the correct option and why.

1. How is G2's 10% on 50 MVA expressed on a 100 MVA base?
   A. 0.20 pu
   B. 0.05 pu
   C. 0.10 pu
   D. 0.40 pu
   Answer: A. X_new = X_old x S_new/S_old = 0.10 x 100/50 = 0.20 pu. (Key point: Per-unit base change)

2. How is the Thevenin reactance at F built up?
   A. (G1+T1) parallel (G2+T2), in series with the two parallel lines
   B. All reactances added in series
   C. All reactances in parallel
   D. G1 and G2 in series with each line separately
   Answer: A. 0.25 || 0.36 = 0.1475 plus 0.2296/2 = 0.1148 gives X_th = 0.2623 pu. (Key point: Thevenin reactance)

3. A 40 ohm line on a 132 kV, 100 MVA base is how many pu?
   A. 0.2296
   B. 0.4
   C. 4.35
   D. 0.0574
   Answer: A. Z_base = 132^2/100 = 174.24 ohm, so 40/174.24 = 0.2296 pu. (Key point: Line reactance in pu)

4. What is the fault level obtained?
   A. About 381 MVA, i.e. 100/X_th
   B. About 262 MVA
   C. About 38 MVA
   D. About 1667 MVA
   Answer: A. Fault MVA = S_base/X_th = 100/0.2623 = 381.2 MVA, with I_f = 3.81 pu = 1.667 kA. (Key point: Fault MVA)

## Related in Power System Analysis II

- [Fault at receiving end of 132 kV lines](https://www.bctengineer.com/question.md?key=semester_5%2Fpower_system_analysis_ii%3Afault-132kv-receiving-end-2071) — Power System Analysis II, chapter 3
- [Fault at receiving end of 220 kV lines](https://www.bctengineer.com/question.md?key=semester_5%2Fpower_system_analysis_ii%3Afault-220kv-two-generators) — Power System Analysis II, chapter 3
- [Fault MVA at bus 5 with inductive lines](https://www.bctengineer.com/question.md?key=semester_5%2Fpower_system_analysis_ii%3Afault-mva-bus5-mh-lines) — Power System Analysis II, chapter 3, asked 2×
- [Fault at far end of 33 kV line](https://www.bctengineer.com/question.md?key=semester_5%2Fpower_system_analysis_ii%3Afault-far-end-33kv-line) — Power System Analysis II, chapter 3
- [Fault at generator terminal feeding motor](https://www.bctengineer.com/question.md?key=semester_5%2Fpower_system_analysis_ii%3Afault-generator-terminal-motor-new) — Power System Analysis II, chapter 3
- [Generator-reactor system fault MVA](https://www.bctengineer.com/question.md?key=semester_5%2Fpower_system_analysis_ii%3Agenerator-reactor-fault-mva) — Power System Analysis II, chapter 3

## Related in other subjects

- [Nominal-T 100 km line, 50 MVA at 132 kV](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3Anominal-t-100km-50mva) — Power System Analysis I, chapter 6
- [Fault level: two 25 MVA generators, 50% reduction](https://www.bctengineer.com/question.md?key=semester_7%2Fpower_plant_equipment%3Afault-two-25mva-50-percent) — Power Plant Equipment, chapter 4
- [Fault level: two 50 MVA generators, 50% reduction](https://www.bctengineer.com/question.md?key=semester_7%2Fpower_plant_equipment%3Afault-two-50mva-50-percent) — Power Plant Equipment, chapter 4
- [Fault level: two 40 MVA generators, 2 Ω feeder](https://www.bctengineer.com/question.md?key=semester_7%2Fpower_plant_equipment%3Afault-two-40mva-2-ohm-feeder) — Power Plant Equipment, chapter 4, asked 5×