title: "Generator-reactor system fault MVA"
subject: "Power System Analysis II"
chapter: 3
key: "semester_5/power_system_analysis_ii:generator-reactor-fault-mva"
source: https://www.bctengineer.com/q/semester_5/power_system_analysis_ii/generator-reactor-fault-mva
site: BCT Engineering
---

# Generator-reactor system fault MVA

Power System Analysis II · Chapter 3: Power System Fault Calculation

- Asked in: 2072 Chaitra, 10 marks
- Video: [102. Short Circuit MVA of a Power System](https://www.youtube.com/watch?v=wxYQ8QoCHsk) — Bright Engineers
- Answer checked by Claude Sonnet 5.5 on 2026-10-14
- Page: https://www.bctengineer.com/q/semester_5/power_system_analysis_ii/generator-reactor-fault-mva
- Whole chapter: https://www.bctengineer.com/md/semester_5/power_system_analysis_ii/chapter-3

## Question

An interconnected generator reactor system has been shown in figure below. The base values for the given % reactance are the rating of individual pieces of equipments. Determine the fault current and fault MVA for a 3-phase short circuit fault at F. Assume bus bar voltage as 11 kV. [Figure: G1 10 MVA, 10% connected at the faulted bus F; reactor 10 MVA, 5% between bus F and the bus of G2 (20 MVA, 15%); reactor 8 MVA, 4% between the G2 bus and G3 (20 MVA, 15%)]

## Short answer

On 20 MVA base, Thevenin reactance at F is 0.0984 pu. Fault current = 10.16 pu = 10.67 kA at 11 kV. Fault MVA = 20 / 0.0984 = 203 MVA.

## Answer

The fault MVA is found by converting every reactance to one common MVA base, reducing the network to a single Thevenin reactance seen from F, and using $\text{Fault MVA} = \text{Base MVA}/X_{th}$ with prefault voltage 1 pu.

#### Step 1: Choose base and convert reactances
Base: $S_b = 20$ MVA, $V_b = 11$ kV. Use $X_{new} = X_{old}\,\dfrac{S_b}{S_{rated}}$ (same voltage, so no voltage correction).

| Element | Rating | Given X | X on 20 MVA (pu) |
|---|---|---|---|
| G1 | 10 MVA | 10% | $0.10 \times 20/10 = 0.20$ |
| Reactor R1 (F to G2 bus) | 10 MVA | 5% | $0.05 \times 20/10 = 0.10$ |
| G2 | 20 MVA | 15% | 0.15 |
| Reactor R2 (G2 bus to G3) | 8 MVA | 4% | $0.04 \times 20/8 = 0.10$ |
| G3 | 20 MVA | 15% | 0.15 |

#### Step 2: Reactance diagram
All generator EMFs are equal (1 pu) and their neutral is the reference, so for a 3-phase fault every source branch ends on the reference bus.

```text
   F (G1 bus)        R1=0.1       B (G2 bus)  R2=0.1
 ---o----------------/\/\/\---------o-------/\/\/\---+
    |                               |                |
  G1 0.2                         G2 0.15          G3 0.15
    |                               |                |
 ===+===========  reference  =======+================+===
```

#### Step 3: Reduce the network as seen from F
$$
\begin{aligned}
X_{R2+G3} &= 0.10 + 0.15 = 0.25 \\
X_B &= 0.15 \parallel 0.25 = \frac{0.15 \times 0.25}{0.40} = 0.09375 \\
X_{R1+B} &= 0.10 + 0.09375 = 0.19375 \\
X_{th} &= 0.20 \parallel 0.19375 = \frac{0.20 \times 0.19375}{0.39375} = 0.09841\ \text{pu}
\end{aligned}
$$

#### Step 4: Fault current and fault MVA
$$
\begin{aligned}
I_f &= \frac{1}{X_{th}} = \frac{1}{0.09841} = 10.16\ \text{pu} \\
I_b &= \frac{S_b}{\sqrt{3}\,V_b} = \frac{20\times 10^6}{\sqrt{3}\times 11\times 10^3} = 1049.7\ \text{A} \\
I_f &= 10.16 \times 1049.7 = 10\,667\ \text{A} \approx 10.67\ \text{kA} \\
\text{Fault MVA} &= \frac{S_b}{X_{th}} = \frac{20}{0.09841} = 203.2\ \text{MVA}
\end{aligned}
$$

Check: $\sqrt{3} \times 11 \times 10.667 = 203.2$ MVA.

The fault MVA does not depend on the base chosen. With a 10 MVA base every pu reactance is halved, so $X_{th} = 0.04920$ pu and $10/0.04920 = 203.2$ MVA, the same result.

**Answer: Fault current ≈ 10.67 kA (10.16 pu on 20 MVA base); fault MVA ≈ 203.2 MVA.**

## Check yourself

The answer's key points as multiple-choice questions, with the correct option and why.

1. Reactor R2 (8 MVA, 4%) on a 20 MVA base is
   A. 0.04 x 8/20 = 0.016 pu
   B. 0.04 pu
   C. 0.04 x 20/8 = 0.10 pu
   D. 0.04 x 20 = 0.8 pu
   Answer: C. X_new = X_old x S_base/S_rated = 0.04 x 20/8 = 0.10 pu. (Key point: Common base conversion)

2. Seen from F, how is the network reduced?
   A. R2 + G3 = 0.25, parallel with G2 = 0.09375, plus R1 = 0.19375, parallel with G1 gives X_th
   B. All five reactances in parallel
   C. All five reactances in series
   D. G1 in series with G2 then parallel with G3
   Answer: A. Work from the far end: (R2 + G3) || G2, then add R1, then put in parallel with G1 at F. (Key point: Network reduction order)

3. With X_th = 0.09841 pu on 20 MVA, fault MVA is
   A. 20 x 0.0984 = 1.97 MVA
   B. 20/0.09841 = 203.2 MVA
   C. 10/0.09841 MVA
   D. 1/0.0984 = 10.2 MVA
   Answer: B. Fault MVA = S_base/X_th = 203.2 MVA, and I_f = 10.67 kA at 11 kV. (Key point: Fault MVA)

4. If a 10 MVA base were used instead, the fault MVA would be
   A. Half as large
   B. Twice as large
   C. The same 203.2 MVA
   D. Undefined
   Answer: C. All pu values double but S_base halves, so S_base/X_th is unchanged; the physical fault level does not depend on the base. (Key point: Base independence)

## Related in Power System Analysis II

- [HV bus fault and limiting reactor](https://www.bctengineer.com/question.md?key=semester_5%2Fpower_system_analysis_ii%3Ahv-bus-fault-reactor-limit) — Power System Analysis II, chapter 3
- [L-G fault and 3-phase fault, 30 MVA generator](https://www.bctengineer.com/question.md?key=semester_5%2Fpower_system_analysis_ii%3Alg-fault-30mva-voltages-3phase) — Power System Analysis II, chapter 5
- [Neutral reactance for 15 MVA generator](https://www.bctengineer.com/question.md?key=semester_5%2Fpower_system_analysis_ii%3Aneutral-reactance-15mva) — Power System Analysis II, chapter 5
- [Fault through impedance at bus 2](https://www.bctengineer.com/question.md?key=semester_5%2Fpower_system_analysis_ii%3Afault-impedance-bus2-actual-currents) — Power System Analysis II, chapter 3
- [L-L fault current in kA at bus 3](https://www.bctengineer.com/question.md?key=semester_5%2Fpower_system_analysis_ii%3All-fault-bus3-ka) — Power System Analysis II, chapter 5
- [Fault MVA at bus 5 with inductive lines](https://www.bctengineer.com/question.md?key=semester_5%2Fpower_system_analysis_ii%3Afault-mva-bus5-mh-lines) — Power System Analysis II, chapter 3, asked 2×

## Related in other subjects

- [Bus-bar reactor scheme: 30 MVA and 50 MVA](https://www.bctengineer.com/question.md?key=semester_7%2Fpower_plant_equipment%3Abus-bar-reactor-30-50-mva) — Power Plant Equipment, chapter 4, asked 2×
- [Per unit circuit of three-generator system, 30 MVA base](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3Apu-circuit-30mva-g1-g2-g3) — Power System Analysis I, chapter 3
- [Fault level: four 25 MVA generators, bus reactor](https://www.bctengineer.com/question.md?key=semester_7%2Fpower_plant_equipment%3Afault-four-25mva-bus-reactor) — Power Plant Equipment, chapter 4
- [Bus-bar reactor scheme with four generators](https://www.bctengineer.com/question.md?key=semester_7%2Fpower_plant_equipment%3Abus-bar-reactor-four-generators) — Power Plant Equipment, chapter 4, asked 2×