# L-G fault of unloaded generator: equal currents

Power System Analysis II · Chapter 5: Unsymmetrical Faults on Power Systems

- Asked in: 2080 Bhadra, 8 marks
- Video: [Single Line to Ground Fault on an Unloaded Generator/LG Fault](https://www.youtube.com/watch?v=WtJvn4aLcTE) — Dr.Nagaraja Kumari
- Answer checked by Claude Sonnet 5.5 on 2026-10-14
- Page: https://www.bctengineer.com/q/semester_5/power_system_analysis_ii/lg-fault-unloaded-generator-derivation
- Whole chapter: https://www.bctengineer.com/md/semester_5/power_system_analysis_ii/chapter-5

## Question

Draw positive sequence, negative sequence and zero sequence network of synchronous generator. Show that all three sequence currents of faulty phase are equal in case of single line to ground fault of unloaded synchronous generator. Also find the expression of fault current.

## Short answer

Boundary conditions I_b=I_c=0 and V_a=Z_f I_a give I_a0=I_a1=I_a2=I_a/3, so all three sequence networks are in series. The fault current for a bolted single line-to-ground fault is I_f = 3E_a/(Z1+Z2+Z0); with fault impedance Z_f it is I_f = 3E_a/(Z1+Z2+Z0+3Z_f).

## Answer

For an L-G fault on phase a of an unloaded generator, $I_b = I_c = 0$, which gives $I_{a0} = I_{a1} = I_{a2} = I_a/3$; the three sequence networks are in series and $I_f = 3E_a/(Z_1+Z_2+Z_0)$ (bolted) or $3E_a/(Z_1+Z_2+Z_0+3Z_f)$ with fault impedance.

**Generator:** star connected, balanced EMFs $E_a$, $a^2E_a$, $aE_a$; neutral grounded through $Z_n$.

#### Sequence networks of an unloaded generator
The generator EMFs are balanced (positive sequence only), so with $Z_0 = Z_{g0} + 3Z_n$:
$$
V_{a0} = -Z_0I_{a0}, \qquad V_{a1} = E_a - Z_1I_{a1}, \qquad V_{a2} = -Z_2I_{a2}
$$
```text
 Positive        Negative        Zero
  F1 o            F2 o            F0 o
     |Ia1 ^          |Ia2 ^          |Ia0 ^
    Z1              Z2              Z0
     |               |               |
   (Ea)              |               |
     |               |               |
  N1 o            N2 o            N0 o
```
- **Positive sequence:** contains the EMF $E_a$ and $Z_1$ (sub-transient reactance $X_d''$ for fault studies). No current flows in $Z_n$.
- **Negative sequence:** no EMF, impedance $Z_2$, connected to the neutral directly.
- **Zero sequence:** no EMF, impedance $Z_0 = Z_{g0} + 3Z_n$; the current through the neutral is $3I_{a0}$.

#### Boundary conditions (fault on phase a through $Z_f$)
```text
  a o----------+
  b o---  (Ib=0)
  c o---  (Ic=0)
               |  Ia = If
              Zf
               |
            ground
```
$$
I_b = 0, \qquad I_c = 0, \qquad V_a = Z_fI_a
$$

#### Sequence currents are equal
$$
\begin{bmatrix} I_{a0}\\I_{a1}\\I_{a2} \end{bmatrix} = \frac13\begin{bmatrix} 1&1&1\\1&a&a^2\\1&a^2&a \end{bmatrix}\begin{bmatrix} I_a\\0\\0 \end{bmatrix}
\quad\Rightarrow\quad I_{a0} = I_{a1} = I_{a2} = \frac{I_a}{3}
$$
So the **same current flows in all three sequence networks**, which means they are in series.

#### Voltage condition
$$
V_a = V_{a0} + V_{a1} + V_{a2} = Z_fI_a = 3Z_fI_{a1}
$$
Substituting the network equations:
$$
-Z_0I_{a1} + E_a - Z_1I_{a1} - Z_2I_{a1} = 3Z_fI_{a1}
$$
$$
I_{a1} = I_{a2} = I_{a0} = \frac{E_a}{Z_1 + Z_2 + Z_0 + 3Z_f}
$$

#### Fault current
$$
I_f = I_a = 3I_{a1} = \frac{3E_a}{Z_1 + Z_2 + Z_0 + 3Z_f}
$$
For a bolted fault ($Z_f = 0$): $I_f = \dfrac{3E_a}{Z_1+Z_2+Z_0}$.

#### Interconnection of sequence networks
```text
   F1 --(Ea)--[Z1]-- N1 == F2 --[Z2]-- N2 == F0 --[Z0]-- N0
   |                                                       |
   +------------------------[ 3Zf ]------------------------+
              common current  Ia1 = Ia2 = Ia0
```
The three networks are connected in **series** with $3Z_f$: $N_1$ is joined to $F_2$ (the "==" links), $N_2$ is joined to $F_0$, and $N_0$ returns to $F_1$ through $3Z_f$. The common current $I_{a1}$ flows through all of them. Both conditions ($I_{a0} = I_{a1} = I_{a2}$ and $V_{a0}+V_{a1}+V_{a2} = 3Z_fI_{a1}$) are satisfied only by this series connection.

## Check yourself

The answer's key points as multiple-choice questions, with the correct option and why.

1. In the sequence networks of an unloaded generator, which network contains the EMF?
   A. Negative sequence only
   B. Zero sequence only
   C. All three
   D. Positive sequence only
   Answer: D. Generator EMFs are balanced, so only the positive sequence network has a source. (Key point: Sequence networks of generator)

2. A generator neutral is grounded through Zn. What zero sequence impedance appears in the zero sequence network?
   A. Z0 = Zg0 + 3Zn
   B. Z0 = Zg0 + Zn
   C. Z0 = Zg0
   D. Z0 = Zg0 + Zn/3
   Answer: A. The neutral carries 3Ia0, so its drop 3Zn Ia0 appears as 3Zn in the zero sequence network. (Key point: Zero sequence impedance with neutral impedance)

3. Why does Ib = Ic = 0 give Ia0 = Ia1 = Ia2?
   A. Because Z0 = Z1 = Z2
   B. Because each sequence current is (1/3)(Ia + 0 + 0) = Ia/3
   C. Because the neutral is isolated
   D. Because the fault impedance is zero
   Answer: B. With only Ia nonzero, every row of the transformation gives Ia/3, so the same current flows in all three sequence networks. (Key point: Equal sequence currents)

4. What is the L-G fault current with fault impedance Zf at the terminals of an unloaded generator?
   A. Ea/(Z1 + Z2 + Z0 + Zf)
   B. 3Ea/(Z1 + Z2 + Z0)
   C. 3Ea/(Z1 + Z2 + Z0 + 3Zf)
   D. Ea/(Z1 + Z2 + Z0 + 3Zf)
   Answer: C. Ia1 = Ea/(Z1 + Z2 + Z0 + 3Zf) and If = Ia = 3Ia1. (Key point: Fault current expression)

## Related in Power System Analysis II

- [Equal positive and negative sequence impedances](https://www.bctengineer.com/question.md?key=semester_5%2Fpower_system_analysis_ii%3Astatic-circuit-positive-negative-equal) — Power System Analysis II, chapter 4
- [DLG fault sequence network connection](https://www.bctengineer.com/question.md?key=semester_5%2Fpower_system_analysis_ii%3Adlg-sequence-network-connection) — Power System Analysis II, chapter 5, asked 3×
- [Fault currents of isolated-neutral 380 V generator](https://www.bctengineer.com/question.md?key=semester_5%2Fpower_system_analysis_ii%3Agenerator-faults-380v-isolated-neutral) — Power System Analysis II, chapter 5
- [L-G fault and 3-phase fault, 30 MVA generator](https://www.bctengineer.com/question.md?key=semester_5%2Fpower_system_analysis_ii%3Alg-fault-30mva-voltages-3phase) — Power System Analysis II, chapter 5
- [No zero sequence in line-to-line fault](https://www.bctengineer.com/question.md?key=semester_5%2Fpower_system_analysis_ii%3All-fault-zero-sequence-absent) — Power System Analysis II, chapter 5, asked 2×
- [L-G fault through Zf: currents and voltages](https://www.bctengineer.com/question.md?key=semester_5%2Fpower_system_analysis_ii%3Alg-fault-with-zf-derivation) — Power System Analysis II, chapter 5

## Related in other subjects

- [Positive/negative bias current effect and reduction](https://www.bctengineer.com/question.md?key=semester_4%2Fadvanced_electronics%3Apositive-negative-bias-current) — Advanced Electronics, chapter 2
- [Delta load line currents and power, ABC sequence](https://www.bctengineer.com/question.md?key=semester_1%2Fbasic_electrical_engineering%3Adelta-unbalanced-52-45-380v-abc) — Basic Electrical Engineering, chapter 8
- [Delta load (15+j20) phase and line currents](https://www.bctengineer.com/question.md?key=semester_1%2Fbasic_electrical_engineering%3Adelta-load-15j20-220v-phasors) — Basic Electrical Engineering, chapter 8
- [Fault current: 50 MW and 40 MW generators](https://www.bctengineer.com/question.md?key=semester_7%2Fpower_plant_equipment%3Afault-50mw-40mw-equal-current) — Power Plant Equipment, chapter 4