# Line-to-line fault current calculation

Power System Analysis II · Chapter 5: Unsymmetrical Faults on Power Systems

- Asked in: 2075 Asoj, 6 marks; 2074 Asoj, 8 marks; 2074 Chaitra, 9 marks; 2068 Chaitra, 8 marks (asked 4 times)
- Video: [LINE TO LINE FAULT ON AN UNLOADED SYNCHRONOUS GENERATOR](https://www.youtube.com/watch?v=DnX0an2FgWc) — P SUMALATHA
- Answer checked by Claude Sonnet 5.5 on 2026-10-14
- Page: https://www.bctengineer.com/q/semester_5/power_system_analysis_ii/line-to-line-fault-calculation
- Whole chapter: https://www.bctengineer.com/md/semester_5/power_system_analysis_ii/chapter-5

## Question

Explain (derive) with necessary mathematical expressions and diagrams how fault current and bus voltages are calculated when a line-to-line fault occurs in a 3-phase power system network. Draw a diagram showing interconnection of sequence networks for this type of fault.

## Short answer

For a line-to-line fault, I_a0=0 and I_a2 = –I_a1, so positive and negative networks connect in parallel opposition through Z_f. I_a1 = V_f/(Z_1+Z_2+Z_f). Fault current I_f = –j√3 V_f/(Z_1+Z_2+Z_f). Sequence voltages at the fault bus are V_a1=V_f–Z_1 I_a1, V_a2=Z_2 I_a1; voltages at other buses follow from the Z-bus matrices.

## Answer

In a line-to-line (L-L) fault the zero sequence current is zero, $I_{a1} = -I_{a2}$, and the positive and negative sequence networks are connected in parallel (opposition) through $Z_f$ at the fault point. Fault current is $I_f = -j\sqrt3\,E_a/(Z_1+Z_2+Z_f)$.

**Model:** the network is represented at the fault bus k by its Thevenin sequence equivalents: prefault voltage $V_f = V_k(0)$ and impedances $Z_1 = Z_{kk}^{(1)}$, $Z_2 = Z_{kk}^{(2)}$, $Z_0 = Z_{kk}^{(0)}$ (from the sequence Z-bus matrices). For a generator terminal fault, $V_f = E_a$ and $Z$ are the machine's own values.

#### Boundary conditions (fault between phases b and c through $Z_f$)
```text
  a o-----------  Ia = 0
  b o-----+        Ib = If -->
          Zf
  c o-----+        Ic = -Ib
```
$$
I_a = 0, \qquad I_b + I_c = 0, \qquad V_b - V_c = Z_fI_b
$$

#### Sequence currents
$$
\begin{aligned}
I_{a0} &= \tfrac13(I_a + I_b + I_c) = \tfrac13(0 + I_b - I_b) = 0 \\
I_{a1} &= \tfrac13(I_a + aI_b + a^2I_c) = \tfrac13(a - a^2)I_b \\
I_{a2} &= \tfrac13(I_a + a^2I_b + aI_c) = \tfrac13(a^2 - a)I_b
\end{aligned}
$$
Hence
$$
I_{a0} = 0, \qquad I_{a2} = -I_{a1}
$$
#### Voltage condition
$$
\begin{aligned}
V_b - V_c &= (a^2 - a)V_{a1} + (a - a^2)V_{a2} = (a^2 - a)(V_{a1} - V_{a2}) \\
Z_fI_b &= Z_f\,(a^2I_{a1} + aI_{a2}) = Z_f(a^2 - a)I_{a1}
\end{aligned}
$$
so
$$
V_{a1} - V_{a2} = Z_fI_{a1}
$$
With $V_{a1} = V_f - Z_1I_{a1}$ and $V_{a2} = -Z_2I_{a2} = Z_2I_{a1}$:
$$
I_{a1} = -I_{a2} = \frac{V_f}{Z_1 + Z_2 + Z_f}
$$

#### Fault current
$$
\begin{aligned}
I_b &= I_{a0} + a^2I_{a1} + aI_{a2} = (a^2 - a)I_{a1} = -j\sqrt3\,I_{a1} \\
I_f &= I_b = -I_c = \frac{-j\sqrt3\,V_f}{Z_1 + Z_2 + Z_f}
\end{aligned}
$$

#### Voltages at the fault bus
$$
\begin{aligned}
V_{a1} &= V_f - Z_1I_{a1}, \quad V_{a2} = Z_2I_{a1}, \quad V_{a0} = 0 \\
V_a &= V_{a1} + V_{a2}, \quad V_b = a^2V_{a1} + aV_{a2}, \quad V_c = aV_{a1} + a^2V_{a2}
\end{aligned}
$$
For a bolted fault ($Z_f = 0$), $V_{a1} = V_{a2}$, so $V_a = 2V_{a1}$ and $V_b = V_c = -V_{a1}$.

#### Voltages at other buses (i) of a network
Using the sequence bus impedance matrices, with the fault at bus k:
$$
V_i^{(1)} = V_i(0) - Z_{ik}^{(1)}I_{a1}, \qquad V_i^{(2)} = -Z_{ik}^{(2)}I_{a2}, \qquad V_i^{(0)} = 0
$$
Phase voltages follow from $V_{abc} = AV_{012}$ (with the $\pm30^\circ$ phase shift of Δ-Y transformers applied to the positive and negative sequence values when crossing them). Line currents then follow from $I_{ij} = (V_i - V_j)/z_{ij}$ in each sequence network.
#### Interconnection of sequence networks
```text
        Ia1 -->           <-- Ia2
  +--(Ea)--Z1---o F1--Zf--o F2---Z2--+
  |                                  |
  N1 ------------------------------- N2

  Zero sequence network: not connected (Ia0 = 0)
```
The positive and negative sequence networks are connected **in parallel (in opposition)** through $Z_f$; the zero sequence network is left open.

#### Steps in summary
1. Form $Z_1$, $Z_2$ at the fault point (Thevenin), and take $V_f$ = prefault voltage.
2. $I_{a1} = -I_{a2} = V_f/(Z_1+Z_2+Z_f)$, $I_{a0} = 0$.
3. $I_f = -j\sqrt3 I_{a1}$.
4. Find sequence voltages, then phase voltages at the fault and other buses.

## Check yourself

The answer's key points as multiple-choice questions, with the correct option and why.

1. Which set of conditions describes an L-L fault between phases b and c through Zf?
   A. Ib = Ic = 0, Va = Zf Ia
   B. Ia = 0, Ib = -Ic, Vb - Vc = Zf Ib
   C. Va = Vb = Vc = 0
   D. Ia = Ib = Ic
   Answer: B. Phase a is healthy, fault current flows b to c, and the voltage across the fault is Zf Ib. (Key point: Boundary conditions)

2. What do the boundary conditions give for the sequence currents?
   A. Ia0 = Ia1 = Ia2
   B. Ia1 = Ia2 = 0
   C. Ia0 = Ia1 + Ia2
   D. Ia0 = 0 and Ia2 = -Ia1
   Answer: D. Ia + Ib + Ic = 0 gives Ia0 = 0, and the transform gives Ia2 = -Ia1. (Key point: Sequence relations)

3. How are the sequence networks connected for an L-L fault?
   A. Positive and negative in parallel (opposition) through Zf, zero network open
   B. All three in series
   C. All three in parallel
   D. Positive and zero in series, negative open
   Answer: A. Va1 - Va2 = Zf Ia1 and Ia1 = -Ia2 gives positive and negative linked through Zf; no zero network. (Key point: Network interconnection)

4. Which is the L-L fault current magnitude?
   A. Vf/(Z1 + Z2 + Z0)
   B. 3Vf/(Z1 + Z2 + Zf)
   C. sqrt(3) Vf/(Z1 + Z2 + Zf)
   D. Vf/(Z1 + Z2 + 3Zf)
   Answer: C. Ib = (a^2 - a)Ia1 = -j sqrt(3) Ia1 with Ia1 = Vf/(Z1+Z2+Zf). (Key point: Fault current expression)

## Related in Power System Analysis II

- [SLG fault at bus 3, currents and voltages](https://www.bctengineer.com/question.md?key=semester_5%2Fpower_system_analysis_ii%3Aslg-fault-bus3-three-generators) — Power System Analysis II, chapter 5
- [SLG fault: sequence networks in series](https://www.bctengineer.com/question.md?key=semester_5%2Fpower_system_analysis_ii%3Aslg-sequence-networks-series) — Power System Analysis II, chapter 5, asked 5×
- [L-L fault current in kA at bus 3](https://www.bctengineer.com/question.md?key=semester_5%2Fpower_system_analysis_ii%3All-fault-bus3-ka) — Power System Analysis II, chapter 5
- [DLG fault sequence network connection](https://www.bctengineer.com/question.md?key=semester_5%2Fpower_system_analysis_ii%3Adlg-sequence-network-connection) — Power System Analysis II, chapter 5, asked 3×
- [L-L fault line voltages, 25 MVA alternator](https://www.bctengineer.com/question.md?key=semester_5%2Fpower_system_analysis_ii%3All-fault-25mva-line-voltages) — Power System Analysis II, chapter 5, asked 2×
- [LLG fault sequence currents at bus 3](https://www.bctengineer.com/question.md?key=semester_5%2Fpower_system_analysis_ii%3Allg-fault-bus3-sequence-currents) — Power System Analysis II, chapter 5

## Related in other subjects

- [Interconnected system SLD with bus voltages](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3Ainterconnected-sld-bus-voltages) — Power System Analysis I, chapter 1
- [Reactance diagram of eight-bus system](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3Areactance-diagram-eight-bus) — Power System Analysis I, chapter 3
- [External actors and library system sequence diagram](https://www.bctengineer.com/question.md?key=semester_6%2Fobject_oriented_analysis_and_design%3Aexternal-actors-library-system-sequence-diagram) — Object Oriented Analysis and Design, chapter 2
- [Star load (8+j6) line, phase current](https://www.bctengineer.com/question.md?key=semester_1%2Fbasic_electrical_engineering%3Astar-load-8j6-400v-ryb) — Basic Electrical Engineering, chapter 8