# 3-bus load flow with Q limits (cut off)

Power System Analysis II · Chapter 2: Load Flow Analysis

- Asked in: 2074 Asoj
- Answer checked by Claude Sonnet 5.5 on 2026-10-14
- Page: https://www.bctengineer.com/q/semester_5/power_system_analysis_ii/load-flow-reference-load-generator-bus
- Whole chapter: https://www.bctengineer.com/md/semester_5/power_system_analysis_ii/chapter-2

## Question

Suppose you are given a 3-bus power system network with one reference bus, one load bus and one generator bus with reactive power limits and asked to perform the [rest of the question is cut off in the scan: ...unknown variables and total losses in the network].

## Short answer

Form Ybus and start with a flat voltage profile. For PV bus 2, compute Q2, check Q-limits; if violated fix Q and treat as PQ, else correct angle and reset |V2|. Update PQ bus 3 with the Gauss–Seidel formula. Iterate until convergence, then compute slack bus power and line flows to obtain total losses.

## Answer

The scanned question is cut off. It is taken here as: *describe how to carry out the load flow of such a 3-bus system (Gauss-Seidel method) to find the unknown variables and the total losses.* Bus 1 is the reference (slack) bus, bus 2 the generator (PV) bus with Q-limits, and bus 3 the load (PQ) bus.

#### Known and unknown quantities
| Bus | Type | Known | Unknown |
|---|---|---|---|
| 1 | Reference (slack) | $\lvert V_1\rvert$, $\delta_1 = 0$ | $P_1$, $Q_1$ |
| 2 | Generator (PV) | $P_2$, $\lvert V_2\rvert$, $Q_{min}$, $Q_{max}$ | $Q_2$, $\delta_2$ |
| 3 | Load (PQ) | $P_3$, $Q_3$ | $\lvert V_3\rvert$, $\delta_3$ |

#### Step-by-step procedure
1. **Form $Y_{bus}$** from the line data: $Y_{ii}$ = sum of admittances connected to bus $i$ (including half line charging), $Y_{ij} = -y_{ij}$.
2. **Net injections:** $P_i = P_{Gi} - P_{Li}$, $Q_i = Q_{Gi} - Q_{Li}$.
3. **Flat start:** $V_2^{(0)} = |V_2|_{spec}\angle 0^\circ$, $V_3^{(0)} = 1\angle 0^\circ$.
4. **PV bus 2:** find the reactive power

$$
Q_2^{(k+1)} = -\text{Im}\left\{V_2^{(k)*}\sum_{j=1}^{3}Y_{2j}V_j\right\}
$$

5. **Check Q-limits.** If $Q_{min} \le Q_2 \le Q_{max}$, keep bus 2 as PV. If not, set $Q_2$ to the violated limit and treat bus 2 as a PQ bus (its voltage magnitude is then not reset).
6. **Update $V_2$:**

$$
V_2^{(k+1)} = \frac{1}{Y_{22}}\left[\frac{P_2 - jQ_2}{V_2^{(k)*}} - Y_{21}V_1 - Y_{23}V_3^{(k)}\right]
$$

   If bus 2 is still PV, keep only the angle and reset the magnitude to $|V_2|_{spec}$.
7. **Update $V_3$** using the newest $V_2$:

$$
V_3^{(k+1)} = \frac{1}{Y_{33}}\left[\frac{P_3 - jQ_3}{V_3^{(k)*}} - Y_{31}V_1 - Y_{32}V_2^{(k+1)}\right]
$$

8. **Convergence test:** stop when $|V_i^{(k+1)} - V_i^{(k)}| < \varepsilon$ (e.g. 0.0001) for all buses. Otherwise repeat from step 4. An acceleration factor of about 1.6 may be used on PQ buses.
9. **Slack bus power:**

$$
P_1 - jQ_1 = V_1^{*}\left(Y_{11}V_1 + Y_{12}V_2 + Y_{13}V_3\right)
$$

   and $P_{G1} = P_1 + P_{L1}$, $Q_{G1} = Q_1 + Q_{L1}$.
10. **Line flows:** $S_{ij} = V_i\left[(V_i - V_j)y_{ij} + V_i\,y_{sh,ij}\right]^{*}$.
11. **Total losses:**

$$
\begin{aligned}
P_{loss} &= \sum_{i=1}^{3}P_i = P_1 + P_2 + P_3 \\
&= \sum_{\text{lines}}\text{Re}(S_{ij} + S_{ji})
\end{aligned}
$$

and similarly $Q_{loss} = \sum Q_i$.

```text
 Read data -> form Ybus -> flat start
            |
            v
 +--> Q2 from present voltages
 |    check Q-limits (PV or PQ?)
 |    update V2 (reset |V2| if PV)
 |    update V3
 |    converged? --no--+
 |                     |
 +---------------------+
            | yes
            v
 slack P1,Q1 -> line flows -> losses
```

## Check yourself

The answer's key points as multiple-choice questions, with the correct option and why.

1. Which quantities are unknown at the generator (PV) bus 2?
   A. P2 and |V2|
   B. |V2| and delta2
   C. P2 and Q2
   D. Q2 and delta2
   Answer: D. At a PV bus P and |V| are specified, so Q and the angle must be found. (Key point: Unknowns by bus type)

2. In Gauss-Seidel, what is done if calculated Q2 violates its limit?
   A. Q2 is set to the violated limit and bus 2 is treated as PQ
   B. The slack bus is changed
   C. The iteration is stopped
   D. Q2 is set to zero and |V2| is kept
   Answer: A. Q is fixed at the limit and the voltage magnitude is no longer reset, so the bus behaves as PQ. (Key point: Q-limit violation)

3. Which V2 is used when updating V3 in the same iteration?
   A. The initial V2(0)
   B. The newest V2(k+1)
   C. The average of V2(k) and V2(k+1)
   D. The specified magnitude with zero angle
   Answer: B. Gauss-Seidel uses the latest available values immediately, which speeds convergence. (Key point: Sequential update)

4. How is the total real power loss found after convergence?
   A. P1 alone
   B. The difference of the largest and smallest bus voltage
   C. The slack bus Q
   D. The sum of all bus injections P1 + P2 + P3
   Answer: D. Total loss equals the algebraic sum of net bus injections, equal to the sum of line losses. (Key point: Total losses)

## Related in Power System Analysis II

- [G-S load flow with given Ybus, losses](https://www.bctengineer.com/question.md?key=semester_5%2Fpower_system_analysis_ii%3Ags-ybus-j12-two-iterations) — Power System Analysis II, chapter 2
- [G-S with PV bus Q limits and losses](https://www.bctengineer.com/question.md?key=semester_5%2Fpower_system_analysis_ii%3Ags-pv-bus-q-limits-2071) — Power System Analysis II, chapter 2
- [Network losses from given bus voltages](https://www.bctengineer.com/question.md?key=semester_5%2Fpower_system_analysis_ii%3Anetwork-losses-given-voltages) — Power System Analysis II, chapter 2
- [G-S load flow, j0.12 lines, losses](https://www.bctengineer.com/question.md?key=semester_5%2Fpower_system_analysis_ii%3Ags-three-bus-j012-losses) — Power System Analysis II, chapter 2, asked 2×
- [Reactive power injection and generation limits](https://www.bctengineer.com/question.md?key=semester_5%2Fpower_system_analysis_ii%3Areactive-power-injection-limits) — Power System Analysis II, chapter 1
- [Generator reactive power at constant terminal voltage](https://www.bctengineer.com/question.md?key=semester_5%2Fpower_system_analysis_ii%3Agenerator-reactive-power-infinite-bus) — Power System Analysis II, chapter 1

## Related in other subjects

- [Lateral load elements; stepwise [cut off]](https://www.bctengineer.com/question.md?key=semester_5%2Fconcrete_technology_and_masonry_structure%3Alateral-elements-stepwise-74c) — Concrete Technology and Masonry Structure, chapter 9
- [Network: unknown discharges and head losses](https://www.bctengineer.com/question.md?key=semester_4%2Fhydraulics%3Anetwork-find-unknown-discharges-head-losses) — Hydraulics, chapter 3, asked 2×
- [Reactive power flow between machines via j10 Ω](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3Atwo-machines-reactive-j10) — Power System Analysis I, chapter 3
- [Direction of active and reactive power flow](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3Adirection-active-reactive-flow) — Power System Analysis I, chapter 6