# Power invariance of symmetrical transformation

Power System Analysis II · Chapter 4: Unbalanced System Analysis

- Asked in: 2075 Chaitra, 6+2 marks
- Video: [POWER INVARIANCE IN SYMMETRICAL COMPONENTS /KTU / POWER SYSTEM ANALYSIS](https://www.youtube.com/watch?v=GJHJYKfeaEQ) — praveen raj
- Answer checked by Claude Sonnet 5.5 on 2026-10-14
- Page: https://www.bctengineer.com/q/semester_5/power_system_analysis_ii/power-invariance-zero-sequence
- Whole chapter: https://www.bctengineer.com/md/semester_5/power_system_analysis_ii/chapter-4

## Question

Prove that the symmetrical component transformation is power invariant. Discuss also the significance of zero sequence circuit.

## Short answer

The transformation gives S = 3(Va0Ia0*+Va1Ia1*+Va2Ia2*); with the unitary form it is exactly invariant. Zero sequence currents are in phase, require ground/neutral return, so the zero sequence network governs earth faults, grounding impedance, and protection coordination.

## Answer

A transformation is **power invariant** if the power calculated from the transformed (sequence) quantities equals the power calculated from the original (phase) quantities. The symmetrical component transformation gives $S = 3(V_{a0}I_{a0}^* + V_{a1}I_{a1}^* + V_{a2}I_{a2}^*)$, which is power invariant apart from a constant factor 3, and exactly invariant in its unitary form.

#### Proof
Complex power in phase quantities:
$$
S = V_aI_a^* + V_bI_b^* + V_cI_c^* = V_p^TI_p^*
$$
With $V_p = AV_s$, $I_p = AI_s$, where $A = \begin{bmatrix} 1&1&1\\1&a^2&a\\1&a&a^2 \end{bmatrix}$:
$$
S = (AV_s)^T(AI_s)^* = V_s^T\,A^TA^*\,I_s^*
$$
$A$ is symmetric, so $A^T = A$; and $a^* = a^2$, so $A^* = \begin{bmatrix} 1&1&1\\1&a&a^2\\1&a^2&a \end{bmatrix}$. Using $1+a+a^2 = 0$, $a^3 = 1$:
$$
A^TA^* = \begin{bmatrix} 3 & 1+a+a^2 & 1+a^2+a \\ 1+a^2+a & 1+a^3+a^3 & 1+a^4+a^2 \\ 1+a+a^2 & 1+a^2+a^4 & 1+a^3+a^3 \end{bmatrix} = \begin{bmatrix} 3&0&0\\0&3&0\\0&0&3 \end{bmatrix}
$$
Hence
$$
S = 3V_s^TI_s^* = 3V_{a0}I_{a0}^* + 3V_{a1}I_{a1}^* + 3V_{a2}I_{a2}^*
$$

#### Exact power invariance
If the transformation matrix is taken as $T = \frac{1}{\sqrt3}A$, then $T^TT^* = \frac13\cdot3U = U$ (unit matrix) and
$$
S = V_p^TI_p^* = V_s^TI_s^* = V_{0}I_{0}^* + V_{1}I_{1}^* + V_{2}I_{2}^*
$$
So the power is the same in both reference frames: the transformation is **power invariant**. With the usual matrix $A$ the sequence power of phase a is multiplied by 3 (three phases), and there are still no cross terms.

#### Significance of the zero sequence circuit
- Zero sequence currents are equal and in phase in all three phases, so they need a **return path through neutral or ground**: $I_n = 3I_{a0}$. The zero sequence network therefore depends on transformer winding connections (star grounded, star ungrounded, delta) and on neutral grounding.
- It decides the current in **ground faults** (L-G, L-L-G). Since about 70–80% of faults are L-G, the zero sequence network is essential for finding earth fault current, choosing neutral grounding impedance and setting earth fault relays.
- A neutral impedance $Z_n$ appears as $3Z_n$ only in the zero sequence circuit, so grounding methods change only this network.
- Delta windings block zero sequence current from the lines but let it circulate inside; this is used to trap third harmonics and to isolate ground faults between voltage levels.
- Zero sequence currents in lines induce voltages in nearby telephone lines (interference) and are used for ground-fault detection.

## Check yourself

The answer's key points as multiple-choice questions, with the correct option and why.

1. With the usual A, S = 3(Va0 Ia0* + ...) so the transformation is:
   A. Not related to phase power
   B. Exactly invariant
   C. Power invariant apart from the factor 3
   D. Invariant only for balanced
   Answer: C. A is not unitary. (Key point: Matrix A)

2. Exact power invariance is obtained with:
   A. T = 3A
   B. T = A^-1
   C. T = A/3
   D. T = A/sqrt(3)
   Answer: D. T^T T* = U. (Key point: Exact invariance)

3. The zero sequence network is essential because:
   A. It decides ground fault current and neutral grounding effects
   B. It is the only network with sources
   C. It carries load power
   D. It affects only line-to-line faults
   Answer: A. Most faults are L-G. (Key point: Zero sequence importance)

4. A delta winding in the zero sequence network:
   A. Passes it to lines
   B. Blocks zero sequence current from lines but lets it circulate
   C. Amplifies it
   D. Shorts it to ground outside
   Answer: B. Used to trap third harmonics. (Key point: Delta winding)

## Related in Power System Analysis II

- [No zero sequence in line-to-line fault](https://www.bctengineer.com/question.md?key=semester_5%2Fpower_system_analysis_ii%3All-fault-zero-sequence-absent) — Power System Analysis II, chapter 5, asked 2×
- [Sequence networks decoupled for static circuit](https://www.bctengineer.com/question.md?key=semester_5%2Fpower_system_analysis_ii%3Astatic-circuit-sequence-decoupled) — Power System Analysis II, chapter 4
- [No zero sequence current in delta lines](https://www.bctengineer.com/question.md?key=semester_5%2Fpower_system_analysis_ii%3Adelta-zero-sequence-absent) — Power System Analysis II, chapter 4, asked 2×
- [Sequence impedances and zero sequence comment](https://www.bctengineer.com/question.md?key=semester_5%2Fpower_system_analysis_ii%3Asequence-impedance-star-load-zero) — Power System Analysis II, chapter 4, asked 2×
- [Zero sequence Thevenin impedance at bus 2](https://www.bctengineer.com/question.md?key=semester_5%2Fpower_system_analysis_ii%3Azero-sequence-thevenin-bus2) — Power System Analysis II, chapter 4
- [Initial symmetrical current, load short circuit](https://www.bctengineer.com/question.md?key=semester_5%2Fpower_system_analysis_ii%3Ainitial-current-load-short-circuit) — Power System Analysis II, chapter 3

## Related in other subjects

- [Transmission and y parameters, prove not reciprocal or symmetrical](https://www.bctengineer.com/question.md?key=semester_3%2Felectrical_circuit_theory%3Atransmission-and-y-parameters-neither-reciprocal) — Electrical Circuit Theory, chapter 7, asked 2×
- [Pure inductive circuit, zero real power](https://www.bctengineer.com/question.md?key=semester_1%2Fbasic_electrical_engineering%3Apure-inductive-circuit-power-derivation) — Basic Electrical Engineering, chapter 6, asked 2×
- [Pure capacitor circuit, zero real power](https://www.bctengineer.com/question.md?key=semester_1%2Fbasic_electrical_engineering%3Apure-capacitor-instantaneous-current) — Basic Electrical Engineering, chapter 6, asked 2×
- [Phase sequence and significance](https://www.bctengineer.com/question.md?key=semester_1%2Fbasic_electrical_engineering%3Aphase-sequence-significance) — Basic Electrical Engineering, chapter 8