# Equivalent Z0, Z1, Z2 at bus 3

Power System Analysis II · Chapter 5: Unsymmetrical Faults on Power Systems

- Asked in: 2068 Chaitra, 8 marks
- Video: [POSITIVE, NEGATIVE, ZERO SEQUENCE REACTANCE DIAGRAM / KTU/ POWER SYSTEM ANALYSIS](https://www.youtube.com/watch?v=zWNFHgJ7b5s) — praveen raj
- Answer checked by Claude Sonnet 5.5 on 2026-10-14
- Page: https://www.bctengineer.com/q/semester_5/power_system_analysis_ii/sequence-thevenin-z0-z1-z2-bus3
- Whole chapter: https://www.bctengineer.com/md/semester_5/power_system_analysis_ii/chapter-5

## Question

Draw positive, negative and zero sequence networks. If an unsymmetrical fault occurs at bus 3, determine equivalent Z0, Z1 and Z2. [Figure: G1 100 MVA, 11 kV, X1 = X2 = j0.2 pu, X0 = j0.05 pu (Y grounded) - T1 100 MVA, 11/220 kV, j0.1 pu (Δ / Y grounded) - parallel lines L1 (100 MVA, 220 kV, j0.1 pu) and L2 (100 MVA, 220 kV, 0.12 pu) - T2 50 MVA, 11/220 kV, j0.075 pu (Y grounded through j0.03 pu on line side / Δ) - G2 50 MVA, 11 kV, X1 = X2 = j0.15 pu, X0 = j0.03 pu (Y grounded through j0.024 pu)]

## Short answer

Positive and negative sequence impedances at bus 3: Z1 = Z2 = j0.1983 pu. Zero-sequence impedance: Z0 = j(0.1+0.0545) ∥ j0.33 = j0.105 pu (or j0.094 pu depending on neutral reactor base).

## Answer

**Assumptions:** base 100 MVA; bus 1 = G1 terminal, bus 2 = T1 HV side, bus 3 = T2 HV side (end of the parallel lines), bus 4 = G2 terminal. Neutral reactances (j0.03 for T2, j0.024 for G2) are taken on their own 50 MVA rating. Line zero-sequence reactance is taken equal to the given value since no separate $X_0$ is given.

#### Per-unit values on 100 MVA
| Element | $X_1 = X_2$ | $X_0$ |
|---|---|---|
| G1 | 0.20 | 0.05 |
| T1 | 0.10 | 0.10 |
| L1 ∥ L2 | $0.1\|0.12 = 0.0545$ | 0.0545 |
| T2 ($\times 2$) | 0.15 | 0.15 |
| T2 neutral ($\times 2$) | – | $3\times0.06 = 0.18$ |
| G2 ($\times 2$) | 0.30 | 0.06 |
| G2 neutral ($\times 2$) | – | $3\times0.048 = 0.144$ |

#### Positive sequence network
```text
 E1-j0.2-(1)-j0.1-(2)-j0.0545-(3)-j0.15-(4)-j0.3-E2
                                |
                                F
```
$$
Z_1 = j(0.2+0.1+0.0545)\ \|\ j(0.15+0.3) = j0.3545\ \|\ j0.45 = j0.1983\ \text{pu}
$$

#### Negative sequence network
Same reactances, emfs shorted:
$$
Z_2 = j0.1983\ \text{pu}
$$

#### Zero sequence network
- T1 Δ (G1 side)/Yg (line side): bus 2 to reference through $j0.1$; G1 isolated.
- T2 Yg through j0.03 (line side)/Δ (G2 side): bus 3 to reference through $j(0.15+0.18) = j0.33$; G2 isolated.
```text
 ref-j0.1-(2)-j0.0545-(3)-j0.33-ref
                       |
                       F
 G1 (j0.05) and G2 (j0.06+j0.144) isolated by deltas
```
$$
Z_0 = j(0.1+0.0545)\ \|\ j0.33 = j0.1545\ \|\ j0.33 = j0.1053\ \text{pu}
$$

**Answer:** $Z_1 = Z_2 = j0.198$ pu, $Z_0 = j0.105$ pu at bus 3.

(If the neutral reactance j0.03 is taken as already on the 100 MVA base, $Z_0 = j0.1545\|j0.24 = j0.094$ pu.)

## Check yourself

The answer's key points as multiple-choice questions, with the correct option and why.

1. Why must T2 and G2 (50 MVA) values be converted?
   A. Different frequency
   B. To a common 100 MVA base: values double
   C. They are star-connected
   D. Voltage ratings differ so values halve
   Answer: B. Values on 50 MVA are multiplied by 100/50, so T2 becomes 0.15 and G2 0.30 on the 100 MVA base. (Key point: Per-unit base conversion)

2. Z1 at bus 3 is:
   A. 0.3545 + 0.45
   B. (0.3545 in parallel with 0.45) = 0.1983 pu
   C. 0.0545
   D. 0.2 + 0.1
   Answer: B. The G1 branch (0.2+0.1+0.0545) and the G2 branch (0.15+0.3) are in parallel; Z2 equals Z1. (Key point: Positive-sequence Thevenin)

3. In the zero-sequence network at bus 3, the G2 side path is:
   A. Isolated by T2 delta; bus 3 grounds through T2 star plus 3Xn (0.33 pu)
   B. G2's X0 only
   C. Open circuit
   D. Zero
   Answer: A. T2's grounded star on the line side gives j(0.15 + 3x0.06) = j0.33 to reference; G2 is behind the delta. (Key point: Zero network)

## Related in Power System Analysis II

- [L-L fault current in kA at bus 3](https://www.bctengineer.com/question.md?key=semester_5%2Fpower_system_analysis_ii%3All-fault-bus3-ka) — Power System Analysis II, chapter 5
- [SLG fault at bus 3, currents and voltages](https://www.bctengineer.com/question.md?key=semester_5%2Fpower_system_analysis_ii%3Aslg-fault-bus3-three-generators) — Power System Analysis II, chapter 5
- [DLG fault at bus 2, fault MVA](https://www.bctengineer.com/question.md?key=semester_5%2Fpower_system_analysis_ii%3Adlg-fault-bus2-sequence-networks) — Power System Analysis II, chapter 5
- [L-G fault at bus 1 through Zf](https://www.bctengineer.com/question.md?key=semester_5%2Fpower_system_analysis_ii%3Alg-fault-bus1-parallel-lines) — Power System Analysis II, chapter 5
- [LLG fault sequence currents at bus 3](https://www.bctengineer.com/question.md?key=semester_5%2Fpower_system_analysis_ii%3Allg-fault-bus3-sequence-currents) — Power System Analysis II, chapter 5
- [Zero sequence Thevenin impedance at bus 2](https://www.bctengineer.com/question.md?key=semester_5%2Fpower_system_analysis_ii%3Azero-sequence-thevenin-bus2) — Power System Analysis II, chapter 4

## Related in other subjects

- [Differential protection: 11 kV, 100 MVA generator](https://www.bctengineer.com/question.md?key=semester_6%2Fswitchgear_and_protection%3Agenerator-differential-11kv-6-ohm) — Switchgear and Protection, chapter 7
- [Fault level: two 25 MVA generators, 50% reduction](https://www.bctengineer.com/question.md?key=semester_7%2Fpower_plant_equipment%3Afault-two-25mva-50-percent) — Power Plant Equipment, chapter 4
- [Fault level: four 25 MVA generators, bus reactor](https://www.bctengineer.com/question.md?key=semester_7%2Fpower_plant_equipment%3Afault-four-25mva-bus-reactor) — Power Plant Equipment, chapter 4
- [Impedance diagram, 100 MVA 132 kV base, with load](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3Aimpedance-diagram-100mva-132kv-load) — Power System Analysis I, chapter 3