title: "Current carrying capacity of cable"
subject: "Industrial Power Distribution and Illumination"
chapter: 3
key: "semester_6/industrial_power_distribution_and_illumination:cable-current-capacity-factors"
source: https://www.bctengineer.com/q/semester_6/industrial_power_distribution_and_illumination/cable-current-capacity-factors
site: BCT Engineering
---

# Current carrying capacity of cable

Industrial Power Distribution and Illumination · Chapter 3: Power Carrying Devices

- Asked in: 2073 Magh, 8 marks
- Video: [How to calculate current carrying capacity of the cable](https://www.youtube.com/watch?v=2Awciz5iHE0) — Tech Doct
- Answer checked by Claude Opus 5.5 (high effort) on 2026-10-14
- Page: https://www.bctengineer.com/q/semester_6/industrial_power_distribution_and_illumination/cable-current-capacity-factors
- Whole chapter: https://www.bctengineer.com/md/semester_6/industrial_power_distribution_and_illumination/chapter-3

## Question

Define current carrying capacity of cable. Write down the factors that affect the current carrying capacity of cable. Describe the method of calculation while determining the size of 3.5 core cable.

## Short answer

Current carrying capacity is the max continuous current a cable can carry within its temperature limit. Factors: conductor material/size, insulation, ambient temp, grouping, installation method, laying depth, soil resistivity, harmonics. To size a 3.5 core cable, calculate full-load current, derate using product of correction factors, select tabulated rating ≥ derated current, then check voltage drop and short-circuit withstand.

## Answer

#### Current carrying capacity
The **current carrying capacity (ampacity)** of a cable is the maximum continuous current it can carry under given installation conditions without the conductor exceeding its permissible temperature (70 °C for PVC, 90 °C for XLPE insulation).

#### Factors affecting current carrying capacity
1. **Conductor material and size:** copper carries about 1.3 times the current of aluminium of the same size; larger area gives lower resistance.
2. **Type of insulation:** XLPE (90 °C) allows more current than PVC (70 °C).
3. **Ambient temperature (air or ground):** a higher ambient leaves less temperature margin, so the rating is reduced.
4. **Grouping:** cables laid close together heat each other; derating factors apply for the number of cables and their spacing.
5. **Method of installation:** in air, on trays, in conduit, in ducts or buried directly; each method dissipates heat differently.
6. **Depth of laying:** deeper cables dissipate heat less well.
7. **Thermal resistivity of soil:** dry or sandy soil conducts heat poorly, lowering the rating.
8. **Number of loaded cores and harmonics:** harmonic currents (e.g. from drives) load the neutral and increase heating.
9. **Load cycle:** cables with cyclic loads can be rated higher than continuous ones.

#### Method of sizing a 3.5 core cable
1. **Find the full-load current:**
```text
I = P / (√3 × V × cos φ × η)
```
2. **Find the total derating factor** (product of temperature, grouping, depth and soil factors from the standard/maker's tables).
3. **Required tabulated rating** = I / derating factor. Select the smallest size whose rating is equal to or greater than this.
4. **Check voltage drop:**
```text
VD = √3 × I × L × (R cos φ + X sin φ)
```
It should normally be within about 5% (often 3% for motor feeders).
5. **Check short-circuit withstand:** A ≥ I_sc × √t / k (k = 115 for Cu PVC, 76 for Al PVC, 94 for Al XLPE).
6. Choose the size that meets all three conditions; the neutral is half size (3.5 core).

#### Example
A 75 kW, 400 V motor, cos φ = 0.85, η = 0.92, fed by a 100 m Al PVC armoured cable buried in ground. Derating: temperature 0.89, grouping 0.8. Fault level 10 kA for 0.2 s.

```text
I = 75000 / (1.732×400×0.85×0.92) = 138.4 A
Total derating = 0.89 × 0.8      = 0.712
Required rating = 138.4 / 0.712  = 194.4 A
```
From the manufacturer's table, a **3.5 × 120 mm² Al** armoured cable (rating about 215 A in ground, R ≈ 0.32 Ω/km, X ≈ 0.07 Ω/km) is selected. (Exact ratings vary by maker.)

```text
VD = 1.732 × 138.4 × 0.1 × (0.32×0.85 + 0.07×0.527)
   = 7.41 V  = 1.85 % of 400 V   (OK, < 5%)
Short circuit: A ≥ 10000 × √0.2 / 76 = 58.8 mm²  (OK)
```
**Answer: 3.5 × 120 mm² Al armoured cable** satisfies current, voltage drop and short-circuit conditions.

## Check yourself

The answer's key points as multiple-choice questions, with the correct option and why.

1. What is the current carrying capacity of a cable?
   A. The current at which the cable melts
   B. The maximum voltage the cable can withstand
   C. The short-circuit current for 1 second
   D. The maximum continuous current without the conductor exceeding its permissible temperature (70 C for PVC, 90 C for XLPE)
   Answer: D. Ampacity is limited by conductor temperature under the given installation conditions. (Key point: Definition of ampacity)

2. Which change reduces the current carrying capacity of a buried cable?
   A. Dry sandy soil with high thermal resistivity, or cables grouped closely together
   B. Using XLPE instead of PVC insulation
   C. Using a larger conductor area
   D. Lower ambient temperature
   Answer: A. Poor heat dissipation (soil, grouping, depth, high ambient) lowers the rating; XLPE and larger area raise it. (Key point: Factors affecting rating)

3. After finding the full-load current, how is the tabulated rating required determined?
   A. Multiply the load current by the derating factor
   B. Divide the load current by the total derating factor (product of temperature, grouping, depth, soil factors)
   C. Add the derating factors to the load current
   D. Divide the load current by the power factor only
   Answer: B. Required rating = I / derating factor, then pick the smallest size with equal or greater rating. (Key point: Sizing procedure)

4. Besides current rating, which two checks must the chosen cable pass?
   A. Only insulation colour and drum length
   B. Earth resistance and lightning impulse level
   C. Voltage drop (about 5%, 3% for motor feeders) and short-circuit withstand A >= Isc x sqrt(t) / k
   D. Harmonic distortion and cable weight only
   Answer: C. The cable size must satisfy current, voltage drop and short-circuit conditions. (Key point: Checks after selection)

## Related in Industrial Power Distribution and Illumination

- [Conductor sizing factors and armoured cable](https://www.bctengineer.com/question.md?key=semester_6%2Findustrial_power_distribution_and_illumination%3Aconductor-size-factors-armoured) — Industrial Power Distribution and Illumination, chapter 3
- [3.5 core cable for 60 A over 200 m](https://www.bctengineer.com/question.md?key=semester_6%2Findustrial_power_distribution_and_illumination%3Acable-60a-200m) — Industrial Power Distribution and Illumination, chapter 5
- [Cable size MDB to SDB1 (80 kW) and SDB2 (10 kW)](https://www.bctengineer.com/question.md?key=semester_6%2Findustrial_power_distribution_and_illumination%3Acable-mdb-sdb-80kw-10kw) — Industrial Power Distribution and Illumination, chapter 5, asked 5×
- [Cable size MDB to SDB1 (70 kW) and SDB2 (90 kW)](https://www.bctengineer.com/question.md?key=semester_6%2Findustrial_power_distribution_and_illumination%3Acable-mdb-sdb-70kw-90kw) — Industrial Power Distribution and Illumination, chapter 5, asked 5×
- [Cable size MDB to SDB-1 (60 kW) and SDB-2 (75 kW)](https://www.bctengineer.com/question.md?key=semester_6%2Findustrial_power_distribution_and_illumination%3Acable-mdb-sdb-60kw-75kw) — Industrial Power Distribution and Illumination, chapter 5, asked 4×
- [How cable size is chosen in an installation](https://www.bctengineer.com/question.md?key=semester_6%2Findustrial_power_distribution_and_illumination%3Acable-size-chosen-installation) — Industrial Power Distribution and Illumination, chapter 5, asked 2×

## Related in other subjects

- [Fusing current and current carrying capacity](https://www.bctengineer.com/question.md?key=semester_6%2Fswitchgear_and_protection%3Afusing-current-carrying-capacity) — Switchgear and Protection, chapter 3
- [Methods of determining bearing capacity](https://www.bctengineer.com/question.md?key=semester_6%2Fbuilding_technology%3Abc-determination-methods) — Building Technology, chapter 2, asked 2×
- [Factors while routing signal traces on PCB](https://www.bctengineer.com/question.md?key=semester_5%2Finstrumentation_ii%3Aroute-factors) — Instrumentation II, chapter 8, asked 4×
- [Highway capacity; factors affecting capacity and LOS](https://www.bctengineer.com/question.md?key=semester_7%2Ftransportation_engineering_ii%3Ahighway-capacity-factors-level-of-service) — Transportation Engineering II, chapter 1