title: "Drawing hall 40 × 25 × 6 m, 2×36 W fluorescent"
subject: "Industrial Power Distribution and Illumination"
chapter: 7
key: "semester_6/industrial_power_distribution_and_illumination:drawing-hall-2x36w-fluorescent"
source: https://www.bctengineer.com/q/semester_6/industrial_power_distribution_and_illumination/drawing-hall-2x36w-fluorescent
site: BCT Engineering
---

# Drawing hall 40 × 25 × 6 m, 2×36 W fluorescent

Industrial Power Distribution and Illumination · Chapter 7: Illumination Design Principles

- Asked in: 2070 Magh, 8 marks
- Video: [How to solve illumination problem's !! question from  VTU QP !! By Sharan Sir!!](https://www.youtube.com/watch?v=-pIazs-fjYs) — Knowledge center
- Answer checked by Claude Opus 5.5 (high effort) on 2026-10-14
- Page: https://www.bctengineer.com/q/semester_6/industrial_power_distribution_and_illumination/drawing-hall-2x36w-fluorescent
- Whole chapter: https://www.bctengineer.com/md/semester_6/industrial_power_distribution_and_illumination/chapter-7

## Question

A drawing hall 40m×25m×6m height is to be illuminated with 2×36W fluorescent lamp to an average illumination of 90 Lm/m² on a working plane 1 m above the floor. Estimate suitable numbers, sizes of lamps. Mounting height 1m below the ceiling. Sketch the spacing layout. Assume: coefficient of utilization 0.8 depreciation factor 1.2, space height ratios 1.4 and the lamp efficiency is 60lumen/watt.

## Short answer

With mounting height 4 m above working plane, lumen method yields 31.3 but spacing limit 5.6 m requires 8×5=40 luminaires of 2×36 W, spaced 5 m both ways, giving 115.2 lux average illuminance.

## Answer

**Given:** hall 40 m × 25 m × 6 m, E = 90 lm/m² on a plane 1 m above floor, 2 × 36 W fluorescent (72 W per luminaire) at 60 lm/W, CU = 0.8, depreciation factor 1.2, SHR = 1.4, luminaires 1 m below ceiling.

Mounting height above working plane: Hm = (6 − 1) − 1 = **4 m**.

#### Number of luminaires

Lumen method: N = (E × A) / (φ × UF × MF), where φ is the output of one luminaire.

```text
Area A        = 40 × 25 = 1000 m²
φ per luminaire = 72 W × 60 lm/W = 4320 lm
MF            = 1/DF = 1/1.2 = 0.833
Total lumens  = E × A × DF / UF
              = 90 × 1000 × 1.2 / 0.8
              = 135000 lm
N             = 135000 / 4320 = 31.25
```

Rounding up and fitting a regular grid: **8 × 5 = 40 luminaires** (8 along the 40 m side, 5 along the 25 m side).

#### Arrangement and spacing

```text
Spacing along length = 40/8 = 5 m
Spacing along width  = 25/5 = 5 m
End spacing (to wall) = half of these
Max spacing = SHR × Hm = 1.4 × 4 = 5.6 m
5 m and 5 m ≤ 5.6 m  → OK
Actual E = 40 × 4320 × 0.8 × 0.833 / 1000
         = 115.2 lux (≥ 90 lux required)
```

The lumen calculation needs only 32 luminaires, but the 5.6 m spacing limit governs: 40/5.6 = 7.1 → 8 luminaires along the length and 25/5.6 = 4.5 → 5 across the width. A 7 × 5 grid gives 5.71 m spacing (> 5.6 m) and an 8 × 4 grid gives 6.25 m, so both are too wide. So **8 × 5 = 40 luminaires of 2 × 36 W** are used at 5 m × 5 m spacing (2.5 m from the walls). Total load = 40 × 72 = 2880 W.

#### Layout diagram

```text
Plan 40 m × 25 m (o = luminaire)
+-----------------+
| o o o o o o o o |
| o o o o o o o o |
| o o o o o o o o |
| o o o o o o o o |
| o o o o o o o o |
+-----------------+
Spacing between luminaires = 5 m both ways
End spacing to each wall   = 2.5 m
Mounting height: 5 m above floor (Hm = 4 m)
```

## Check yourself

The answer's key points as multiple-choice questions, with the correct option and why.

1. For a 6 m high hall with working plane 1 m above floor and luminaires 1 m below ceiling, what is Hm?
   A. 6 m
   B. 5 m
   C. 4 m
   D. 3 m
   Answer: C. Hm is measured from working plane to luminaire: (6 - 1) - 1 = 4 m. (Key point: Mounting height Hm)

2. Which total lumen requirement is used for E = 90 lux, A = 1000 m^2, CU = 0.8, DF = 1.2?
   A. 90 x 1000 x 0.8 / 1.2 = 60000 lm
   B. 90 x 1000 / (0.8 x 1.2) = 93750 lm
   C. 90 x 1000 x 1.2 / 0.8 = 135000 lm
   D. 90 x 1000 x 1.2 x 0.8 = 86400 lm
   Answer: C. Depreciation factor multiplies the requirement (MF = 1/DF) and CU divides it: 135000 lm. (Key point: Total lumens with depreciation factor)

3. The lumen calculation needs about 32 luminaires, yet 40 are installed. Why?
   A. The spacing limit 5.6 m forces an 8 x 5 grid
   B. Extra luminaires are added as spares
   C. Each luminaire has only 36 W
   D. The room has no walls to reflect light
   Answer: A. A 7 x 5 grid gives 5.71 m and 8 x 4 gives 6.25 m, both above the 5.6 m maximum, so 8 x 5 = 40 is used. (Key point: Why 40 luminaires not 32)

4. How much light does one 2 x 36 W luminaire give at 60 lm/W?
   A. 2160 lm
   B. 4320 lm
   C. 72 lm
   D. 8640 lm
   Answer: B. 72 W x 60 lm/W = 4320 lm per luminaire. (Key point: Luminaire output)

## Related in Industrial Power Distribution and Illumination

- [Drawing hall 40 × 25 × 6 m, 90 lm/m² LED](https://www.bctengineer.com/question.md?key=semester_6%2Findustrial_power_distribution_and_illumination%3Adrawing-hall-40x25-90lux-led) — Industrial Power Distribution and Illumination, chapter 7, asked 2×
- [Drawing hall 40 × 25 × 6 m, 250 lux LED](https://www.bctengineer.com/question.md?key=semester_6%2Findustrial_power_distribution_and_illumination%3Adrawing-hall-40x25-250lux) — Industrial Power Distribution and Illumination, chapter 7, asked 3×
- [Drawing hall 40 × 20 × 6 m lighting design](https://www.bctengineer.com/question.md?key=semester_6%2Findustrial_power_distribution_and_illumination%3Adrawing-hall-40x20-led) — Industrial Power Distribution and Illumination, chapter 7, asked 2×
- [Factory hall 55.75 m × 40.25 m LED lighting](https://www.bctengineer.com/question.md?key=semester_6%2Findustrial_power_distribution_and_illumination%3Afactory-hall-led-55x40) — Industrial Power Distribution and Illumination, chapter 7, asked 4×
- [Conference hall 2×36 W CFL lighting](https://www.bctengineer.com/question.md?key=semester_6%2Findustrial_power_distribution_and_illumination%3Aconference-hall-cfl) — Industrial Power Distribution and Illumination, chapter 7
- [Process room 40 × 20 m twin 40 W fluorescent](https://www.bctengineer.com/question.md?key=semester_6%2Findustrial_power_distribution_and_illumination%3Aprocess-room-40x20-fluorescent) — Industrial Power Distribution and Illumination, chapter 7, asked 2×