# Purpose of earthing, earthed vs unearthed system

Industrial Power Distribution and Illumination · Chapter 2: Earthing

- Asked in: 2074 Bhadra, 4 marks
- Video: [Earthing Systems Explained: TT, TN-S, TN-C, TN-C-S & IT (Complete Guide)](https://www.youtube.com/watch?v=PYCH4yRwbAk) — Gaurav J - TheElectricalGuy
- Answer checked by Claude Opus 5.5 (high effort) on 2026-10-14
- Page: https://www.bctengineer.com/q/semester_6/industrial_power_distribution_and_illumination/earthing-purpose-earthed-unearthed
- Whole chapter: https://www.bctengineer.com/md/semester_6/industrial_power_distribution_and_illumination/chapter-2

## Question

What is the major purpose of earthing? Describe the consequences of earth and unearthed system.

## Short answer

The major purpose is to protect people by keeping enclosures near earth potential and to ensure fast fault clearance. In an earthed system, a fault causes a large current that trips protection, while an unearthed system allows supply to continue but causes healthy phases to rise to line voltage and may produce transient overvoltages.

## Answer

#### Major purpose of earthing
Earthing connects the system neutral and the exposed metal parts of equipment to earth through a low-resistance path. Its main purposes are:
- **Safety of persons:** keeps metal bodies near earth potential so a fault does not cause a dangerous shock.
- **Quick fault clearance:** a large earth-fault current makes fuses, MCBs and relays trip quickly.
- **Stable system voltage:** the earthed neutral fixes phase-to-earth voltage and limits overvoltages.
- **Safe discharge of lightning and static charges.**

#### Consequences of earthed and unearthed systems

| Point | Earthed system | Unearthed system |
|---|---|---|
| Fault current on first earth fault | Large; protection trips | Very small (capacitive); nothing trips |
| Shock risk | Low; faulty part isolated fast | Healthy phases rise to line voltage; shock risk from second fault |
| Voltage of healthy phases | Stays near phase voltage | Rises to √3 × phase voltage |
| Overvoltages | Limited | Arcing ground gives transient overvoltages up to 5–6 times normal |
| Fault location | Easy (relay shows faulty feeder) | Difficult |
| Continuity of supply | Feeder trips on first fault | Supply can continue after one fault |
| Insulation needed | Phase voltage level | Line voltage level (costlier) |

**Summary:** an earthed system is safer and is used for almost all LV industrial and building installations. An unearthed system gives continuity during a single fault, but causes overvoltage, insulation stress, arcing grounds and hidden faults, so it is used only in special cases (some mines and process plants with insulation monitoring).

## Check yourself

The answer's key points as multiple-choice questions, with the correct option and why.

1. How does earthing help fuses and MCBs clear faults quickly?
   A. It reduces the supply voltage
   B. It gives a large earth-fault current that makes protection trip
   C. It removes the load
   D. It blocks leakage current
   Answer: B. A low-resistance earth path allows a large fault current, so the protective device operates fast. (Key point: Quick fault clearance)

2. In an unearthed system with a first earth fault, what happens to the healthy phases?
   A. They fall to zero
   B. They stay at phase voltage
   C. They rise to sqrt(3) times the phase voltage, i.e. line voltage
   D. They rise to 5 times phase voltage permanently
   Answer: C. With one phase at earth potential, the other phases rise to line voltage relative to earth. (Key point: Healthy phase voltage)

3. Which problem is specific to the unearthed system?
   A. Fault current is large
   B. Arcing ground causing transient overvoltages up to 5-6 times normal
   C. Easy fault location
   D. Supply is lost on the first fault
   Answer: B. Arcing grounds in an unearthed system create severe transient overvoltages and the fault is hard to locate. (Key point: Arcing ground)

## Related in Industrial Power Distribution and Illumination

- [Earthing purpose and points to be earthed](https://www.bctengineer.com/question.md?key=semester_6%2Findustrial_power_distribution_and_illumination%3Aearthing-purpose-points-earthed) — Industrial Power Distribution and Illumination, chapter 2, asked 2×
- [Earth resistance factors and rod earthing diameter](https://www.bctengineer.com/question.md?key=semester_6%2Findustrial_power_distribution_and_illumination%3Aearth-resistance-rod-diameter) — Industrial Power Distribution and Illumination, chapter 2
- [Equipment earthing objective and earth resistance factors](https://www.bctengineer.com/question.md?key=semester_6%2Findustrial_power_distribution_and_illumination%3Aearthing-objective-factors) — Industrial Power Distribution and Illumination, chapter 2, asked 2×
- [Reducing earth resistance and pipe earthing](https://www.bctengineer.com/question.md?key=semester_6%2Findustrial_power_distribution_and_illumination%3Areduce-earth-resistance-pipe-earthing) — Industrial Power Distribution and Illumination, chapter 2
- [Earth resistance factors and lightning arrester earthing](https://www.bctengineer.com/question.md?key=semester_6%2Findustrial_power_distribution_and_illumination%3Aearth-resistance-lightning-arrester) — Industrial Power Distribution and Illumination, chapter 2
- [Low earth resistance and equipment earthing methods](https://www.bctengineer.com/question.md?key=semester_6%2Findustrial_power_distribution_and_illumination%3Alow-earth-resistance-methods) — Industrial Power Distribution and Illumination, chapter 2

## Related in other subjects

- [Chemical earthing and earth resistance](https://www.bctengineer.com/question.md?key=semester_6%2Fswitchgear_and_protection%3Achemical-earthing-resistance) — Switchgear and Protection, chapter 5
- [Improper earthing and system grounding practice](https://www.bctengineer.com/question.md?key=semester_8%2Fhigh_voltage_engineering%3Aimproper-earthing-system-grounding) — High Voltage Engineering, chapter 2
- [Short note: Earthing system](https://www.bctengineer.com/question.md?key=semester_1%2Fbasic_electrical_and_electronics_engineering%3Ashort-note-earthing-system) — Basic Electrical and Electronics Engineering, chapter 4
- [Major advantages of per unit system](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3Aper-unit-major-advantages) — Power System Analysis I, chapter 3