# Short note: Factor of maximum utilization Ku

Industrial Power Distribution and Illumination · Chapter 1: Introduction

- Asked in: 2073 Bhadra, 2 marks
- Video: [6. DIVERSITY FACTOR, COINCIDENCE FACTOR,  CAPACITY , UTILISATION  FACTOR  & PLANT USE FACTOT](https://www.youtube.com/watch?v=TWDcwSwv504) — Electrical Tutorial
- Answer checked by Claude Opus 5.5 (high effort) on 2026-10-14
- Page: https://www.bctengineer.com/q/semester_6/industrial_power_distribution_and_illumination/short-note-ku
- Whole chapter: https://www.bctengineer.com/md/semester_6/industrial_power_distribution_and_illumination/chapter-1

## Question

Write a short note on factor of maximum utilization (Ku).

## Short answer

Factor of maximum utilization (ku) = actual maximum power used / rated power (ku ≤ 1). Accounts for equipment not running at full rating (e.g., motors at 0.75, lighting/heating at 1). Applied per load before simultaneity factor ks. Example: 10 kVA motor with ku=0.75 counted as 7.5 kVA for board demand calculation.

## Answer

The **factor of maximum utilization (ku)** is the ratio of the maximum power actually taken by a load in normal operation to its rated (installed) power:

```text
ku = Actual maximum power used / Rated power   (ku ≤ 1)
```

It is used in industrial load estimation (IEC method) because equipment rarely runs at full rating. For example, a motor is chosen with a margin and usually runs at about 75% of its rating.

**Typical values:**
- Motors in industry: ku ≈ 0.75
- Incandescent lighting and heating: ku = 1
- Socket outlets: depends on what is plugged in

**Example:** a 10 kVA motor with ku = 0.75 is counted as 7.5 kVA when the demand of its distribution board is worked out. ku is applied to each individual load, before the factor of simultaneity ks is applied to groups.

## Check yourself

The answer's key points as multiple-choice questions, with the correct option and why.

1. What is the factor of maximum utilization?
   A. Ratio of group MD to sum of individual MDs
   B. Ratio of average to maximum demand
   C. Ratio of connected load to MD
   D. Ratio of the maximum power a load actually takes to its rated power
   Answer: D. ku = actual maximum power used / rated power, at most 1. (Key point: Definition of ku)

2. Which typical ku values are used?
   A. Motors 1; lighting 0.75
   B. Motors 0.2; lighting 0.2
   C. Motors about 0.75; incandescent lighting and heating 1
   D. All loads 0.5
   Answer: C. Motors usually run below rating, while lighting and heating run at full rating. (Key point: Typical values)

3. A 10 kVA motor with ku = 0.75 is counted as how much?
   A. 13.3 kVA
   B. 7.5 kVA
   C. 10.75 kVA
   D. 0.75 kVA
   Answer: B. 10 x 0.75 = 7.5 kVA. (Key point: Example)

## Related in Industrial Power Distribution and Illumination

- [Selecting distribution transformer size using Ku and Ks](https://www.bctengineer.com/question.md?key=semester_6%2Findustrial_power_distribution_and_illumination%3Atransformer-size-ku-ks) — Industrial Power Distribution and Illumination, chapter 4, asked 3×
- [Load factor and demand factor numerical](https://www.bctengineer.com/question.md?key=semester_6%2Findustrial_power_distribution_and_illumination%3Aconsumer-load-demand-factor) — Industrial Power Distribution and Illumination, chapter 1
- [Connected load, MD, demand, diversity, load factor](https://www.bctengineer.com/question.md?key=semester_6%2Findustrial_power_distribution_and_illumination%3Aload-terminology-five-terms) — Industrial Power Distribution and Illumination, chapter 1
- [Demand factor and diversity factor of substation](https://www.bctengineer.com/question.md?key=semester_6%2Findustrial_power_distribution_and_illumination%3Aload-centre-demand-diversity-numerical) — Industrial Power Distribution and Illumination, chapter 1
- [Connected load, MD, demand factor, load factor](https://www.bctengineer.com/question.md?key=semester_6%2Findustrial_power_distribution_and_illumination%3Adefine-connected-load-md-df-lf) — Industrial Power Distribution and Illumination, chapter 1
- [Most economical power factor for 50 kW factory](https://www.bctengineer.com/question.md?key=semester_6%2Findustrial_power_distribution_and_illumination%3Aoptimum-pf-50kw-factory) — Industrial Power Distribution and Illumination, chapter 10

## Related in other subjects

- [Ku-band HEMT amplifier: stability and gains](https://www.bctengineer.com/question.md?key=semester_7%2Frf_and_microwave_engineering%3Aku-band-hemt-amplifier) — RF and Microwave Engineering, chapter 6
- [Load, capacity and utilization factors](https://www.bctengineer.com/question.md?key=semester_7%2Fhydropower_engineering%3Aload-capacity-utilization-factor-220gwh) — Hydropower Engineering, chapter 3
- [Arc furnace power factor and time to melt steel](https://www.bctengineer.com/question.md?key=semester_7%2Futilization_of_electrical_energy%3Aarc-furnace-pf-melting-time-steel) — Utilization of Electrical Energy, chapter 5
- [Maximum speed and distance before braking (2.5 km)](https://www.bctengineer.com/question.md?key=semester_7%2Futilization_of_electrical_energy%3Amax-speed-50kmph-2-5km-trapezoidal) — Utilization of Electrical Energy, chapter 4