# Distribution substation with single line diagram

Industrial Power Distribution and Illumination · Chapter 4: Distribution Substation of Industrial Plant

- Asked in: 2070 Magh, 8 marks
- Video: [How to make Low Voltage distribution single line drawing (SLD )and calculation (11KV Substation)](https://www.youtube.com/watch?v=yEG6V4eXxHA) — electrical mastar
- Answer checked by Claude Opus 5.5 (high effort) on 2026-10-14
- Page: https://www.bctengineer.com/q/semester_6/industrial_power_distribution_and_illumination/sld-distribution-substation
- Whole chapter: https://www.bctengineer.com/md/semester_6/industrial_power_distribution_and_illumination/chapter-4

## Question

With the help of single line diagram, explain the distribution substation in an industry.

## Short answer

11 kV supply comes via LA, isolator, VCB/DO fuse with O/C & E/F relays, HT metering, to 11/0.4 kV Dyn11 transformer. LT side: ACB incomer, MDB busbar with MCCBs feeding SDBs for motors/lighting, and APFC panel. Provides step-down, switching, protection, metering, and power factor correction.

## Answer

A distribution substation in an industry receives power from the utility at 11 kV, steps it down to 400/230 V and distributes it to the shops through switchgear and protective devices. It is the heart of the plant's electrical system.

#### Single line diagram
```text
 11 kV overhead line / cable (NEA)
            |
        [LA]   lightning arresters
            |
        [AB]   gang-operated isolator
            |
     [DO fuse] or [VCB + O/C, E/F relay]
            |
     [HT metering: CT/PT, kWh, kVA MD]
            |
        (TR)   11/0.4 kV, Dyn11
            |      neutral & body earthed
        [ACB/MCCB] LT incomer + meters
            |
 ====== MDB 400 V, 3-ph 4-wire busbar ======
    |          |          |          |
  MCCB       MCCB       MCCB      MCCB
    |          |          |          |
  SDB-1      SDB-2      SDB-3    APFC panel
  motors    lighting   sockets   (capacitors)
    |          |          |
 starters    MCB        MCB+RCCB
    |          |          |
  400 V M   230 V      230 V
```

#### Explanation of the parts
1. **Incoming 11 kV supply**: tapped from the utility feeder by overhead line or HT cable.
2. **Lightning arresters**: one per phase, protect the transformer and switchgear from lightning and switching surges by diverting them to earth.
3. **AB switch / isolator**: off-load switch to isolate the whole substation for maintenance.
4. **HT protection**: drop-out fuses for small (pole/H-pole) substations; VCB or SF₆ breaker with overcurrent and earth-fault relays for larger plants.
5. **HT metering**: CTs and PTs feed the trivector/kWh meter for energy and maximum demand billing.
6. **Transformer**: 11/0.4 kV, delta-star (Dyn11). The delta HV winding traps triplen harmonics; the star LV gives 400 V between lines and 230 V phase to neutral. Rating is chosen on maximum demand.
7. **LT incomer (ACB/MCCB)**: main switch and protection against overload and short circuit on the LT side, with ammeter, voltmeter and kWh meter.
8. **Main distribution board (MDB)**: copper/aluminium busbars with outgoing MCCBs or switch-fuse units to each SDB.
9. **APFC panel**: automatic capacitor bank to keep power factor near unity, reducing current, losses and demand charges.
10. **Sub-distribution boards**: near the load centres; feed motors through starters (DOL, star-delta, soft starter) and lighting/socket circuits through MCBs and RCCBs.
11. **Earthing**: separate electrodes for transformer neutral, equipment bodies and lightning arresters.
12. **Standby supply**: a diesel generator with changeover switch (ATS) at the MDB feeds essential loads during outages.

**Types used**: pole/H-pole mounted (up to about 250 kVA), plinth-mounted outdoor (above 250 kVA), indoor or packaged substations where space or environment demands.

## Check yourself

The answer's key points as multiple-choice questions, with the correct option and why.

1. What is the role of the industrial distribution substation?
   A. Receives 11 kV, steps down to 400/230 V and distributes via protective switchgear
   B. Generates power
   C. Converts to DC
   D. Stores energy
   Answer: A. It is the heart of the plant's electrical system. (Key point: Role)

2. Which HT protection suits small versus large plants?
   A. VCB for small; DO fuses for large
   B. Only AB switches
   C. DO fuses for small; VCB/SF6 with O/C and E/F relays for large
   D. Only lightning arresters
   Answer: C. Larger plants need relay-controlled breakers. (Key point: HT protection)

3. What do HT CTs and PTs feed?
   A. A trivector/kWh meter for energy and maximum demand billing
   B. The lightning arresters
   C. The earthing system
   D. The APFC capacitors
   Answer: A. Instrument transformers scale down HT quantities. (Key point: HT metering)

4. How are essential loads supplied during an outage?
   A. The lightning arresters
   B. A second AB switch
   C. A diesel generator with changeover (ATS) at the MDB
   D. Reverse feeding from SDBs
   Answer: C. ATS transfers essential loads. (Key point: Standby supply)

## Related in Industrial Power Distribution and Illumination

- [Importance of distribution substation with SLD](https://www.bctengineer.com/question.md?key=semester_6%2Findustrial_power_distribution_and_illumination%3Adistribution-substation-importance-sld) — Industrial Power Distribution and Illumination, chapter 4
- [Layout of indoor substation with single transformer](https://www.bctengineer.com/question.md?key=semester_6%2Findustrial_power_distribution_and_illumination%3Aindoor-substation-single-transformer) — Industrial Power Distribution and Illumination, chapter 4
- [Single line diagram from 11 kV to end use](https://www.bctengineer.com/question.md?key=semester_6%2Findustrial_power_distribution_and_illumination%3Asld-11kv-to-end-use) — Industrial Power Distribution and Illumination, chapter 4, asked 3×
- [Locating substation and floor distribution board](https://www.bctengineer.com/question.md?key=semester_6%2Findustrial_power_distribution_and_illumination%3Alocate-substation-floor-db) — Industrial Power Distribution and Illumination, chapter 4
- [Distribution substation site selection factors](https://www.bctengineer.com/question.md?key=semester_6%2Findustrial_power_distribution_and_illumination%3Asubstation-site-location-factors) — Industrial Power Distribution and Illumination, chapter 4
- [Types of substation and 11 kV SLD](https://www.bctengineer.com/question.md?key=semester_6%2Findustrial_power_distribution_and_illumination%3Asubstation-types-11kv-sld) — Industrial Power Distribution and Illumination, chapter 4, asked 3×

## Related in other subjects

- [Single line diagram and its significance](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3Asingle-line-diagram-significance) — Power System Analysis I, chapter 3
- [MBI block diagram and advantages in industry](https://www.bctengineer.com/question.md?key=semester_5%2Finstrumentation_ii%3Ambi-block-advantages) — Instrumentation II, chapter 1
- [Single slit diffraction intensity distribution](https://www.bctengineer.com/question.md?key=semester_1%2Fengineering_physics%3Asingle-slit-intensity-distribution) — Engineering Physics, chapter 4, asked 3×
- [Single phase vs 3-phase distribution transformer](https://www.bctengineer.com/question.md?key=semester_8%2Ftransmission_and_distribution_system_design%3Asingle-vs-three-phase-transformer) — Transmission and Distribution System Design, chapter 7, asked 2×