title: "Substation classification and 11 kV schematic"
subject: "Industrial Power Distribution and Illumination"
chapter: 4
key: "semester_6/industrial_power_distribution_and_illumination:substation-classification-11kv-schematic"
source: https://www.bctengineer.com/q/semester_6/industrial_power_distribution_and_illumination/substation-classification-11kv-schematic
site: BCT Engineering
---

# Substation classification and 11 kV schematic

Industrial Power Distribution and Illumination · Chapter 4: Distribution Substation of Industrial Plant

- Asked in: 2073 Magh, 2+6 marks
- Video: [LECTURE-11|| electric substation, classification, comparison.](https://www.youtube.com/watch?v=GAZkun9sGZg) — VISHNU CHANDRAN
- Answer checked by Claude Opus 5.5 (high effort) on 2026-10-14
- Page: https://www.bctengineer.com/q/semester_6/industrial_power_distribution_and_illumination/substation-classification-11kv-schematic
- Whole chapter: https://www.bctengineer.com/md/semester_6/industrial_power_distribution_and_illumination/chapter-4

## Question

Classify the distribution substation of industry according to service and design. Draw and explain the schematic diagram of a distribution substation of a typical industry from 11 kV to end use.

## Short answer

By service: step-down, switching, converting, PFC substations. By design: outdoor (pole/plinth), indoor, compact. Schematic: 11 kV feeder → LA → AB switch → DO fuse → metering → 11/0.4 kV Dyn11 transformer → LT breaker → MDB → MCCBs to SDBs for motors (400 V) and lighting (230 V), plus APFC panel.

## Answer

#### Classification of industrial distribution substations
**According to service**
- Step-down (transformer) substation: 11/0.4 kV or 33/11 kV.
- Switching substation: only switchgear, no transformer.
- Converting substation: AC to DC or frequency conversion.
- Power factor correction substation: capacitor banks.

**According to design**
- Outdoor: pole-mounted (single pole), H-pole (double pole, up to about 250 kVA), plinth-mounted (above 250 kVA).
- Indoor: equipment inside a building.
- Underground and packaged/compact (kiosk) substations.

#### Schematic diagram from 11 kV to end use
```text
 11 kV overhead feeder (utility, NEA)
            |
        [LA]  lightning arresters (3 nos)
            |
        [AB]  air-break / gang-operated isolator
            |
        [DO]  drop-out fuse  (or HT VCB + relay)
            |
        [HT metering CT/PT]  (for HT consumers)
            |
        (TR)  11/0.4 kV, Dyn11 transformer
            |      neutral + body earthed
        [ACB / MCCB]  LT main breaker + LT meter
            |
 ======== MDB  400 V, 3-ph 4-wire busbar ========
     |            |            |            |
   MCCB         MCCB         MCCB         MCCB
     |            |            |            |
   SDB-1        SDB-2        SDB-3       APFC panel
  (motors)    (lighting)    (sockets)   (capacitors)
     |            |            |
   MCB/MPCB      MCB          MCB/RCCB
     |            |            |
   400 V M     230 V lamps   230 V outlets
```

#### Explanation
1. **11 kV incoming** line from the utility feeder.
2. **Lightning arresters** protect the transformer from lightning and switching surges.
3. **AB switch** isolates the substation (off-load) for maintenance.
4. **DO fuse** (or VCB with overcurrent and earth fault relays in bigger plants) protects the transformer from internal faults and overloads.
5. **HT metering** for energy billing of HT consumers.
6. **11/0.4 kV Dyn11 transformer** gives 400 V line and 230 V phase voltage with a solidly earthed neutral.
7. **LT ACB/MCCB** is the main LT switch and protection; LT meters show current, voltage and energy.
8. **MDB** busbars divide power into feeders with MCCBs; an **APFC panel** improves power factor.
9. **SDBs** near each shop feed **motors** (through starters and overload relays) at 400 V and **lighting and sockets** at 230 V through MCBs and RCCBs.
10. **Earthing** of neutral, equipment bodies and arresters completes the system.

## Check yourself

The answer's key points as multiple-choice questions, with the correct option and why.

1. Which is a classification by service?
   A. Pole, plinth and underground
   B. Step-down, switching, converting and power factor correction substations
   C. Indoor and outdoor only
   D. Single-phase and three-phase
   Answer: B. Pole, plinth, indoor and underground relate to design. (Key point: Classification by service)

2. What size separates H-pole from plinth-mounted substations?
   A. About 25 kVA
   B. About 1000 kVA
   C. About 50 kVA
   D. About 250 kVA
   Answer: D. H-pole up to 250 kVA, plinth above 250 kVA. (Key point: H-pole and plinth sizes)

## Related in Industrial Power Distribution and Illumination

- [Single line diagram from 11 kV to end use](https://www.bctengineer.com/question.md?key=semester_6%2Findustrial_power_distribution_and_illumination%3Asld-11kv-to-end-use) — Industrial Power Distribution and Illumination, chapter 4, asked 3×
- [Substation classification and indoor substation](https://www.bctengineer.com/question.md?key=semester_6%2Findustrial_power_distribution_and_illumination%3Asubstation-classify-indoor) — Industrial Power Distribution and Illumination, chapter 4
- [Distribution substation with single line diagram](https://www.bctengineer.com/question.md?key=semester_6%2Findustrial_power_distribution_and_illumination%3Asld-distribution-substation) — Industrial Power Distribution and Illumination, chapter 4
- [Types of substation and 11 kV SLD](https://www.bctengineer.com/question.md?key=semester_6%2Findustrial_power_distribution_and_illumination%3Asubstation-types-11kv-sld) — Industrial Power Distribution and Illumination, chapter 4, asked 3×
- [Classification of industrial distribution substations](https://www.bctengineer.com/question.md?key=semester_6%2Findustrial_power_distribution_and_illumination%3Asubstation-classification-service-design) — Industrial Power Distribution and Illumination, chapter 4, asked 2×
- [Importance of distribution substation with SLD](https://www.bctengineer.com/question.md?key=semester_6%2Findustrial_power_distribution_and_illumination%3Adistribution-substation-importance-sld) — Industrial Power Distribution and Illumination, chapter 4

## Related in other subjects

- [Design: 100 kVA 11/132 kV transformer with winding data](https://www.bctengineer.com/question.md?key=semester_5%2Felectric_machine_design%3Adesign-100kva-11-132kv) — Electric Machine Design, chapter 3, asked 3×
- [Capacitor size, four-node 11 kV feeder](https://www.bctengineer.com/question.md?key=semester_8%2Ftransmission_and_distribution_system_design%3Acapacitor-size-four-node-feeder) — Transmission and Distribution System Design, chapter 7, asked 5×
- [Design: 500 kVA 66/11 kV power transformer](https://www.bctengineer.com/question.md?key=semester_5%2Felectric_machine_design%3Adesign-500kva-66-11kv) — Electric Machine Design, chapter 3, asked 6×
- [Design: 4000 kVA 66/11 kV power transformer](https://www.bctengineer.com/question.md?key=semester_5%2Felectric_machine_design%3Adesign-4000kva-66-11kv) — Electric Machine Design, chapter 3, asked 5×