# Percentage differential protection of alternator

Switchgear and Protection · Chapter 7: Protective Relays

- Asked in: 2070 Bhadra, 8 marks; 2073 Bhadra, 8 marks (asked 2 times)
- Video: [SGP412 Simple Differential Protection of Alternators](https://www.youtube.com/watch?v=Or79KmTrbx0) — Lectures in Electrical Engineering
- Answer checked by Claude Opus 5.5 (high effort) on 2026-10-14
- Page: https://www.bctengineer.com/q/semester_6/switchgear_and_protection/alternator-percentage-differential
- Whole chapter: https://www.bctengineer.com/md/semester_6/switchgear_and_protection/chapter-7

## Question

Explain with a neat sketch the percentage differential protection of an alternator.

## Short answer

Percentage differential protection compares currents at both ends of stator winding. A restraining coil carries through current, while an operating coil carries the difference. It trips when differential current exceeds a set percentage of through current, providing stability against CT errors during external faults and sensitivity for internal faults.

## Answer

**Percentage (biased) differential protection** of an alternator compares the current entering and leaving each phase winding; it trips when the difference exceeds a fixed percentage of the through current. It protects the stator against phase-to-phase and phase-to-earth faults (Merz-Price scheme with bias).

#### Why "percentage" (biased) is needed
In a simple differential (circulating current) scheme, the two CTs of a phase never match perfectly. During heavy external faults, CT saturation and ratio errors make a spill current flow in the relay, which can cause a false trip. A **restraining (bias) coil** carrying the through current raises the operating current in proportion to the load, so the relay stays stable on external faults but is sensitive to internal faults.

#### Arrangement

```text
 Neutral side                     Line side
   CT1  ┌──── stator winding ────┐  CT2
 ──(○)──┤                        ├──(○)──► to bus
   │ I₁                        I₂ │
   │                              │
   └──R/2──┬───────────┬──R/2────┘
           │ restraining coil R  │
           └────► O ◄─────────────┘
           operating coil (mid-point)
 (one such set per phase; star point of
  CTs connected to the relay neutral)
```

- Identical CTs are placed at the neutral end and the line end of each phase winding.
- CT secondaries are connected so that their currents circulate in the pilot wires.
- The **restraining coil** is connected in the pilot wires (carries (I₁ + I₂)/2).
- The **operating coil** is connected between the mid-point of the restraining coil and the CT star point (carries I₁ − I₂).

#### Operation
- **Normal load or external fault:** I₁ = I₂, so the operating coil current is nearly zero. Any small spill current due to CT mismatch is overcome by the large restraining torque.
- **Internal fault:** current in the faulty winding differs at the two ends (or one end gets reversed current when the generator is in parallel with others). A large differential current I₁ − I₂ flows in the operating coil, its torque exceeds the restraining torque and the relay trips the generator breaker and field breaker.

**Operating condition:**

```text
|I₁ − I₂| > K × (|I₁| + |I₂|)/2  + I₀
K = bias slope (typically 5–20%), I₀ = minimum pick-up
```

#### Characteristic

```text
 Operating  │        /  Trip zone
 current    │       /
 |I₁−I₂|    │      /  slope K
            │     /
            │____/   No-trip (restrain) zone
            └──────────────────────
              through current (I₁+I₂)/2
```

#### Features
- Protects about 85–90% of the winding against earth faults (when neutral is earthed through resistance, faults near the neutral give little current); a separate restricted earth fault or 100% stator earth fault relay covers the rest.
- Fast, selective; unaffected by load or external faults.
- Needs CTs of identical characteristics; pilot wires are short since both CTs are near the machine.

## Check yourself

The answer's key points as multiple-choice questions, with the correct option and why.

1. Why is a restraining (bias) coil used in the differential protection of an alternator?
   A. To make the relay slower on internal faults
   B. To stop false tripping from CT mismatch/saturation spill current during heavy external faults
   C. To increase the CT ratio
   D. To supply the field breaker
   Answer: B. CT errors and saturation cause spill current on external faults; the restraining coil raises the operating threshold in proportion to through current so the relay stays stable. (Key point: Why bias is needed)

2. In the scheme described, which currents do the operating coil and restraining coil carry?
   A. Operating: (I1+I2)/2; restraining: I1-I2
   B. Both carry I1 only
   C. Operating: I1-I2; restraining: (I1+I2)/2
   D. Operating: I1+I2; restraining: I1-I2
   Answer: C. The operating coil carries the difference I1-I2 and the restraining coil carries the through (average) current (I1+I2)/2. (Key point: Operating and restraining coils)

3. What happens in the relay for an external fault compared with an internal fault?
   A. External: large operating current, trips; internal: restrains
   B. External: I1 = I2 so operating current is near zero and restraint dominates; internal: large I1-I2 exceeds restraint and trips
   C. Both cases give identical operating current
   D. External fault trips only the field breaker
   Answer: B. For through faults the two CT currents are equal so there is almost no operating current; for internal faults the difference is large and the operating torque exceeds the restraining torque. (Key point: Behaviour on external vs internal fault)

4. The operating condition |I1-I2| > K(|I1|+|I2|)/2 + I0 means that:
   A. The relay trips when the difference exceeds a percentage (slope K) of the through current plus a minimum pick-up
   B. The relay trips only when I1 = I2
   C. K is the CT ratio
   D. I0 is the restraining current
   Answer: A. K is the bias slope (about 5-20%) and I0 the minimum pick-up, so the threshold grows with through current. (Key point: Operating condition and limits)

## Related in Switchgear and Protection

- [Percentage differential relay: 125 MVA transformer](https://www.bctengineer.com/question.md?key=semester_6%2Fswitchgear_and_protection%3Apercentage-differential-125mva) — Switchgear and Protection, chapter 7
- [Percentage differential relay: 150 MVA transformer](https://www.bctengineer.com/question.md?key=semester_6%2Fswitchgear_and_protection%3Apercentage-differential-150mva) — Switchgear and Protection, chapter 7
- [Percentage bias in differential relay](https://www.bctengineer.com/question.md?key=semester_6%2Fswitchgear_and_protection%3Apercentage-bias-differential) — Switchgear and Protection, chapter 7
- [Earth fault protection: 20 MVA alternator](https://www.bctengineer.com/question.md?key=semester_6%2Fswitchgear_and_protection%3Aearth-fault-20mva-5-ohm) — Switchgear and Protection, chapter 7
- [Differential protection: 11 kV, 100 MVA generator](https://www.bctengineer.com/question.md?key=semester_6%2Fswitchgear_and_protection%3Agenerator-differential-11kv-6-ohm) — Switchgear and Protection, chapter 7
- [Differential protection of power transformer](https://www.bctengineer.com/question.md?key=semester_6%2Fswitchgear_and_protection%3Atransformer-differential-protection) — Switchgear and Protection, chapter 7

## Related in other subjects

- [Protection for alternator and step-up transformer](https://www.bctengineer.com/question.md?key=semester_8%2Fpower_plant_design%3Amega-project-protection) — Power Plant Design, chapter 4
- [Emf and regulation of 1500 kVA alternator](https://www.bctengineer.com/question.md?key=semester_5%2Felectric_machines_ii%3Aregulation-1500kva-12000v) — Electric Machines II, chapter 1, asked 2×
- [Servo differential equation: ζ, frequency and overshoot](https://www.bctengineer.com/question.md?key=semester_3%2Fcontrol_systems%3Aservo-de-64z) — Control Systems, chapter 3