# CB terms: making, breaking, operating duty

Switchgear and Protection · Chapter 6: Circuit Breakers

- Asked in: 2075 Baisakh, 4 marks
- Video: [SGP210 Circuit Breakers Ratings](https://www.youtube.com/watch?v=OJenX-r3uSw) — Lectures in Electrical Engineering
- Answer checked by Claude Opus 5.5 (high effort) on 2026-10-14
- Page: https://www.bctengineer.com/q/semester_6/switchgear_and_protection/cb-terms-making-breaking-duty
- Whole chapter: https://www.bctengineer.com/md/semester_6/switchgear_and_protection/chapter-6

## Question

Explain the terms related to Circuit Breaker: i) Making Capacity ii) Breaking Capacity iii) Operation Duty iv) Rated Current.

## Short answer

Making capacity is the peak closing current including DC offset, equal to 2.55 times the symmetrical breaking current. Breaking capacity is the rms symmetrical current or √3×V×I in MVA. Operating duty is the specified O–t–CO–t′–CO sequence; rated current is the continuous rms current without exceeding temperature limits.

## Answer

These terms define the ratings of a circuit breaker as per IEC 62271-100 / IS 13118.

#### i) Making capacity
The **peak value of current** that the CB can make (close on to) at rated voltage when closing on a short circuit, including the DC offset of the first cycle. The contacts must withstand the large electromagnetic force at this first peak.
```text
Making current = 1.8 × √2 × I_b = 2.55 × I_b (peak)
```
#### ii) Breaking capacity
The largest current the CB can break at rated voltage under specified conditions. Expressed as the **rms symmetrical breaking current** *I_b* (kA) or as MVA:
```text
Breaking capacity (MVA) = √3 × V(kV) × I_b(kA)
```
Asymmetrical breaking current includes the DC component at contact separation.

#### iii) Operating duty
The **sequence of operations** the CB must perform at rated breaking current, with given time intervals. Standard duties:
- **O – t – CO – t′ – CO**, e.g. O – 3 min – CO – 3 min – CO (non-auto-reclose duty)
- **O – 0.3 s – CO – 3 min – CO** (rapid auto-reclosing duty)

Here O = open, CO = close followed immediately by open, *t* = dead time. The CB must keep its rated breaking capacity throughout this sequence.

#### iv) Rated current
The **rms value of normal current** the CB can carry continuously at rated frequency without the temperature of any part exceeding its permitted limit. Standard values: 400, 630, 800, 1250, 1600, 2000, 2500, 3150 A, etc.

**Example:** a 33 kV CB rated 1250 A, 25 kA, duty O–0.3 s–CO–3 min–CO has breaking capacity √3 × 33 × 25 = 1429 MVA and making capacity 2.55 × 25 = 63.75 kA peak.

## Check yourself

The answer's key points as multiple-choice questions, with the correct option and why.

1. Making capacity of a CB is
   A. the rms value of the normal current
   B. the peak current including DC offset in the first cycle that it can close onto a short circuit
   C. the time to close the contacts
   D. the MVA it can interrupt
   Answer: B. It is a peak value equal to 2.55 x I_b, because the contacts face large electromagnetic force at the first peak. (Key point: Making capacity)

2. Breaking capacity can be expressed as
   A. rms symmetrical breaking current I_b or MVA = sqrt(3) x kV x I_b
   B. peak current x 2.55
   C. normal current x voltage
   D. short time current x time
   Answer: A. It is the largest current broken at rated voltage, given in kA rms or MVA. (Key point: Breaking capacity)

3. In the duty O - 0.3 s - CO - 3 min - CO, what does CO mean?
   A. Close, followed immediately by open
   B. Continuous operation
   C. Current off
   D. Circuit open for long time
   Answer: A. O is open and CO is a close operation followed immediately by an open; the CB must keep its rated breaking capacity through the sequence. (Key point: Operating duty)

4. The rated current of a CB is
   A. the maximum fault current it can break
   B. the rms normal current it carries continuously without exceeding temperature limits
   C. the peak making current
   D. the current it can carry for 3 s
   Answer: B. It is the continuous normal current at rated frequency, e.g. 400, 630, 800, 1250 A. (Key point: Rated current)

## Related in Switchgear and Protection

- [Breaking, making, short-time ratings (500 MVA)](https://www.bctengineer.com/question.md?key=semester_6%2Fswitchgear_and_protection%3Acb-ratings-500a-500mva) — Switchgear and Protection, chapter 6
- [Breaking MVA and making kA (800 A, 33 kV)](https://www.bctengineer.com/question.md?key=semester_6%2Fswitchgear_and_protection%3Acb-breaking-making-800a) — Switchgear and Protection, chapter 6
- [HVDC circuit breaker operation](https://www.bctengineer.com/question.md?key=semester_6%2Fswitchgear_and_protection%3Ahvdc-circuit-breaker) — Switchgear and Protection, chapter 6
- [CB ratings: 2500 A, 1500 MVA, 33 kV](https://www.bctengineer.com/question.md?key=semester_6%2Fswitchgear_and_protection%3Acb-ratings-2500a-1500mva) — Switchgear and Protection, chapter 6
- [CB ratings: 33 kV, 1500 A, 3000 MVA](https://www.bctengineer.com/question.md?key=semester_6%2Fswitchgear_and_protection%3Acb-ratings-1500a-3000mva) — Switchgear and Protection, chapter 6
- [Specifying breaker on 132/66 kV transformer](https://www.bctengineer.com/question.md?key=semester_6%2Fswitchgear_and_protection%3Abreaker-x-specification) — Switchgear and Protection, chapter 6

## Related in other subjects

- [Short circuit MVA of feeder circuit breaker](https://www.bctengineer.com/question.md?key=semester_5%2Fpower_system_analysis_ii%3Afeeder-cb-short-circuit-mva) — Power System Analysis II, chapter 3, asked 2×
- [Boundary layer concept and related terms](https://www.bctengineer.com/question.md?key=semester_3%2Ffluid_mechanics%3Abl-concept-terms-separation) — Fluid Mechanics, chapter 8
- [Reactor to protect circuit breaker of small station](https://www.bctengineer.com/question.md?key=semester_7%2Fpower_plant_equipment%3Areactor-protect-circuit-breaker) — Power Plant Equipment, chapter 4
- [Soil moisture tension and related terms](https://www.bctengineer.com/question.md?key=semester_6%2Firrigation_and_drainage_engineering%3Asoil-moisture-tension-terms) — Irrigation and Drainage Engineering, chapter 2