# Contactor construction and remote control circuit

Switchgear and Protection · Chapter 4: Isolators and Contactors

- Asked in: 2078 Chaitra, 6 marks
- Video: [The Difference Between Contactors And Relays - ELECTROMAGNETIC SWITCHES electricians use](https://www.youtube.com/watch?v=YwAm2D-mm_g) — Electrician U
- Answer checked by Claude Opus 5.5 (high effort) on 2026-10-14
- Page: https://www.bctengineer.com/q/semester_6/switchgear_and_protection/contactor-remote-control
- Whole chapter: https://www.bctengineer.com/md/semester_6/switchgear_and_protection/chapter-4

## Question

Explain the construction and operating principle of contactor. Draw the circuit diagram for remote control of a contactor.

## Short answer

A contactor uses an electromagnetic coil to close main contacts and a spring to open them. For remote control, Start buttons are wired in parallel and Stop buttons in series; a hold-in auxiliary contact maintains the coil after start is released, providing no-volt protection.

## Answer

A **contactor** is an electrically operated switch in which a magnetic coil closes the main contacts and a spring opens them when the coil is de-energised. It is used for frequent on-load switching and remote control of motors and other loads.

#### Construction
- **Coil and laminated core** (electromagnet), AC cores with a shading ring.
- **Armature** carrying the moving contacts through an insulated carrier.
- **Main contacts** (normally 3 NO, silver alloy) for the power circuit.
- **Auxiliary contacts** (NO/NC) for latching, interlocking and indication.
- **Return spring**, **arc chutes/splitters**, moulded **housing** and terminals.

#### Operating principle
1. Control voltage on the coil produces flux; the armature is attracted against the spring.
2. Main contacts close and the load is energised; auxiliary contacts change state.
3. Removing coil voltage lets the spring open the contacts; the arc is extinguished in the arc chute at current zero.
4. Since the coil drops out at low voltage, the contactor also gives no-volt protection.

#### Circuit for remote control of a contactor
START buttons are connected **in parallel** and STOP buttons **in series**, so the motor can be started or stopped from the local panel or from a distant point. The hold-in auxiliary contact K is connected in parallel with the START buttons. Only thin control wires go to the remote station.
```text
 L --[Fuse]--[STOP local]--[STOP remote]--+--------------+--------------+
                 (NC)           (NC)      |              |              |
                                    [START local]  [START remote]   [K aux NO]
                                         (NO)           (NO)          (hold)
                                          |              |              |
                                          +--------------+--------------+
                                                         |
                                                   [OL relay NC]
                                                         |
                                                    ( K coil )
                                                         |
 N ------------------------------------------------------+

 Power: L1,L2,L3 -> fuses -> K main -> OL -> Motor
```
#### Working of the remote scheme
1. Pressing any START button energises coil K; the main contacts close and the motor runs.
2. The auxiliary contact K (in parallel with the START buttons) closes and **holds** the coil after the button is released.
3. Pressing any STOP button opens the series path; the coil drops out and the motor stops.
4. The overload relay NC contact also opens the coil path on overload.
5. Indicating lamps through auxiliary contacts show ON/OFF status at the remote point.

This arrangement allows control of large motors (pumps, fans, cranes) from a control room using low-power control wiring, and safe automatic disconnection on overload or supply failure.

## Check yourself

The answer's key points as multiple-choice questions, with the correct option and why.

1. In remote control of a contactor, how are multiple START buttons connected?
   A. In series
   B. In parallel
   C. In series with the coil neutral
   D. Across the main contacts
   Answer: B. Any START button in parallel can energise the coil. (Key point: START wiring)

2. How are multiple STOP buttons connected?
   A. In parallel
   B. Across the coil
   C. In series, so pressing any one opens the coil path
   D. Through the K auxiliary contact
   Answer: C. Series NC STOP buttons mean any one breaks the circuit. (Key point: STOP wiring)

3. What holds the coil energised after a START button is released?
   A. Remote STOP button
   B. K auxiliary NO contact in parallel with the START buttons
   C. The overload relay
   D. Indicating lamp
   Answer: B. The auxiliary contact closes with the main contacts and bridges the START buttons. (Key point: Holding)

4. What is a main advantage of this arrangement?
   A. Heavy power cables run to the remote station
   B. Only thin low-power control wires go to the remote station
   C. Fuses are not needed
   D. The motor needs no overload relay
   Answer: B. Control circuit carries only coil current, so remote stations need light wiring. (Key point: Advantage of remote scheme)

## Related in Switchgear and Protection

- [Construction and principle of contactor](https://www.bctengineer.com/question.md?key=semester_6%2Fswitchgear_and_protection%3Acontactor-construction-principle) — Switchgear and Protection, chapter 4
- [Contactor for motor control and protection](https://www.bctengineer.com/question.md?key=semester_6%2Fswitchgear_and_protection%3Acontactor-motor-control-protection) — Switchgear and Protection, chapter 4, asked 3×
- [Isolator construction, principle and application](https://www.bctengineer.com/question.md?key=semester_6%2Fswitchgear_and_protection%3Aisolator-construction-principle) — Switchgear and Protection, chapter 4
- [Feeder switching guideline; contactor in place of CB](https://www.bctengineer.com/question.md?key=semester_6%2Fswitchgear_and_protection%3Afeeder-isolator-cb-guideline) — Switchgear and Protection, chapter 4

## Related in other subjects

- [Data logger and remote control block diagrams](https://www.bctengineer.com/question.md?key=semester_2%2Fbasic_electronics_engineering%3Adata-logger-remote-control) — Basic Electronics Engineering, chapter 7
- [Report on road construction in remote Nepal](https://www.bctengineer.com/question.md?key=semester_5%2Fcommunication_english%3Areport-road-construction-remote-nepal) — Communication English, chapter 9
- [Remote control or digital multimeter](https://www.bctengineer.com/question.md?key=semester_2%2Fbasic_electronics_engineering%3Aremote-control-or-dmm) — Basic Electronics Engineering, chapter 7
- [Transformer operating principle and emf equation](https://www.bctengineer.com/question.md?key=semester_4%2Felectrical_machines_i%3Atransformer-principle-emf-equation) — Electrical Machines I, chapter 2, asked 6×